State of Tamilnadu - Section

Section 3 in The Tamil Nadu Electricity Supply Code, 2004

3. Categories of supply.

- Supply of electricity available to the consumer is of the following categories:
(a)Single-phase 2 wire 240 volts between phase and neutral for supply to a total connected load not exceeding 4,000 watts (including power loads).
(b)three-phase 4 wire 415 volts between phases and 240 volts between phase and neutral for supply to a total connected load exceeding 4,000 watts but not exceeding a demand of 112 KW.
(c)The consumer may elect to avail supply under any one of the above categories where the connected load does not exceed 4,000 watts.
(d)Three-phase 3 wire, 11,000 volts and above between phases for power installation exceeding a demand of 112 KW, the minimum demand however being 63 KVA.