Section 22(1) in The Static and Mobile Pressure Vessels (Unfired) Rules, 2016

(1)Each vessel shall be located with respect to the nearest building or group of buildings or line of adjoining property which may be built on and with respect to other vessels and facilities in accordance with the distances specified in the Tables below:-Table-1Minimum Safety Distances for Corrosive, Toxic or Permanent Flammable Gases
Sl. No. Water capacity of vessel (in litres) Minimum distance from building or group ofbuildings or line of adjoining property Minimum distance between pressure vessels
(1) (2) (3) (4)
(i) Not above 2000 5 metres 1 metre
(ii) Above 2000 but not above 10,000 10 metres 1 metre
(iii) Above 10,000 but not above 20,000 15 metres 1.5 metres
(iv) Above 20,000 but not above 40,000 20 metres 2 metres
(v) Above 40,000 30 metres 2 metres
Table-2Minimum Safety Distances for Non-Corrosive, Non-Flammable or Non-Toxic Gases
Sl. No. Water capacity of vessel (in litres) Minimum distance from building or group ofbuildings or line of adjoining property Minimum distance between vessels
(1) (2) (3) (4)
(i) Not above 2000 3 metres 1 metre
(ii) Above 2000 but not above 10,000 5 metres 1 metre
(iii) Above 10,000 but not above 20,000 7.5 metres 1.5 metres
(iv) Above 20,000 but not above 40,000 10 metres 2 metres
(v) Above 40,000 15 metres 2 metres
Table-3Minimum Safety Distances for Liquefied Flammable Gases
Sl. No. Water capacity of vessel(in litres) Minimum distance from building or group ofbuildings or line of adjoining property Minimum distance between vessels
Above ground Underground or aboveground vessels covered withearth (mound) Above ground Underground or aboveground vessels covered withearth (mound)
(1) (2) (3) (4) (5) (6)
(i) Not above 2000 5 metres 3 metres 1 metre 1 metre
(ii) Above 2000 but not above 7,500 10 metres 3 metres 1 metre 1 metre
(iii) Above 7,500 but not above 10,000 10 metres 5 metres 1.5 metres 1 metre
(iv) Above 10,000 but not above 20,000 15 metres 7.5 metres 2 metres 1 metre
(v) Above 20,000 but not above 40,000 20 metres 10 metres 2 metres 1 metre
(vi) Above 40,000 but not above 3,50,000 30 metres 15 metres 2 metres or 1/4thof the 1 metre
(vii) Above 3,50,000 but not above 4,50,000 40 metres 15 metres sum of diameter of adjacent vessel or ½the diameter of the two adjacent vessels, whichever is greater 1 metre
(viii) Above 4,50,000 but not above 7,50,000 60 metres 15 metres 1 metre
(ix) Above 7,50,000 but not above 38,00,000 90 metres 15 metres 1 metre
(x) Above 38,00,000 120 metres 15 metres 1 metre
Table-4Minimum Safety Distances (in meters) between facilities associated with storage of liquefied flammable gas in petroleum refinery, gas processing plants, storage terminals and bottling plants
(A)For Total Storage above 100 Tonnes
From/ To Storage Vessel Property line/ buildings not associated withstorage and operation Sheds for filling, storage and evacuation ofcylinders Tank Truck loading/ unloading gantry Tank Wagon gantry Pump/ compress or Shed Fire Water Pump room
(1) (2) (3) (4) (5) (6) (7) (8)
Storage Vessel Table 3 Table 3 30 30 50 15 60
Property line/ buildings not associated withstorage and operation Table 3 ----- 30 30 50 30 --
Sheds for filling, storage and evacuation ofcylinders 30 30 15 30 50 15 60
Tank Truck loading/ unloading gantry 30 30 30 30 50 30 60
Tank Wagon gantry 50 50 50 50 50 30 60
Pump/ compressor Shed 15 30 15 30 30 --- 60
Fire Water Pump room 60 --- 60 60 60 60 ---
(B)For Total Storage not above 100 Tonnes
From/ To Storage Vessel Property line/ buildings not associated withstorage and operation Sheds for filling, storage and evacuation ofcylinders Tank truck unloading/ loading gantry Fire Water Pump room
(1) (2) (3) (4) (5) (6)
Storage Vessel Table 3 Table 3 Table 3 15 30
Property line/ buildings not associated with storage &operation Table 3 ----- 15 15 --
Sheds for filling, storage and evacuation of cylinders Table 3 15 15 15 30
Tank truck unloading/ loading gantry 15 15 15 15 30
Fire Water Pump room 30 -- 30 30 --
Table-5Minimum Safety Distances (in metres) between facilities associated with storage and dispensing of liquefied petroleum gas in liquefied petroleum gas dispensing station as automotive fuel to motor vehicles
To/ From LPG Storage Vessels Fill point of LPG Storage vessel and Centre of LPG Tank-Truckunloading hard stand LPG Dispenser Property line Petroleum Class A or B service Station licensed in Form XIVof Petroleum Rules 2002
Fill point of petroleum class A/B tanks Vent pipe of petroleum class A/B tanks Petroleum Class A/B dispensing pump
(1) (2) (3) (4) (5) (6) (7) (8)
LPG Storage Vessels Table 3 9 (aboveground/ mounded vessels exceeding 7,500litres capacity)6 (aboveground/ mounded vessels not exceeding7,500 litres capacity)3 (underground vessel) 9 (above-ground vessels not exceeding 20,000litres capacity or underground/ mounded vessels)15 (above-ground vessels exceeding 20,000 litres capacity) Table 3 9 9 9
Fill point of LPG Storage vessel and Centre ofLPG Tank-Truck unloading hard stand 9 (aboveground/ mounded vessels exceeding 7,500litres capacity)6 (aboveground/ mounded vessels not exceeding7,500 litres capacity)3 (underground vessel) -- 6 9 6 6 6
LPG Dispenser 9 (aboveground vessels not exceeding 20,000litres capacity or underground/ mounded vessels)15(aboveground vessels exceeding 20,000 litres capacity) 6 -- 6 6 6 6
Property line Table 3 9 6 -- 3 4 6
Table-6Minimum Safety Distance for Non-Flammable, Non-Toxic, Cryogenic Liquids And Liquefied Nitrous Oxide
Water capacity of vessel (litres) Between two vessels (meter) Between vessel and any building or adjoining property line orpedestrian passage (meter) Between vessel and flammable structure, naked flame, pipelinecontaining flammable fluids, electric installation or places ofpublic assembly or drain (meter)
(1) (2) (3) (4)
Up to 1,000 0.5 2 3
Above 1,000 but not above 10,000 1 3 5
Above 10,000 1 3 7.5
Table-7Minimum Safety Distances for Liquid Carbon Dioxide
Water capacity of vessel in litres Between two vessels Between vessel and any building or adjoining property line orplaces of public assembly or drain
(1) (2) (3)
Not exceeding 50,000 1 metre 2 metres
Exceeding 50,000 2 metres 4 metres