[Cites 0, Cited by 0]
[Entire Act]
State of Bihar - Section
Section 5 in Schedule for Retail Tariff Rates and Terms and Condition of Supply for FY, 2006-07
5. Shunt Capacitor Installation. - (a) Every LT consumer (except agriculture connection having load upto 5 HP) whose connected load includes induction motor of capacity of 5 HP and above, shall arrange to install low tension shunt capacitors of appropriate capacity at his cost across terminals of his motor (s). The consumer shall ensure that the capacitors installed by him are properly matched with the actual rating of the motor so as to ensure power factor of 90%.
(b)All LT consumers having welding transformers will be required to install suitable shunt capacitor (s) of adequate capacity so as to ensure power factor of not less than 90%.(c)The capacitors shall be of standard manufacture and meet the Bureau of Indian Standards specification.(d)Consumers not complying to above shall be liable to pay a surcharge of 5% (five percent) of the billed amount excluding DPS till the capacitors are installed.(e)Any LT consumer (except agricultural connection having load upto 5 HP) who fails to maintain power factor of 90% in any month shall pay a surcharge of 5% (five percent) of the billed amount excluding DPS till the defective capacitors are replaced and power factor of 90% is maintained.(f)No new supply to LT installations having induction motor of 5 HP and above or welding transformers will be released unless shunt capacitors are installed to the satisfaction of the Board.(g)The appropriate ratings of shunt capacitor to be installed on the motors of different ratings are provided in the "Electric Supply Code" issued by the Commission.Part-B High Tension Supply| System of supply | : | High Tension-Alternating Current, 50 cycles, Three Phase at 11KV/6.6 KV and above. |
| Demand chargeRs./KVA/Month of billing demand | Energy chargesPaisa/KWh |
| 180 | All units-425 |
| Demand chargeRs./KVA/Month of billing demand | Energy chargesPaisa/KWh |
| 175 | All units-420 P. |
| Demand chargeRs./KVA/Month of billing demand | Energy chargesPaisa/KWh |
| 170 | All units-415 |
| Demand chargeRs./KVA/Month of billing demand | Energy chargesPaisa/KWh |
| 750 | All units-135 P |
| Rs.| (| 750 +| 351 x Actual hours of supply630 x Actual hours of supply| ) |
| Demand chargeRs. /KVA/ Month of billing demand | Energy chargesPaise/unit | |
| RTS-I | ||
| 25 KV supply | Rs. 160 | All units-444 P |
| RTS-II | ||
| 132 KV supply | Rs. 160 | All units-438 P |