meter was installed for the verification of billing pattern of energy meter as the readings in both the energy meter as well as the check ... genuineness of the number seals on the meter and the meter terminal cover have been checked by the HTM wing and found in order
Through that check meter, they can compare the meter reading with the
meter affixed inside the premises ie., the disputed meter and also he
admitted ... occurrence and inspected the meter. At that time, he replaced the old meter
and fixed the new meter. Further he has stated in his evidence
theft.
2. It is the case of the petitioner that the check meter installed in
the petitioner's Ice factory got damaged ... petitioner has paid the requisite fee for installation of
new check meter. The authorities of the respondent Board had inspected
the premises
chance of defect and
furthermore, the meter is tamper proof meter. The respondents would take
meter reading on 26th of every month, after verifying ... both main and check meters, due to non availability of
the meters at TANGEDCO. The same electronic L&T meters are provided
check meter arrangement
was provided after erecting and testing of new 11 KV metering set with revised 5
slot time of day meter at HTSC ... both main meter and check meter. Since the main metering set was declared
as defective, after recording the check metering test values with the main
error in the main meter.
Thereafter, by way of an abundant caution, the main meter and the check
meter were interchanged on 16.07.2010. Thereafter ... Board had contended that continuously this meter was
lagging and showing variance between the main meter and the check
meter. It is not the first
both the dates, the respondent
authorities have found that both the check meter as well as the main
meter are functioning normally and there ... authorities have found that there was no tampering in the
check meter as well as in the main meter. However
consumer may also be allowed to install a check meter after recalibration by the Licensee. Such check ... meter shall be of high quality, high precision and high accuracy and sealed by the Licensee. Whenever the Licensees meter becomes defective the check
during August, 2000, his meter reading checked by A.P.T.S., Electricity Board and the same was inspected by the Assistant Executive Engineer/APTS ... meter had been placed in the existing position and that there was difference in the recording of energy between the existing meter and the check
disposed by order dated
28.10.2005 with directions.
2.3.Thereafter, a check meter was installed by the
Department on 24.10.2005. However, this check meter ... meter recording the electricity consumed was
defective
b) The meter (now in use) which was installed on
10.10.2001 and the check meter which was installed