Section 30(13) in Punjab Urban Planning and Development Building Rules, 2018

(13)Meter rooms. - For all buildings 15 m and above in height and in special occupancies, like educational, assembly, institutional, industrial, storage, hazardous and mixed occupancies with any of the aforesaid occupancies having area more than 500 m2 on each floor, provision shall be made for an independent and ventilated meter (service) room, as per requirements of electric (service) supply undertakings on the ground floor with direct access from outside for the purpose of termination of electric supply from the licensee's service and alternative supply cables. The door/ doors provided for the service room shall have fire resistance of not less than two hours.