"8. CONCLUSION
Based on the visual, physical, chemical and
stereomicroscopic as well as tool mark
examination of the remnants of the burnt electric
meter, the cause of burning of digital electric meter
No. 92301905 installed vide CA No. 60013564905
was:
8.1 not due to electric short circuit caused by
defective electrical components or excessive power
transmission effects as observed from the
steromicroscopic data,
8.2 not on account of deliberate use of ignitable
fire accelerants for burning as seen from the results
of GC-MS analysis,
8.3 not on account of any other natural calamities
such as lightening, thunderstorm etc.,
8.4 not on account of burning of premises where
the meter was installed as the premises was found
unaffected.