"8. CONCLUSION Based on the visual, physical, chemical and stereomicroscopic as well as tool mark examination of the remnants of the burnt electric meter, the cause of burning of digital electric meter No. 92301905 installed vide CA No. 60013564905 was:
8.1 not due to electric short circuit caused by defective electrical components or excessive power transmission effects as observed from the steromicroscopic data, 8.2 not on account of deliberate use of ignitable fire accelerants for burning as seen from the results of GC-MS analysis, 8.3 not on account of any other natural calamities such as lightening, thunderstorm etc., 8.4 not on account of burning of premises where the meter was installed as the premises was found unaffected.