Section 88 in The M.P. Bhumi Vikas Rules, 1984
88. Requirement of water supply in buildings.
- The requirement of water supply for various occupancies shall be as given in Tables 11, 12 and 13, subject to availability thereof.Table-11"Per Capita" water requirements for various occupancies/use| Sl. No. | Type of occupancy | Consumption per head per day (in litres)subject to availability |
| 1. | Residential | |
| (a) in living units | 135 | |
| (b) Hotels with lodging accommodation (per bed) | 180 | |
| 2. | Educational | |
| (a) Day Schools | 45 | |
| (b) Boarding Schools | 135 | |
| 3. | Institutional (Medical Hospitals) | |
| (a) Number of beds not exceeding 100 | 340 | |
| 3. | Institutional (Medical Hospitals) | |
| (a) Number of beds not exceeding 100 | 340 | |
| (b) Number of beds exceeding 100 | 450 | |
| (c) Medical quarters and hostels | 135 | |
| 4. | Assembly-Cinema theatres, auditoria and like (Per seat ofaccommodation) | 15 |
| 5. | Government or Semi/public business | 45 |
| 6. | Mercantile (Commercial) | |
| (a) Restaurants (per seat) | 70 | |
| (b) other business buildings | 45 | |
| 7. | Industrial | |
| (a) Factories where bath rooms are to be provided | 45 | |
| (b) Factories where no bath rooms required to be provided | 30 | |
| 8. | Storage (including warehousing) | 30 |
| 9. | Hazardous | 30 |
| 10. | Intermediate stations (excluding mail and express stops) | 45 (25)* |
| 11. | Junction stations | 70 (45) |
| 12. | Terminal stations | 45 |
| 13. | International and Domestic Airports | 70 |
| S.No. | Classification of Building | Storage capacity |
| 1. | For tenements having common conveniences | 900 litres net per water closet seat. |
| 2. | For residential premises other than tenements having commonconveniences. | 270 litres net for one water closet seat and 180 liters foreach additional seat in the same-flat. |
| 3. | For factories and workshops. | 900 litres per water closet and 180 litres per urinal seat. |
| 4. | For cinemas, public assembly halls etc. | 900 litres per water closet seat and 350 litres per urinalseat. |
| No. | No. of floors | Storage capacity | Remarks |
| For premises occupied as tenements with common conveniences. | |||
| 1. | Floor 1 (Ground) | Nil | Provided no down-take fittings are installed. |
| 2. | Floor 2, 3, 4, 5 and upper floors | 500 litres per tenement | |
| For premises occupied as Flats or Blocks. | |||
| 1. | Floor 1 | Nil | Provided no down take fittings are installed. |
| 2. | Floor 2, 3, 4, 5 and upper floors | 500 litres per tenement |
| Down take taps | 70 litres each |
| Down take taps | 135 litres each |
| Bath-tubs | 200 litres each |