Union of India - Subsection

Section 14(3) in The Static And Mobile Pressure Vessels (Unfired) Rules, 1981

(3)[ Cryogenic pressure vessels .-(i) The design service temperature of the cryogenic pressure vessels shall not be warmer than the normal boiling point of the cryogenic liquid.
(ii)The materials of construction of the inner vessel, its piping and fittings shall be suitable for the service temperature and compatible for the specific cryogenic liquid.
(iii)The outer vessel shall be made of steel not less than 3 mm nominal thickness or of aluminium not less than 4 mm nominal thickness and shall have required structural strength and capable for supporting the inner vessel together with cryogenic liquid, insulation and other fittings. The outer vessel of vacuum insulated cryogenic tanks shall be designed for a minimum collapsible pressure of one atmosphere (gauge). The suitable protecting coating shall be provided on the outer vessel to avoid corrosion. The outer vessel shall also be provided with suitable lifting arrangement and supports for installation or mounting.
(iv)The inner supports between the inner vessel and the outer vessel shall be of non-inflammable materials and capable of supporting the inner vessel together with the maximum allowable cryogenic liquid. The supports shall be able to withstand expansion or contraction within the operating temperature range. Cryogenic pressure vessels meant for transport purpose, shall be able to withstand combined loading of vertical down of two, vertical upward of one and a half, longitudinal of one and a half and lateral of one and a half times the weight of the vessel with attachment and the full load of cryogenic liquid. The factor of safety of the supports shall be as per the design code.