Section 73A(6) in The M.P. Factories Rules, 1962

(6)Explosion panels. - (a) Every oven or drier having an internal total space of not less than half cubic meter shall be provided with suitably designed explosion panels so as to allow release of the pressure of any possible explosion within the oven or drier through explosion vents. The area of openings to be provided by means of such vents together with the area of opening of any access doors which are provided with suitable arrangements for their release in case of an explosion, shall be not less than 2200 square centimeters for every one cubic meter of volume of the oven or drier. The design of the explosion panels and doors as above said shall be such as to secure their complete release under an internal pressure of 0.25 kg per square centimetre.
(b)The explosion releasing panels, shall, as far as practicable, be situated at the roof of the oven or drier or at those portions of the walls where persons do not remain in connection with operation of the oven or drier.