I
(See rules 4,6,11,12,35,46,49,50,53,54,60,61)A: License Forms, Purposes, Licensing Authority and License Fees
| Sl. No. |
Form of license |
Purpose for which granted |
Authority empowered to grant license |
License Fees |
| 1. |
LS-1A |
To store compressed gas in pressure vessels. |
Chief Controller or Controller authorized by him. |
(a) Where the totalwater capacity of vessels in an installation does not exceed5,000 litres. Rs. 5000.(b) Where the total water capacity of vessels inan installation exceeds 5,000 litres. Rs.5000 litres for thefirst 5,000 litres and for every additional 1,000 litres or partthereof Rs. 2500 subject to a maximum of Rs. 50,000.
|
| 2. |
LS-1B |
To store and dispense auto-LPG in auto-LPGdispensing station as automotive fuel to motor vehicles.
|
Chief Controller or Controller authorized by him. |
Same as the license in Form LS-1A. |
| 3. |
LS-2 |
To transport in a pressure vessel by vehicle. |
Chief Controller or Controller authorized by him. |
Rs. 5000/- |
B: Fee other than license fee
| Sl. No. |
Purpose |
Fees |
| 1. |
Approval or renewal of shop approval to manufacture pressurevessel, vapouriser and fittings under Rule 4 (3) (i) and (ii).
|
5000/- |
| 2. |
Approval of design drawing of pressure vessel, vapouriser &fittings under Rule 4(3) (iii).
|
2500/- |
| 3. |
Import of pressure vessel under Rule 4(5). |
5000/- |
| 4. |
Repairing of pressure vessel under Rule 6. |
2500/- |
| 5. |
Recognition of competent person/inspector under Rule 12. |
5000/- for both |
| 6. |
Approval of vehicle mounting drawing for transport ofcompressed gas under Rule 35(2).
|
2000/- |
| 7. |
Prior approval of specification and plans of vessels andpremises under Rule 46.
|
2000/- |
| 8. |
Issue of authenticated copy of license under Rule 49(3). |
1000/- |
| 9. |
Prior approval of alternation in the licensed premises underRule 53(2).
|
2000/- |
| 10. |
Amendment of license under Rules 54(1). |
1000/- |
| 11. |
Transfer of license under Rule 54(2). |
1000/- |
| 12. |
Issue of new license in case of death or disability oflicensee under Rule 60(2).
|
1000/- |
| 13. |
Issue of duplicate copy of license under Rule 61. |
1000/- |
II
(See rule 29)Design, construction, testing and maintenance of dispenser, its pipe connections and installation of auto-LPG dispensing station(A)Storage capacities:-Maximum water capacity of individual vessel shall be limited to 20 M3 , number of Vessels shall not exceed two in an installation and shall be designed for a pressure of not less than 14.5 Kg/sq. cm.. Not more than two unloading of road tanker shall be undertaken at the dispensing station per day.(B)The ALDS may be installed in the existing MS/HSD dispensing stations or in separate installations. The installation, operating procedures, inspections, maintenance, training, emergency plan & procedure for Auto LPG dispensing stations shall be prepared and enforced by the operator. The preventive maintenance schedule and periodic inspection of various equipments shall be carried out by the operator and the records shall be maintained. The safety distances between various facilities shall be as per the Table 5 of Rule 22.(C)The Mobile Tanker unloading for ALDS shall be done using hose with automatic closing arrangement on both ends of the hose (smart hose), so that no release of liquid LPG takes place at the end of unloading. Alternatively, loading arms can be provided. The hose shall not be more than 5.5 m in length and shall conform to recognized Indian or International standard. The unloading shall be undertaken during the lean hours of morning and afternoon with each unloading process not exceeding 60 minutes. Mobile LPG Tanker shall be parked on a hard stand and shall be in drive out position while unloading the product.(D)Venting of LPG shall not be permitted at the ALDS during unloading operation. During the periodic test under rule 19, the LPG shall be evacuated into a mobile evacuation vessel. Venting during maintenance & commissioning shall be only under supervision of an officer of the auto LPG operator. These operations shall be conducted only in the normal working hours. Venting for priming a pump shall not be permitted.(E)Suitable provision shall be available for emergency evacuation of the LPG from the underground vessel into Mobile Evacuation Facility and for periodic inspections.(F)Cathodic protection: The tank shall be provided with cathodic protection. The competent person engaged for certification under Rule 33 shall verify the design, oversee the installation of cathodic protection, witness the pre-commissioning and post commissioning results and based on his observations shall certify the adequacy of such cathodic protection in his certificate.(G)Nozzles on the vessel: Each vessel shall be provided with 2 circular manholes located on top of the vessel having internal diameter 600 mm and 350 mm respectively. The nozzles should be provided for following functions-(i)Two nozzles for installation of safety relief valves.(ii)One nozzle for installation of mechanical level gauge of Rochester type.(iii)One nozzle for electronic level gauge.(iv)One nozzle for installation of level gauge for maximum level alarm or for installation of high level switch.(v)One nozzle for installation of submersible pump or pump suction in case of above ground pump.(vi)One nozzle for installation of arrangement for isolating well of submersible pumps.(vii)One nozzle for liquid inlet from road tanker.(viii)One nozzle for liquid return line from dispenser and vapour outlet line.(ix)One nozzle for drainage of water.(x)Arrangement for installation of pressure gauge may be provided in the vapour return line.(H)Liquid level measurement : Auto LPG tanks should be provided with one mechanical type of level gauge i.e. Rochester gauge and another of a failsafe electronic type. The fail safe electronic gauge should be of a magneto restrictive type. The display as well as power source for the gauge should be installed in a safe area in the sales room, the interconnection between the two being through a suitable zener barrier/galvanic isolation. The maximum level indicator however should be an independent gauge or a level switch and the same should be integrated with a alarm in addition to an automatic tripping arrangement which shuts all ROV's and pumps.(I)Fire safe valves:-All valves installed in ALDS including block valves shall be of 'fire safe' type designed to meet the requirements of API 607 or equivalent in this respect. Such valve by its construction or special protection should remain tightly shut off when exposed to fire.(J)Remote operated valves:-The remote operated valves should be equipped with an open and closed position indicator and should be of fail safe design, set to close within a maximum of 30 seconds. No manual operation should be possible other than with special tools which shall not be available with the operating personnel.(K)Auto LPG Storage Installation:-The underground Auto LPG storage area and above ground piping above it shall be surrounded by a kerb brick wall of minimum 20 cms. thickness and of 30 cms. height. This wall should extend along the entire periphery of the storage area without any break, maintaining a minimum of 3 m. distance from the edge of vertical projection of the underground vessel. Wire fencing shall be laid over this kerb wall so that the combined height of the wall and fencing is not less than 2 m. This fence should be of a sturdy metal meshwork of 50 mm max. mesh, made of wire of at least 2 mm thickness welded in a framework of 50 mm pipes. Two doors should be provided along the fence, each being located on the opposite side of the fencing. The area inside the fence shall be paved with either tiles or concrete. The end of filling pipe leading to the underground vessel should be located at a suitable point just inside the fenced area but accessible from outside in a manner that it is safe from inadvertent damage from vehicles moving outside the fenced area.(L)Auto LPG dispenser and piping:-(i)The type of the dispenser used for dispensing liquefied petroleum gas shall conform to specification and be of a type approved by the Chief Controller.(ii)The dispenser shall be provided with an excess flow valve, a remote operated shut-off valve and a pipe shear or other suitable provision in that order in the liquid inlet pipe.(iii)The dispenser shall be installed on a firm foundation with provision of bollards to protect against physical damage.(iv)A breakaway device with excess flow valves or quick action cut-off valves on both sides of the breakaway device conforming to Underwriters Laboratory, USA, specification number 567 or equivalent shall be provided on the delivery hose so as to prevent spillage of liquefied petroleum gas from both sides of the breakaway point in the event of its breakage.(v)The dispensing nozzle at the end of the hose shall be of self sealing type and suitable for matching with filler connection of cylinders fitted to vehicles as fuel tanks, as specified in standard or code accepted by the Chief Controller.(vi)The hose for delivery of auto LPG by the dispenser to motor vehicles shall be suitable for auto LPG. The design pressure of the hose shall be minimum twenty five kilograms per square centimeters with a safety factor of five and shall be tested at one and half times of the design pressure at an interval not exceeding one year. The hose shall be electrically and mechanically continuous.(vii)The length of the hose connected to the dispenser shall not exceed five meters and fifty centimeters.(viii)Clearly identified switches and circuit breakers shall be provided at easily accessible location not less than six meters away from the dispenser to cut-off power supply in the event of fire, accident or other emergency. The switches or circuit breakers shall be visible from point of dispensing auto LPG to motor vehicles.(ix)Every dispensing unit from which auto LPG introduced into the containers fitted to the motor vehicles, shall be equipped with self sealing type fueling nozzle from which the liquid released on disconnection shall not exceed five millimetres.(x)All metallic auto LPG piping shall be rated for auto LPG and designed to American Standard ASME-B-31.3 with minimum design pressure of twenty five kilograms per square centimetres with a factor of safety of four. The materials of pipe shall be low carbon or alloy-steel conforming to American Standard SA-333 grade 6, or SA-106 grade B Schedule 40 (for above ground) or Schedule 80 (for underground), or equivalent. The pipeline shall be tested at one and half times of design pressure if hydraulically tested or ten percent in excess of design pressure, if pneumatically tested. Joints of pipeline above forty millimetres diameter shall be welded or flanged. Threaded or screwed connection shall not be provided except for special fittings like excess flow valve, pump connections up to fifty millimetres diameter. Wherever threaded joints are used, a seal weld shall be provided. All threaded joints and socket weld pipe fittings shall be rated at least 3000 lb to BS 3799 or at pressure class 3000 to ASME B16.5 or equivalent. All flanged joints shall be rated at least class 300 to BS 1560: Part 2 or ASME:B:16.5 or equivalent.(xi)Piping shall be protected against physical damage, collision or corrosion.(xii)Entire piping system including the appurtenances shall wherever possible be constructed with welded joints and wherever necessary with flanged joints. The number of flanged joints shall be kept down to a minimum.(xiii)Piping shall run directly as far as practicable between points with as few restrictions with elbows or bends as possible.(xiv)Provision shall be made in piping to compensate for expansion, contraction, jarring and vibration. Flexible piping connections shall be introduced into fixed piping systems wherever necessary to compensate for vibration etc. or where a rigid connection is not practical. Flexible connection shall be short not exceeding 500 mm in length and shall be of approved metallic construction suitable for auto LPG and braided on outside with stainless steel wire. The design parameters for flexible piping connections shall be identical to other piping. Non-metallic pipe, tubing or hose shall not be used for permanent connection to storage vessels.(xv)All gaskets shall be of flexi-metallic type.(M)Management and Operation of Auto LPG Dispensing Stations. - The company intends to operate Auto LPG dispensing station shall meet the following criteria for considering recognition by the Chief Controller, it shall -(i)Be a registered company.(ii)Possess requisite rating under Auto LPG Control Order.(iii)Possess a background of operating and managing a business activity.(iv)Have sufficient in-house specialists well conversant with-(a)Knowledge and experience in installation of auto LPG equipments, their operations, maintenance & in training of personnel.(b)Auto LPG regulations and the hazards associated.(c)Codes of practice relating to setting up auto LPG stations.(d)Number of such personnel engaged by the company shall be related to the stations proposed to be put up by the company.(v)Have professional administration and organization with clear levels of responsibility.(vi)Take responsibility for the professional skills of its personnel.(vii)Have a firm arrangement with auto LPG supplier for un-interrupted supply of LPG of Auto LPG specification to the company stations.(viii)Have a firm arrangement with installer for installation and maintenance of its stations. The period of such arrangement should be specified.(ix)Have a well laid out policy with regard to selection and management of its dealers or franchisees.(x)Take responsibility of operations, periodic maintenance and breakdown maintenance in the stations and enters into a legal agreement with its dealers in this respect.(xi)Take responsibility in selection and training of Managers and operators of Auto LPG dispensing station of its franchisees/dealers and enter into a legal agreement with its dealers in this respect.(N)Emergency Plan. - Every Auto LPG dispensing station shall have a written emergency plan in place to control the hazards from serious auto LPG leakage or fire. The plan must be drawn in consultation with local authorities i.e. fire services. This plan should contains instructions for emergency shutdown of the station, warning to customers and other people in the surrounding, calls for assistance, usage of fire fighting equipments among others. The plan shall be tested from time to time for evaluation of its adequacy and shall be updated and modified as required.
III
[See rules 19(4), 21(9), 21(14) and 23(7)]Underground and Mounded Vessels(Design, fabrication, installation, operation, maintenance and periodic inspections)A. Mounded Vessels Installation - The Mounded vessel installations are categorized in the following categories:(a)Category 1 : Upto 100 KL water capacity of each vessel(b)Category 2 : Above 100 KL and upto 500 KL water capacity of each vessel(c)Category 3 : Above 500 KL water capacity of each vessel1. Design code for design and fabrication of the Vessel shall be as per BIS 2825, ASME Section VIII Div. 1 or Div. 2 or PD 5500 or any other standard accepted by the Chief Controller. A single code shall be applied for design, fabrication, inspection and testing. Specific considerations shall be given for internal pressure, internal vacuum and external loading. Design pressure shall be adequate for vapour pressure at 55 deg C plus static head. The design shall also include a minimum corrosion allowance of 1.5mm and stress relieving of complete vessel irrespective of its thickness.
2. In case of LPG, design pressure shall be 14.5 Kg/sq. cm at top of the vessel & temperature of -27OC to + 55OC and the material selection in case of refinery installation shall be suitable for the traces of hydrogen sulphide.
3. The installation shall conform to a recognized Indian or International standard accepted by the Chief Controller. The vessels shall be placed horizontally and the central axis of the vessels shall be parallel to one another and inter distance between the vessels, distance of boundary line of the installation shall be as per the Table 3. A road/clear area of width (See Table A of this schedule) on three sides shall be provided around the mound for moving and firefighting equipment. The facilities like pump house, compressors and firefighting equipments shall be located at a distance from the edge of the vessels as per the Table A of this schedule.
4. The mounded pressure vessels installation shall be done on concrete or compacted sand base foundation. The selection of the type of foundation shall have considerations for sufficient load bearing capacity, depending on the site conditions and the soil mechanics. In case bottom nozzle has been provided for the vessel, an access to the connection, like a tunnel opening of minimum 0.9 m X 1.2 m shall be provided. The bottom level of the vessel shall be above the top of the inspection tunnel. The bottom connection shall be an integral part of the vessel, and shall extend beyond the mound, and shall be at least 3 m from the edge of the Vessel. The bottom outlet pipe connection shall have a slope of 1.5 deg at the end of which a remote operated valve shall be provided.
5. The mound shall be of earth, sand or other non-combustible material of a thickness (as per Table A of this schedule) of the cover for the vessel. The cover material shall be free from any abrasive particles that may damage the anti-corrosive coating provided on the vessel. The mound shall provide adequate protection from the thermal radiation, and shall be sufficiently robust to remain in place in the event of jet flame impingement. The mound shall be protected from erosion, caving in from water seepage and provided with a protective hard cover or lining. The mound and the top surface of the mound shall have proper facility to drain the rain water. Reference points for the settlement of the vessel and the foundation shall be provided and monitoring of the settlement if any shall be done on yearly basis.
6. The external surface of the vessels shall be suitably protected from corrosion by providing suitable external coatings and cathodic protection. The design shall conform to NACE RP 169 or any other standard accepted by the Chief Controller. The protected vessel shall be isolated from the unprotected structures and piping. The calculated life of the cathodic protection shall not be less than 15 years, considering coating defect of minimum 30% on vessel surface. The monitoring of the cathodic protection shall be on a yearly basis and records maintained.
7. Vessels shall be provided with fire safe remote operated valves (ROVs) at the first flange on the liquid lines and the closing time shall not exceed 30 seconds. Each vessel shall be provided with minimum two types of level indicators of which one shall be electronic with High level switch and shall indicate a remote display of the level at the fill point, one additional independent high level switch shall be provided for the Category 3 type of the vessel, two safety relief valves (SRVs), pressure and temperature measuring instruments. All the safety fittings and instrumentation shall be provided on a dome or the manhole cover provided on the shell of the vessel. There shall be adequate size of the manhole not less than 600 mm. Category 2 and 3 type of vessel shall have at least two manholes each of size 600 mm provided on the vessel. The outlet of the SRVs may be connected to a flare system where available or vented vertically up into the atmosphere with vent pipe not less than 3 M from the top of the mound.
8. Provision shall be made for Gas leak detection system. Fire fighting facility shall be provided with fire hydrant or monitor (See Table A of this schedule) in addition to the Water sprinklers to provide a water cover to the exposed surfaces of the vessel and pipelines. Such hydrants and monitors shall not be located within the distances specified in Table A from the exposed surface of vessel, fittings and pipelines. In addition minimum 2 Nos. of fire extinguishers of capacity 75 Kgs. and shall be placed in an accessible position to operate.
9. The mounded Vessels installation shall be inspected and certified by an inspector at every important stage of construction, including the design and fabrication of the vessel, foundation, mound covering, cathodic protection, NDT and hydraulic testing of vessels and piping and final certification of safety under Rule 33.
10. The vessel shall be subjected to internal inspection once in 5 years under Rule 19 and shall include the Non Destructive Tests comprising of ultrasonic thickness measurement check evenly spread over the entire inner surface including both dish ends and the openings, 100% wet fluorescent magnetic particle test of all weld joints, ultrasonic flaw detection of welds not less than 25% of weld seams including all the T-joints of middle circumferential seams and both dish ends weld seams & nozzle joints, liquid penetrant inspection of all the fillet welds, nozzle joints, hardness test randomly on circumferential and longitudinal welds including parent metal and nozzle welds from inside, heat affected zone and the weld beads on all the plates and joints. Alternatively, other established NDT techniques such as acoustic emission testing may be used with prior approval of Chief Controller. The vessel shall be tested pneumatically at a pressure of not more than the design pressure held for 30 minutes.
11. The vessels shall be subject to hydraulic test pressure as per the design code in addition to the above nondestructive tests once in 10 years, or when subjected to any repairs involving hot work. Settlement of the vessel, if any, shall be measured during the first water fill.
12. The safety relief valves shall be inspected and tested under Rule 18 once in a year and the excess flow valves and the remote operated valves shall be inspected and tested once in 5 years during the periodic test under Rule 19.
Table ACategories for Above Ground Covered with Earth (Mounded) Vessel
| Category No. |
Water Capacity of each vessel (KL) |
Clear Width around Mound (M) |
Distance of facilities such as pump room,vapouriser etc. from the edge of the vessel (M)
|
Minimum thickness of the earth cover (M) |
Independent high level gauges requirement |
Minimum numbers and location of Fire Hydrant/Monitor
|
Manhole of minimu m sizes 600 mm |
| 1. |
Upto 100 KL |
3 |
4.5 |
0.5 |
No |
1 No. 15 M |
1 no. |
| 2. |
Above 100 KL-Upto 500KL |
3.5 |
9 |
0.7 |
Yes |
2 Nos. 15 M |
2 nos. |
| 3. |
Above 500 KL |
3.5 |
15 |
0.7 |
Yes |
As per OISD I50 |
2 nos. |
B. Underground Pressure Vessel Installation for Industrial use and Auto LPG Dispensing Stations (ALDS)1. Design code for design and fabrication of the vessel shall be as per BIS-2825, ASME Section VIII Div.1 or Div. 2 or PD 5500 or any other standard accepted by the Chief Controller. A single code shall be applied for design, fabrication, and inspection & testing. Specific considerations shall be given for internal pressure and external loading. Design pressure shall be adequate for vapour pressure at 55 deg C plus static head.
2. The design shall also include a corrosion allowance of 1.5mm and stress relieving of complete vessel irrespective of its thickness.
3. The underground vessels shall be placed within a concrete or brick masonry pit with a distance of 1 mtr between the walls of the pit and the vessel and inter distance between the vessels. Soil cover of at least 500 mm shall be provided over the top surface of the vessel. The vessels shall be installed on a firm RCC foundation and anchored adequately to prevent the floatation of the vessel due to up-lift force of buoyancy in case of a worst scenario of no load of the product and overburden. The designer/fabricator of the vessel shall furnish for prior approval in addition to mechanical design documents and drawings, the civil design drawings and documents and calculations duly vetted by an inspection agency to substantiate that the foundation, securing and anchoring arrangements of the vessel is designed to maximum loading as well as to prevent floatation of the tank considering worst scenario of no load of product and overburden.
4. The external surface of the Vessels shall be suitably protected from corrosion by providing external coatings and cathodic protection. The design shall conform to NACE RP 169 or any other standard acceptable to Chief Controller and shall consider negative cathodic potential of not more than (-) 850 mV and not less than (-) 1200 mV between the vessel surface and the electrolyte, the potential being measured with reference standard copper/copper sulphate reference cell. A minimum polarized shift of (-) 100 milli volts shall be maintained between the native state of the vessel and cathodically protected vessel. The protected vessel shall be isolated from the unprotected structures and piping. The calculated life of the cathodic protection shall not be less than 15 years, considering coating defect of minimum 30% on vessel surface. The monitoring of the cathodic protection shall be done on a yearly basis and records maintained
5. The underground vessels installation shall be undertaken by the recognized installers and inspected and certified by an inspector at every important stage of construction, including the design and fabrication of the vessel, foundation, mound covering, cathodic protection, NDT and hydraulic testing of vessels and piping and final certification of safety under Rule 33.
6. Each storage vessel shall have at least two safety relief valves, two independent level indicating devices of which one shall be electronic with High level switch and shall indicate a remote display of the level at the fill point, suitable arrangement for water draining etc. remote operated valves (ROVs) shall be provided on all liquid and vapour lines connected to the storage vessel that is, filling, discharge, pump by pass and vapour return lines except those of safety relief valves and drain lines and instruments with trappings and those not exceeding 3 mm for liquid and 8 mm for vapour. ROVs shall be operable from LPG unloading area/sales room/control panel and the dispenser operating area. Additional isolation valves shall be provided at shortest distance from ROVs. The ROVs shall have closing time of not more than 30 seconds.
7. Excess flow check valve (EFCV) shall be provided on all the liquid lines (above 3 mm) and vapour lines (above 8 mm) except those of safety relief valves, drain lines and instruments. Closing flow rate of EFCV shall not be more than 20% of the rated flow of the line.
8. Fill point shall be provided with non-return valve and quick shut off isolation valve.
9. Proper arrangement shall be made for earthing and bonding of the road tanker.
10. Vent pipes shall have 3 M height and 6 M away from source of ignition.
11. ALDS with underground and mounded LPG storage vessels shall have two 75 Kg and two 9 Kg DCP fire extinguishers. At ALDS with above ground LPG Vessels, hydrants with minimum water pressure of 7 Kg/sq. cm. shall be provided at convenient location for all round coverage of the storage vessels and handling area, and water sprinklers with spray density of 10 lpm. The fire water shall be preferably diesel driven with capacity to deliver water at rate and pressure specified above. The minimum fire water storage at the premises shall be that needed for fighting fire at least for one hour.
12. The vessel shall be subjected to internal inspection once in 5 years, and shall include the Non Destructive Tests comprising of ultrasonic thickness measurement check evenly spread over the entire inner surface and the openings, 100% wet fluorescent magnetic particle test of all weld joints, ultrasonic flaw detection of all the T-joints, Liquid Penetrant Inspection of all the fillet welds, nozzle joints. The vessel shall be tested pneumatically at a pressure of 1.1 times the design pressure. The pressure shall be held for 30 minutes.
13. The vessels shall be subjected to hydraulic test pressure as per the design code in addition to the above nondestructive tests once in 10 years, or when subject to any repairs involving hot work.
14. The safety relief valves shall be inspected and tested under Rule 18 once in a year and the excess flow valves and the remote operated valves shall be inspected and tested once in 5 years during the period test under Rule 19.
15. The periodic testing under Rule 19 to be conducted for a multi-vessel installation shall be so conducted that both the vessels are tested simultaneously.
16. The underground vessels or aboveground vessels covered by earth mound shall-
(i)have the discharge level of the safety relief valves at least 2 meters above the top surface of the vessel, but in any case not less than 3 meters from the ground level;(ii)be fitted with the necessary piping, fittings, valves and other mounting on top of vessel in such a manner that they can be operated and maintained without disturbing the earth cover. In case of above ground vessel with earth cover (mound), liquid outlet pipe at the bottom may be allowed provided the control valve and emergency valve of this line is just outside the earth cover for the purpose of operation and maintenance from outside.
IV
[See Rule 21 (15)]LNG storage, Transportation and HandlingThese provisions shall apply to the following -(A)The requirements of the design, fabrication and installation and commissioning of LNG storage facility using cryogenic vacuum insulated containers of double wall constructed in accordance with approved pressure vessel codes.(B)The requirements of the road transportation of LNG in a cryogenic double walled vacuum insulated pressure vessel for the safe transportation and handling.(C)The requirements for safe vaporization, transfer and handling.(D)Training of personnel handling the above equipments and facilities.Section 1Storage InstallationsA. Installation Design:1. (a) For LNG cryogenic pressure vessels storage installation, the minimum safety distances between the vessel and to the nearest building or line of adjoining property shall be in accordance with the distances specified in Table 3 under rule 22 of these rules. The maximum aggregate capacity of each such LNG installation shall not exceed 1060 m3.
(b)For non-pressurized LNG storage installation, the minimum safety distances specified in NFPA 59A, as amended from time to time, may be followed.2. The LNG installation shall be designed to withstand the following without loss of structural or functional integrity-
(a)The direct effect of wind forces;(b)Loading due to seismic effect;(c)Erosive action from a spill;(d)Effect of the temperature, any thermal gradient, and any other anticipated degradation resulting from sudden or localized contact with LNG.3. The structural members of the impoundment system must be designed and constructed to prevent impairment of the impoundments reliability and structural integrity as a result of the following
i) Imposed loading from full hydrostatic head of impounded LNG;ii) Hydro dynamic action from injected material.4. Impoundment or dyke areas must be designed so that all areas drain completely to prevent water collection. Drainage pumps and piping must be provided to remove water from collecting in the impoundment area. Where automatically controlled drainage pumps are used they shall be provided with cut off devices that prevent their operation when exposed to LNG temperature.
5. The impounding system for LNG storage vessel must have a minimum volumetric liquid capacity of -
(a)Maximum liquid capacity of vessel for an impoundment serving a single vessel;(b)100% of the largest vessel's maximum liquid capacity.6. The height of the impoundment wall shall be adequate to contain spillage of any LNG. A minimum height of 1 m. is recommended for the impoundment/dyke wall.
7. No other flammable liquid or storage vessel shall be located within an LNG impounding area.
8. A clear space of at least 0.9 mtrs. shall be provided for access to all isolation valves serving multiple vessels. The isolation valve of LNG tank piping should be as close to outer vessel as possible.
9. LNG vessels, cold boxes, piping and pipe supports and other cryogenic apparatus installed within dyke shall be designed and constructed in a manner to prevent damage to these structures and equipments due to freezing or frost heaving in the soil.
10. Proper lighting arrangement shall be done for facilities transferring LNG during night.
11. Electrical grounding and bonding shall be provided.
12. Lightning protection shall not be required on LNG storage containers except that lightning protection ground rods shall be provided for tanks supported on non-conductive foundations.
B. LNG Storage Vessel - General design requirements:1. LNG vessels foundations shall be designed by a qualified engineer and constructed in accordance with recognized structural engineering practices. Prior to the start of design and construction of the foundation, a subsurface investigation shall be conducted by a qualified soil engineer to determine the stratigraphy and physical properties of the soil underlying the site.
2. The design of saddles and legs for the LNG vessel shall include erection load, wind loads and thermal loads.
3. Foundation and support shall have a fire resistance rating of not less than two hrs.
4. LNG vessels installed in areas subject to flooding shall be secured to prevent release of LNG or floatation of the vessel in the event of a flood.
1. The vessel meant for storage of LNG including piping between inner and outer vessel shall be designed in accordance with ASME Section VIII Div. 1 or Div. 2/EN13458/ASME:B.31.3, process piping or equivalent code acceptable to Chief Controller.
2. The inner vessel shall be designed for the most critical combination of loading resulting from internal pressure and liquid heads. The inner vessel supports system shall be designed for shipping, seismic, and operating loads.
3. The outer vessel shall be equipped with a relief or other device to release internal pressure and shall have discharge area of at least 0.0034 cm2/kg of the water capacity of the inner vessel but not exceeding 2000 cm2 and have pressure setting not exceeding 25psi..
4. Thermal barriers shall be provided to prevent outer tank from falling below its design temperature.
5. Those parts of LNG vessels which come in contact with LNG and all materials used in contact with LNG or cold LNG vapour shall be physically and chemically compatible with LNG and intended for service at -1620C.
6. All piping that is a part of LNG vessel including all piping internal to the container, within void space, and external piping connected to the vessel up to the first circumferential external joint of the piping shall be in accordance with ASME Boiler and Pressure Vessel Code, Section VIII or ASME B 31.3 or equivalent.
7. LNG vessels shall be designed to accommodate both top and bottom filling unless other positive means are provided to prevent stratification.
8. Any portion of the outer surface area of an LNG vessel that could accidentally be exposed to low temperatures resulting from the leakage of LNG or cold vapour from flanges, valves etc. shall be intended for such temperatures or protected from the effects of such exposure.
9. Seismic loads shall be considered in the design of the LNG vessel support systems.
C. Fitments :1. Each LNG double walled vessel shall have at least 2 Nos. of safety relief valves capable of achieving the required relief capacity on standalone basis and shall be sized to relieve the flow capacity determined for the largest single contingency or any reasonable and probable combination of contingencies and shall include conditions resulting from operational upset, vapour displacement and flash vaporization.
2. Relief devices shall be vented directly to the atmosphere. Each safety relief valve for LNG vessel shall be able to be isolated from the vessel for maintenance or other purposes by means of a manual full opening stop valve.
3. Safety relief valve shall be designed and installed to prevent any accumulation of water, or other foreign matter at its end.
4. The minimum pressure relieving capacity in kg/hr shall not be less than 3% of the full tank contents in 24 hrs.
5. All liquid connections to the LNG vessel except relief valve and instrumentation connection shall be equipped with automatic fail safe product retention valves.
6. The automatic shut off valves shall be designed to close on occurrence of any of the following conditions:
(ii)Uncontrolled flow of LNG from vessel;(iii)Manual operation from a local and remote location.7. Such of the automatic shutoff valves that require excessive time to operate during emergency i.e. sizes exceeding 200 mm shall be pneumatically operated and also have means of manual operation.
8. All LNG vessels shall have a device that prevents the vessel from becoming liquid full or from covering the inlet of the relief valve with liquid when the pressure in the vessel reaches the set pressure of relieving device under all conditions.
9. Every LNG vessel may be provided with one independent high liquid level alarm which may be part of the liquid level gauging devices. However, the high liquid level flow cut-off device shall not be considered as a substitute for the alarm.
10. Every LNG vessel shall be equipped with at least one liquid level gauging device. The devices shall be designed and installed so that they can be replaced without taking the tank out of operation.
11. Each LNG vessel shall be equipped with a high liquid level flow cut-off device,
12. Each LNG vessel shall be equipped with pressure gauge connected to the vessel at a point above the maximum intended liquid level.
13. Instrumentation for storage and vaporization facilities shall be so designed so that if a power or instrument air failure occurs, the system will proceed to a fail safe condition and maintain that condition until the operator takes appropriate action to reactivate or secure the system
D. Equipment :1. Pumps and compressors employed in LNG source shall be provided with a pressure relieving device on the discharge to limit the pressure to the maximum safe working pressure of the casing and downstream piping and equipment.
2. Each pump shall be provided with adequate vent, relief valve, or both that will prevent over-pressuring the pump case during the maximum possible rate of cool down.
3. The discharge valve of each vaporizer and the piping components and relief valves installed upstream of each vaporizer discharge valve shall be designed for operation at LNG temperatures.
4. Two inlet valves shall be provided to isolate an idle manifolded vaporizer to prevent leakage of LNG into the vaporizer. A safe means of disposing of the LNG or gas that can accumulate between the valves shall be provided in case the vaporisers are of size having inlets more than 50 mm diameter.
5. (i) The ambient air vaporizers should be installed inside the containment area.
(ii)Where the heated vaporizer is located 50 ft (15 m) or more from the heat source, the remote shutoff location shall be at least 50 ft (15 m) from the vaporizer.(iii)Where the heated vaporizer is located less than 50 ft (15 m) from the heat source, it shall have an automatic shut off valve in the LNG liquid line located at least 10 ft (3 m) from the vaporizer and shall close when either of the following occurs -(1)Loss of line pressure (excess flow);(2)The occurrence of a fire is detected by an instrument designed for the purpose and located to detect a fire in the covered area;(3)Low temperature in the vaporizer.(iv)Any ambient vaporizer or a heated vaporizer installed within 50 ft (15 m) of an LNG container shall be equipped with an automatic shutoff valve in the LNG liquid line -(a)The automatic shutoff valve shall be located at least 10 ft (3 m) from the ambient or heated vaporizer and shall close in either of the following situations -(1)Loss of line pressure (excess flow);(2)Abnormal temperature sensed in the immediate vicinity of the vaporiser (fire);(3)Low temperature in the vaporizer discharge line.(b)If the facility is attended, manual operation of the automatic shutoff valve shall be from a point at least 50 ft (15 m) from the vaporizer, in addition to the requirement as specified above in (a).6. A distance of minimum 1 meter shall be maintained between vaporizers.
7. Vaporisers shall be designed, fabricated and inspected as per the requirements of ASME Boiler & Pressure Vessel Code, Section VIII Division 1. or any other equivalent acceptable code to Chief Controller.
8. Manifolded vaporisers shall be provided with both inlet and discharge block valves for each set of vaporizer.
9. Any ambient vaporiser installed within 15 mtrs. of the LNG vessel shall be equipped with an automatic shutoff valve in the liquid line. This valve shall be located minimum at least 3 mtrs. from the vaporisers and shall close when loss of line pressure occurs or abnormal temperature is sensed in the immediate vicinity of the vaporizer or when low temperature in the vaporizer discharge line occurs.
10. Each set of vaporiser shall be provided with a safety relief valve(s) sized in accordance with the following requirements:
(a)Ambient vaporizers-relief valve capacity shall allow discharge equal or greater than 150% of the rated vaporizer natural gas flow capacity without allowing the pressure to rise 10% above the vaporizer maximum allowable working pressure.(b)Relief valves on heated vaporizers-as above, however it shall be located such that they are not subjected to temperatures exceeding 600C during normal operation.11. Automation shall be provided to prevent the discharge of either LNG or vaporizer gas into a distribution system at the temperature either above or below the design temperature of the send out system.
12. Vaporizers shall be provided with outlet temperature monitors.
E. Piping System :1. All piping system and components shall be designed -
(a)To accommodate the effects of thermal cycling fatigue to which the systems will be subjected.(b)Provide for expansion and contraction of piping and piping joints due to temperature changes.2. Piping material including gaskets and thread compounds shall be compatible throughout the range of temperature to which they are subjected.
3. The valves provided in the installation shall be of extended bonnet type with packing seals in a position that prevents leakage or malfunction due to freezing.
4. Shutoff valves shall be provided for all tank connections except connections for liquid level alarms and connections that are blind flanged or plugged.
5. All the piping section between the two valves where the liquid may be trapped shall have the thermal relief valve.
6. Aluminum shall be used only downstream of a product retention valve in vaporizer service.
F. Transfer of LNG :1. Isolation valves shall be installed so that each transfer system can be isolated at its extremities. Where power-operated isolation valves are installed, an analysis shall be made to determine the closure time so that it does not produce a hydraulic shock capable of causing line or equipment failure.
2. Adequate check valves shall be provided to prevent backflow and shall be located as close as practical to the point of connection to any system from which backflow might occur.
G. Pump and Compressor Control. - In addition to a locally mounted device for shutdown of the pump or compressor drive, a readily accessible, remotely located device shall be provided at least 7.5 mtrs away from the equipment to shut down the pump in an emergency.H. Tank Vehicle Unloading Facilities:1. The tank vehicle unloading area shall be of sufficient size to accommodate the vehicles without excessive movement or turning.
2. Transfer piping, pumps, and compressors shall be located or protected by barriers so that they are safe from damage by vehicle movements.
3. Isolation valves and bleed connections shall be provided at the unloading manifold for both liquid and vapour return lines so that hoses and arms can be blocked off, drained of liquid, and depressurized before disconnecting. Bleeds or vents shall discharge in a safe area.
4. The hose connecting point and center of tanker hard stand shall maintain a minimum of 9 mtr. from the protected boundary
I. Emergency Shut Down System (ESD System) :1. Each LNG facility shall incorporate an ESD system that when operated isolates or shuts off sources of LNG and shuts down equipment that add or sustain an emergency if continued to operate.
2. The ESD system shall be of a fail-safe design and shall be installed, located, or protected from becoming inoperative during an emergency or failure at the normal control system.
3. Initiation of the ESD system shall be manual, automatic, or both manual and automatic. Manual actuators shall be located in an area accessible in an emergency and at least 15 mtrs. away from the equipment they serve, and shall be distinctly marked with their designated function.
J. Fire Protection Facilities :1. Each LNG storage facility shall be provided with continuously monitored low-temperature sensors or flammable gas detectors, which must activate visual and audible alarms at the plant site and at an constantly attended location if the facility is not attended continuously.
2. Flammable gas detection system shall activate an audible and a visual alarm at level not no higher than 25% of the LEL of the gas being monitored.
3. Fire detectors shall activate an alarm at the plant site and at a constantly attended location if the plant site is not attended continuously. If determined by an evaluation that it is necessary then fire detectors shall be permitted to activate the ESD system.
4. A fire water supply and delivery system must be provided, unless the fire protection evaluation indicates that the fire water is unnecessary or impractical.
5. Portable or wheeled fire extinguishers, shall be made available at strategic locations. At least 4 such extinguishers of 10 kg. capacity each shall be provided.
K. Personal Protection. - Fire extinguishers provided in the LNG installations shall be based on high expansion foam and dry chemical powder. Every person operating the equipment in the LNG installation should be equipped with under mentioned personal protective equipments-(i)Suitable goggles for protection of eyes from LNG spray.(ii)Hand gloves.(iii)Protective apron.Section 2Road TransportationA. Design-General Requirements. - The safety relief valves provided on the inner vessel of the LNG transport tank shall be sized to meet most stringent condition of simultaneous occurrence of loss of vacuum and external fire. The combined capacity of the safety valves shall be sufficient to limit the pressure in the vessel to the test pressure -(1)The transport vessel must be designed and constructed as per the ASME Boiler & pressure vessel code, EN13530 or equivalent code approved by Chief Controller and also to meet the requirements of ISO 20421. The design temperature of the vessel, piping and valves shall be such that it is suitable for requirement sustaining cold shock caused by a loading of liquid Nitrogen into the vessel during its testing and commissioning.(2)Each vessel must have adequate insulation that will prevent the vessel pressure from exciting the relief valve set pressure within the specified holding time when the vessel is loaded with LNG at the design condition of -(a)specified temperature and pressure of the LNG:(b)the exposure of the vessel to the average ambient temperature of 400C.(3)The outer vessel/jacket of the cryogenic vessel for transportation of LNG must be made of no other material other than steel.(4)No aluminum valve or fitting external to the wetted outer vessel must be installed on LNG transportation vessels. Each transportation vessel must consist of a suitably supported welded inner vessel enclosed within an outer shell with vacuum insulation between the two.B. Structural Integrity :(1)The static design and construction of each vessel used for transportation of LNG must be made in accordance with section VIII, Div. 1 or Div. 2 of ASME Boiler and Pressure Vessel Code, EN 13530 or any other code approved by Chief Controller. The vessel design must include calculation of stress due to design pressure, the weight of lading, the weight of structure supported by the vessel wall, and the effect of the temperature gradients resulting from lading and ambient temperature extremes.(2)In order to account for stresses due to impact in an accident, the design calculations of the vessel shell and heads must include the load resulting from the design pressure in combination with the dynamic pressure resulting from a longitudinal deceleration of 2g. For this loading condition the stress value used may not exceed the lesser of the yield strength or 75% of the Y.S. of the material of construction.(3)The fittings and accessories mounted on the vessel shall be protected in such a way that damage caused by overturning cannot impair operational integrity. This protection may take the form of cylindrical profile of the vessel, of strengthening rings, protective canopies or transverse or longitudinal members so shaped that effective protection is given.(4)The welding of the appurtenances to the vessel wall must be made of attachment of the mounting pad so that there will be no adverse effect upon the loading retention integrity of the vessel.C. Pressure Relief Devices, Piping, Valves and Fittings :(1)The burst pressure of all piping, pipe fittings, hoses and other pressure parts, except for pump seals and pressure relief devices must be at least 4 times the design pressure of the vessels.(2)If a threaded pipe is used, the pipe and fitting must be Schedule 80 or heavier.(3)Each hose coupling must be designed for a pressure of at least 120% of the hose design pressure and there shall be no leakage when connected.(4)Piping must be protected from damage due to thermal expansion and contraction, jarring and vibration. Slip joints shall not be used.(5)Each valve must be suitable for the vessel design pressure at the vessel design service temperature.(6)All fittings must be rated for the maximum vessel pressure and suitable for the coldest temperature to which they will be subjected in actual service.(7)When a pressure building coil is used on the vessel, the vapour connection to that coil must be provided with a valve or check valve as close to the vessel shell as practicable from the vessel in case of damage to the coil. The liquid connection to the coil must also be provided with a valve.(8)Each vessel shall be rated for its holding time, the holding time being the time as determined by testing that will elapse from loading until the pressure of the contents, under equilibrium conditions reaches the level of the lowest pressure relief valve setting.(9)All the discharge lines of relief valves, vent valve, bleed valves etc should be connected to a vent stack which should vent at a safe height.(10)Bursting discs should not be used on the LNG transport vessels.(11)The outer vessel shall be protected by any accidental accumulation of pressure in the annular space by using a relief plate/plug or a bursting disc. The relief device shall function at a pressure not exceeding the internal design pressure of the outer tank, the external design pressure of the inner tank or 25 psi whichever is less.D. Accident damage protection :(1)All valves, fittings, pressure relief devices and other accessories to the vessels, which are not isolated from the vessel by closed intervening shut off valves or check valves must be installed within the motor vehicle framework or within a suitable collision resistant guard or housing and appropriate ventilation must be provided. Each pressure relief device must be protected so that in the event of the upset of the vehicle onto a hard surface, the device's opening will not be prevented and its discharge will not be restricted. The threaded end connection safety valves are preferred in stainless steel body construction.(2)Each protective device or housing and its attachment to the vehicle structure must be designed to withstand static loading in any direction that it may be loaded as a result of front, rear, side or sideswipe collision or the overturn of the vehicle All the valves of tank shall be at rear inside on operation box (cabinet) of suitable size and does not project out of tank diameter. The thickness of cabinet shall be 3 mm minimum.E. Rear End Protection. - Rear end vessel protections devices must:(1)Consist of at least one rear bumper designed to protect the transport vessel and piping in the event of a rear end collision. The rear end vessel protection device design must transmit the force of the collision directly to the chassis of the vehicle. The rear end vessel protection device and its attachments to the chassis must be designed to withstand a load equal to twice the weight of the loaded cargo vessel and attachments, using a safety factor of four based on the tensile strength of the materials used with such load being applied horizontally and parallel to the major axis of the transport vessel.(2)Every part of the loaded transport vessel and any associated valve, pipe, enclosure or protected fitting or structure must be at least 35.5 cm. above ground level.F. Discharge control devices :(1)Each liquid filling and liquid discharge line must be provided with a shut off valve located as close to the vessel as practicable. Unless this valve is manually operable at the valve, the line must also have a manual shut off valve.(2)Each liquid filling and liquid discharge line must be provided with an on vehicle remotely controlled self-closing shutoff valve.(3)Each control valve must be of fail-safe design and spring-based.(4)Each remotely controlled shut off valve must be provided with on vehicle remote means of automatic closure, both mechanical and thermal.(5)Each remotely controlled shut off valve must be provided with on-vehicle remote means automatic closure, both mechanical and thermal. One means may be used to close more than one remotely controlled valve. Remote means of automatic closure must be installed at the ends of the tanker farthest away from the loading/unloading connection area.G. Shear Section. - Unless the valve is located in a rear cabinet forward of and protected by the bumper, the design and installation of each valve, damage to which could result in loss of liquid or vapour must incorporate a shear section or breakage groove adjacent to and outboard of the valve. The shear section or breakage groove must yield or break under strain without damage to the valve that would allow the loss of liquid or vapour.H. Supports and Anchoring. - In case, the transport tanker vehicle is such designed and constructed that the tank is not wholly supported by the vehicle frame, the transport vessel shall be supported by external cradles or load rings. The design calculations for the supports and load bearing vessel and the support attachments must include beam stress, shear stress, torsion stress, bending moment and acceleration stress for the loaded vehicle as a unit, using a safety factor of four based on the tensile strength of the material and static loading that uses the weight of the transport vessel and its attachments when filled to the design weight of the loading. Minimum static loadings must be maximum of the following individually -(i)Vertically downward of two (2).(ii)Vertically upward of one and half (1½).(iii)Longitudinally of one and half (1½). and(iv)Laterally of one and half (1½).I. Gauging devices :(a)Liquid level gauging devices. - The vessel shall have one liquid level device that provides a continuous level indication ranging from full to empty and that is maintainable or replaceable without taking the vessel out of service(b)Pressure gauges. - Each vessel shall be equipped with a pressure gauge connected to the vessel at a point above the maximum liquid level that has a permanent mark indicating the maximum allowable working pressure of the tanker. The pressure gauge shall be housed in a canopy of the tanker.Section 3A. Operation, Maintenance and Training. - Each LNG installation shall provide for written operating, maintenance and training procedures. Such procedures shall be drawn based on experience, knowledge of similar facilities.B. Basic requirements. - Every installation shall meet the following requirements -(1)Have written procedures covering operation, maintenance and training.(2)Keep up-to-date drawings of plant equipments.(3)Have written emergency plan as part of the operations manual.(4)Shall be in liaison with local authorities like Police, Fire Department, Health Authorities and keep them informed about emergency plans and their role in emergency situations.(5)Have documents wherein safety related malfunctions are identified and analysed for the purpose of determining their causes and preventing the possibility of reoccurrence.C. Operating Procedures Manual. - Every installation shall have a written manual of emergency procedures that shall include a types of emergencies that are anticipated and shall include the following procedures-(1)Start up and shut down procedure including initial start up of the LNG facility.(2)Purging and inserting components.(3)Cooling down components.(4)Identify the possibility of abnormal conditions.(5)Safety precautions requirement to be taken while repairs/maintenance in the installation is being carried out(6)Procedures for responding to controllable emergencies including notifying personnel and use of equipments i.e. appropriate to handling of emergency.(7)Procedure for recognizing an uncontrollable emergency and for taking action to ensure that harm to the personnel in the premises and to the public outside is limited.(8)Procedure for immediate notification of the emergency to the local authorities.(9)Procedure for co-ordinating with local authorities in the preparation of any evacuation plan which may be required to protect the public in the event of emergency.D. Maintenance:(i)Every installation shall have a written procedure based on experience and knowledge of similar facilities and conditions under which the installation shall be maintained.(ii)The procedure shall incorporate the need to carry out periodic inspection, tests on every equipment and system in service to verify that the equipment is maintained in accordance with the equipment manufacturer's recommendations.(iii)The written manual shall set out inspection and maintenance programme for each components forming part of the installation. In addition to fixing a schedule for inspection and tests, the procedure to be followed during repairs so as to ensure safety of persons and property should also be laid down.E. Training. - Every installation shall be provided with a training plan and the manner in which it will be implemented and maintained. The training manual shall comprise of under mentioned components -(1)Procedure of basic operation to be carried out in the installation in the normal course.(2)Carrying out of emergency procedures that relate to duties at the installation for each concerned personnel.(3)The characteristics and potential hazards of LNG during operation and maintenance of the facility, including dangers from frostbite that can result from contact with LNG.(4)The methods of carrying out duties of maintaining and operating the facility as set out in the manual of operating and maintenance procedures.(5)The LNG transfer procedure.(6)Fire prevention, including familiarization with the fire control plan of the installation, fire fighting, the potential causes of fire in a facility, and the types, sizes and likely consequences of a fire in the installation.(7)Recognizing situations in which it is necessary to obtain assistance in order to maintain the security of the facility.
| {| |
| Form-AS-I |
| (See rules 50, 54 and 55) |
|
Application for grant, amendment, transfer or renewal of alicense in Form LS-1A/LS-1B to store compressed gas/Auto LPG invessel or vessels and dispense Auto LPG in Auto LPG DispensingStation as automotive fuel to motor vehicles.
|
|
Documents listed in the note must be enclosedwith this application
|
| The replies to be given in this column. |
| 1. Name in which license is required:* |
|
2. Status ofapplicant(individual/company/partnership/Society):
|
| 3. Licensee's complete postal address with pin code |
|
Phone No.with STD code : Fax No.
|
| Mobile No. |
| Email: |
|
4. Location of the premises where compressed gas in vessel(s)is to be stored:
|
|
(a) Plot/Survey/ Khasra/ Gat No.(s):
|
|
(b) Town/Village:
|
|
(c) Tahsil/Taluka/ Mandal:
|
|
(d) PoliceStation:
|
|
(e) Districtand State:
|
|
(f) PINCode:
|
|
5. Chemical name and nature of compressed gas proposed to bestored:**
|
|
(please state whether flammable, corrosive or toxic or othertype)
|
|
6. Chemical name of compressed gas already stored in thepremises:***
|
|
7. (i) Quantity of the compressed gas/Auto LPG proposed to bestored.**(strike out whichever is not applicable):
|
|
(ii)Quantity of the compressed gas/Auto LPG already stored in thepremises*** (strike out whichever is not applicable):
|
|
(iii)Quantity of Petroleum already stored, if any:
|
|
8. Particulars of the license held for the premises underSMPV(U) Rules and Petroleum Rules, if any and full name of thelicensee:
|
|
I hereby declare that the statements made above have beenchecked up by me and are true and I undertake to abide by theterms and conditions of the license which will be granted to me.
|
| Date of Application |
| Signature & designation of the applicant. |
|
* Where the application is made on behalf of a Company, thename and address of the Company and the name of the Manager orAgent should be given and the application should be signed byhim. Every change in the name of the Manager or Agent shall beforthwith intimated to and his specimen signature filed with thelicensing authority.
|
| ** Applicable for grant of license. |
| *** Applicable for amendment, transfer and renewal case |
| Note: |
| Documents required to be submitted with application |
|
Four copies of specifications and plans approved under rule 46(Not required for renewal of a license without amendment)
|
|
License together with approved plans and specificationsattached thereto (Not required for the first grant of license).
|
|
Requisite amount of fee for the grant, renewal, transfer oramendment of license.
|
|
A certificate of safety if required under rule 33 togetherwith test and inspection certificate and as built design drawingof new vessel duly endorsed by Inspector (in case of installationof new vessel or repair/ modification of any vessel)
|
|}Form-AS-2(See rules 50, 54 and 55)Application for the grant, renewal, transfer or amendment of a license in Form LS- 2 to transport compressed gas in a vehicle
|
Documents listedin note must be enclosed with this application
|
| The replies to be given in this column. |
| 1. |
Name in which license required and full postal address withtelephone No., Mobile No. and E-mail
|
__________________ |
| 2. |
Particulars of the vehicle in which compressed gas is proposedto be transported:
|
__________________ |
| |
(i) Make and Model |
__________________ |
| |
(ii) Engine number |
__________________ |
| |
(iii) Chassis number |
__________________ |
| |
(iv) Registered number |
|
| |
(v) Date upto which the vehicle is registered |
|
| |
(vi) Name and full postal address of the registered owner |
|
| 3. |
Name of the compressed gas proposed to be transported (Pleasestate whether flammable, corrosive or toxic).
|
|
| 4. |
Chemical name of compressed gas to be transported in thevehicle
|
|
| 5. |
Water capacity of the pressure vessel and net weight of thecompressed gas proposed to be transported.
|
|
| 6. |
Number and date of approval of the mounting drawing of thevehicle by the Chief Controller
|
__________________ |
| 7. |
Does vehicle (described above) fully conform to therequirements laid down in the rules and the mounting drawingapproved by the Chief Controller.
|
|
| 8. |
Full postal address of the place where the vehicle will benormally stationed.
|
__________________ |
|
I/ We declare that the particulars given above have beenchecked up by me/ us and are correct. I/ We undertake to transportcompressed gas in the vehicle particulars of which are givenabove, in accordance with the provisions of the Indian ExplosivesAct, 1884 and the Static and Mobile Pressure Vessels (Unfired)Rules, 2016 framed there under and any other law or rule for thetime being in force. I/ We understand that any contravention ofthe said Act and the rules framed there under is punishable withimprisonment for a term which may extend to two years, or withfine which may extend to three thousand rupees, or with both.
|
| Place: |
|
| Date: |
Signature of applicant |
Note:Documents required to be submitted with this application(1)Four copies of drawing approved under Rule 35 and as-built vessel design drawing endorsed by Inspector (required only for grant or transfer or amendment with modifications in vehicle or vessel).(2)Safety certificate required under Rule 43 along with test and inspection certificate of the vessel in original plus two photocopies (required only for grant or transfer or amendment).(3)Original valid license, if the vehicle was previously licensed (required only for renewal, transfer or amendment).(4)Requisite amount of fee for the grant, renewal, transfer or amendment of license as per schedule 1.(5)Copy of the registration certificate of the vehicle issued under the Motor Vehicles Act, 1988 (59 of 1988) and weighment slip in respect of mobile pressure vessels for transport of compressed gas (required only for grant or transfer of license).Form AS-3[See rules 4(5)(a) and 50]Application for the grant of permission to import pressure vessel:1. Name in which license required
Applicant's callingApplicant's full postal addressTelephone No(s) and E-mail2. Particulars of storage license held by the applicant under SMPV(U) Rules, 2016 & Gas Cylinders Rules, 2016 :
(i)Number and date of storage license issued by the Chief Controller/ Controller(iii)Capacity of storage as per above license3. Description of the pressure vessel to be imported:
(ii)Specification of vessel(iv)Inspected and tested by(v)Specification of the safety valves fitted to the vessel including set pressure(viii)*Filled with ________________________(True chemical name of the gas)(ix)*Filling ratio, if filled with a liquefiable gas(x)Date of last hydraulic test4. Registration number of vehicle, if applicable
6. Remarks
| Date of application |
Signature of applicant |
| |
Postal address of the applicant |
Note. - 1. Particulars marked with * are not required to be furnished if empty vessel is desired to be imported.2. Two sets of design calculations, test and inspection certificates (certificate of control) complete in all respects pertaining to vessel including design drawing, duly endorsed by third party inspecting agency and mounting drawing for ISO-container, etc. shall accompany this application.
3. In case vessel is desired to be imported duly filled with gas, filler's certificates in respect of items 3(viii) and (ix) shall be furnished.
4. Copy of RC book.
Form-LS-1A(See rules 50, 51, 54 and 55)License to store compressed gas in pressure vessel or vessels
| License No. _______________ |
Fee Rs. ________________ |
License is hereby granted to __________________________________________ ________________________________________________________________________ for the storage of compressed gases in the vessels as indicated below in the premises described below and shown in the plan No. ____________ subject to the provision of the Indian Explosives Act, 1884 (4 of 1884) and the rules made there under and to the further conditions of this license.
| Vessel No. |
Name of Gas |
State of Gas |
Water capacity in cubic meter |
Max. working pressure (kg/cm2) |
Quantity granted in Kgs (liquefied gas) |
| |
|
|
|
|
|
| |
|
|
|
|
|
The license shall remain in force upto the 30th day of September 20____________.The _____________20Chief Controller of Explosives/ Controller of ExplosivesDescription and location of the licensed premisesThe licensed premises, the layout boundaries and other particulars of which are shown in the attached approved plan No. _______________ and consists of ________ vessels for storage of(a)Flammable/ Corrosive/ Toxic gases ________________(b)non-toxic Gases ______________________________and situated at ____________________________________(Plot number) (Name of Street) (Village or Town) (Police Station) District).Space for Endorsement or Renewals
|
The license shall be renewable without anyconcession in fee for five years in the absence of contraventionof the provision of the Indian Explosives Act, 1884, or theStatic and Mobile Pressure Vessels (Unfired) Rules, 2016 framedthere under or of the conditions of the license.
|
Date of renewal |
Date of expiry |
Signature and office stamp of the licensingauthority
|
| |
|
|
|
This license is liable to be canceled if the licensed premises are not found conforming to the description and conditions attached hereto and for contravention of any of the rules and conditions under which this license is granted and the holder of this license is also punishable under the Act.Conditions1. The licensed premises shall conform to the description of location and facilities and to the approved plan, as mentioned on the body of the license.
2. The licensed premises shall have prominently marked thereon the number of the license held for it.
3. The emergency telephone numbers of local fire service, police and the principal marketing company or supplier of the compressed gas, and emergency instructions shall be conspicuously displayed in the licensed premises.
4. The licensed premises shall not be used for any purpose other than the purpose for which the license is granted.
5. The compressed gas shall be stored only in the vessels specified in the license and shown in the approved plan attached hereto.
6. The storage vessel shall at all times maintain requisite safety distance from any other facility, building, boundary, fencing or protected works as specified in appropriate Table specified in rule 22.
7. A suitable hard stand for parking of the vehicle during loading or unloading of any compressed gas shall be provided . The following minimum safety distances shall be provided between the centre of the hard stand and the storage vessel or boundary line of installation; as well as between the loading or unloading points and storage vessel or boundary line of installation as specified under item (ii) of sub-rule 5 of Rule 27.
8. All fitments of the vessel shall be maintained in good operating condition.
9. No alteration of the position of the vessel and no replacement of the vessel shall be effected except with the previous sanction, in writing, of the licensing authority as provided in the rules.
10. Every vessel before being repaired or exhumed shall be made free of compressed gas and thoroughly cleaned in a safe manner. When a vessel is opened for cleaning or repairs, no lamp of any description either ordinary or electric, electric cables or fans and no articles, appliances or equipment capable of igniting flammable vapours shall be brought near the vessel.
11. No person shall cause to repair or repair either by the use of fire, welding, hot riveting or brazing any vessel used for the storage of flammable gas unless it has been thoroughly cleaned and gas-freed or otherwise prepared for safely carrying out such hot work and certified in writing, by a competent person, to have been so prepared. Where the vessel has been certified as gas-free, the certificate shall be preserved by the licensee for a period of not less than three months and produced to the licensing authority on demand.
12. No person shall enter any vessel used for the storage of a toxic or corrosive gas unless he is adequately protected by means of protective clothing, gas masks and such other equipments as may be required in the specific case.
13. Compressed gas shall be filled into or removed from the vessel through designated pipes of required specification and through transfer facilities shown in the approved plan.
14. The vessel shall not be filled between the hours of sunset and sunrise, unless adequate lighting of approved type is provided and except in such manner and such other condition or conditions as are specifically endorsed on the license by the licensing authority.
15. All operations in the licensed premises shall be carried out by persons competent in such operation. Every person managing or employed on or in connection with the licensed premises shall abstain from any act whatsoever which tends to cause fire or explosion and which is not reasonably necessary and to the best of his ability, shall prevent any other person from doing such act.
16. The licensee shall provide for each licensed premises a minimum of two portable foam type or dry chemical type fire extinguishers of 9 kg. capacity each, which shall be kept ready at convenient location for immediate use in the event of any fire in addition to other fire fighting or other mitigating facilities required for flammable or toxic gases..
17. All valves in the premises must be permanently marked in a manner clearly indicating the direction of opening and shutting the valve.
18. Free access to the licensed premises shall be given at all reasonable times to any of the officers specified in rule 70 and every facility shall be afforded to such officer for ascertaining that the rules and the conditions of this license are duly observed.
19. If the licensing authority calls upon the holder of a license by a notice in writing to execute any repairs in the licensed premises which are, in the opinion of such authority, necessary for the safety of the premises, the holder of the license shall execute the repairs within such period as may be specified in the notice.
20. Every vessel shall be outside any building and shall be supported on well designed calculations
21. No artificial light capable of igniting flammable vapour shall at any time be present within nine meters of the vehicle and the loading or unloading points during the transfer of the compressed gas and no person engaged in such transfer shall smoke.
22. All electrically equipment such as motors switches, starters used for transfer of liquefied petroleum gas shall be of flameproof construction conforming to IS/IEC 60079-1 to 11 or of a type approved by the Chief Controller.
23. Smoking, naked lights, lamps, source of fire or any other stimulant capable of igniting flammable vapours shall not be allowed inside the premises. Every person managing or employed on or in connection with licensed premises shall abstain from any act whatsoever which tends to cause fire or explosion and which is not reasonably necessary and to the best of his ability, shall prevent any other person from doing such act.
24. Any accident, fire ,explosion or untoward incident occurred within the licensed premises shall be immediately reported to the Chief Controller of Explosives, Controller, nearest police station and District Magistrate by quickest mode of communication.
Additional conditions for LNG(a)provide for written procedures covering operation and maintenance of the installation and the training of personnel involved in operation and maintenance.(b)provide for written emergency plan as part of operation manual.(c)shall remain in liaison with local authorities like Police, Fire Department, Health Authorities to keep them informed about emergency plan.(d)identify safety related malfunctioning of the equipment and analyze them for preventing their possible reoccurrence.(ii)The personnel engaged in operation of the installation shall be adequately trained with respect to following -(a)Procedure for basic operation to be carried out in the installation.(b)Carrying out emergency procedure.(c)The methods for carrying out duties for maintaining and operating the facilities as set out in the operating and maintenance procedure.(d)LNG transfer procedure.(e)Fire prevention including familiarization with the fire control plan.(f)Recognizing situations in which it is necessary to obtain assistance outside to maintain safety of the facility.(iii)The installation shall be equipped with adequate personnel protective safety equipments like gloves, goggles, apron, etc. and no person shall operate any equipment in the installation without making use of such protective equipment.(iv)Emergency rescue vehicle shall be provided for installation more than 400 kms from the loading installations.Form LS-1B(See rules 50, 51, 54 and 55)License to store and dispense auto LPG in auto LPG dispensing station as automotive fuel to motor vehicles.
| License No :_____________________ |
Fee Rs. ________________ |
License is hereby granted to ____________________________________________ for storage of auto-LPG in the pressure vessels indicated below in the premises described below and dispensing auto-LPG of as automotive fuel to motor vehicles, subject to the provisions of the Indian Explosive Act, 1884 (4 of 1884) and the rules made there under and to the further conditions of this license.
| Vessel No. |
Nature of installation (whether underground,mounded or aboveground)
|
Water capacity in cubic meter |
Quantity of auto-LPG granted in Kgs |
| |
|
|
|
| |
|
|
|
The license shall remain in force up to the 30th day of September 20____________.The _____________20 Chief Controller of Explosives/Controller of ExplosivesDescription of location and facilities of the licensed premisesThe licensed premises, the layout, boundaries and other particulars of which are shown in the attached approved plan No. ________________dated _____________are situated at (address)_________________________________________________________and consists(in addition to storage vessels mentioned above) of :-(i)____________________numbers dispensers, make________________(ii)other facilities_________________________Space for Endorsement of Renewals
|
The license shall be renewable without anyconcession in fee for five years in the absence of contraventionof the provisions of the Indian Explosives Act, 1884 or Staticand Mobile Pressure Vessels (Unfired) Rules, 2016 framed thereunder, or of the condition of the license.
|
Date of Renewal |
Date of Expiry |
Signature and Office Stamp of the LicensingAuthority
|
This license is liable to be canceled if the licensed premises are not found conforming to the description and conditions attached hereto and for contravention of any of the rules and conditions of this license and the holder of this license is also punishable under the Act.Conditions1. The licensed premises shall conform to the description of location and facilities and to the approved plan, as mentioned on the body of the license.
2. The licensed premises shall be used only for the purpose it is licensed for.
3. Every licensed premises under these rules shall have prominently marked thereon the number of the license held for it.
4. The emergency telephone numbers of local fire service, police and the principal marketing company or supplier of the compressed gas, and emergency instructions shall be conspicuously displayed in the licensed premises.
5. Auto-LPG shall be stored only in one or more pressure vessels installed aboveground, underground or aboveground covered with earth (mound) as per provisions of these rules.
6. The storage vessel, dispenser, pumps, compressor, piping and other fittings shall be of a design suitable for auto- LPG.
7. Storage vessels shall not be installed within any building or shed.
8. A hard stand for parking the tank-truck for the purpose of unloading auto-LPG into the storage vessels shall be provided as per rules.
9. The facilities and equipments of the licensed premises shall meet the safety distance requirements as specified in Table-5 of rule 22.
10. Auto-LPG shall be dispensed only into those containers of motor vehicles, which are approved by the Chief Controller, and have passed the periodic statutory tests under Gas Cylinders Rules, conducted by a testing station recognized by the Chief Controller.
11. The dispenser used for dispensing auto-LPG shall conform to Schedule-II and a specification approved by the Chief Controller..
12. Pump used for pumping auto-LPG shall be of either centrifugal, submersible or positive displacement type. Positive displacement pump shall be provided with bye-pass to prevent over-pressure.
13. Hazardous area classification for the dispenser shall be as under :-
(a)Entire space within the dispenser enclosure cabinet and forty six centimetres horizontally from the exterior of enclosure cabinet and up to an elevation of one hundred and twenty one centimetres above dispenser base and the entire pit or open space beneath the dispenser shall be zone-2.(b)Upto forty six centimetres vertically above the surrounding ground level and horizontally beyond forty six centimetres up to six meters on all sides of the dispenser enclosure cabinet shall be zone-1.14. All piping and fittings shall conform to Schedule-II.
15. No person shall enter or cause to repair or repair either by the use of fire, welding, hot riveting or brazing any vessel used for the storage of flammable gas unless it has been thoroughly cleaned and gas-freed or otherwise prepared for safely carrying out such hot work and certified in writing, by a competent person.
16. The operation of the licensed premises shall be under the supervision of a person having knowledge of the equipments used in the premises and trained in handling compressed gas, and other operators shall be conversant with the hazards associated with the compressed gas and fire fighting operations.
17. Auto-LPG shall not be filled into or removed from the vessel except by means of transfer facilities shown in the approved plan attached to the license.
18. Smoking, naked lights, lamps, source of fire or any other stimulant capable of igniting flammable vapours shall not be allowed inside the premises. Every person managing or employed on or in connection with licensed premises shall abstain from any act whatsoever which tends to cause fire or explosion and which is not reasonably necessary and to the best of his ability, shall prevent any other person from doing such act.
19. The vessel shall not be filled between the hours of sunset and sunrise.
20. All electrically equipment such as motors switches, starters, etc, used for transfer of liquefied petroleum gas shall be of flameproof construction conforming to IS/IEC 60079-1 to 11 or of a type approved by Chief Controller.
21. At least two numbers of nine kilograms capacity dry chemical type fire-extinguishers shall be provided near the tank-truck unloading area and one number similar extinguisher shall be provided near each dispenser and transfer pump location. In addition, fire fighting facilities specified in rule 26 shall be provided.
22. During the period of unloading of liquefied petroleum gas from tank-truck to the storage vessels dispensing operation to vehicles shall not be carried out.
23. The emergency telephone numbers of local fire service, police and the principal marketing company, and emergency instructions shall be conspicuously displayed in the licensed premises.
24. All valves on the vessel and pipelines in the premises must be permanently marked in a manner clearly indicating the direction of opening and closing.
25. Free access to the licensed premises shall be given at all reasonable times to any of the officers specified in Rule 70 and every facility shall be afforded to such officer for ascertaining that the rules and the conditions of this license are duly observed.
26. If the licensing authority calls upon the holder of a license by a notice in writing to execute any repairs in the licensed premises which are, in the opinion of such authority, necessary for the safety of the premises, the holder of the license shall execute the repairs within such period as may be specified in the notice.
27. Any accident, fire ,explosion or untoward incident occurred within the licensed premises shall be immediately reported to the Chief Controller of Explosives, Controller, nearest police station and District Magistrate by quickest mode of communication.
Form LS-2(See rules 50, 51, 54 and 55)License to transport compressed gas in a pressure vessel by a vehicle
| License No :_____________________ |
Fee Rs. ________________ |
License is hereby granted to ___________________________________________ to transport compressed gas by the vehicle as described below subject to the provisions of the Indian Explosives Act, 1884 (4 of 1884) and the rules made there under and to the further conditions of this license.This license will remain valid upto the _____________(one or more, maximum five years from date of grant)
| Date of Issue: |
Chief Controller of Explosives/ Controller of Explosives |
Description of the vehicleMake and Model _________________________ Engine Number _________________________Chassis Number _________________________Registration Number ______________________Name of the registered owner ________________________________________________ Chemical name of the compressed gas to be carried in the Vehicle ___________________ Authorized carrying capacity of the vehicle ____________________________________Endorsement of Renewals
| Date of Renewal _____________________ |
Date of Expiry ________________ |
Signature and office Stamp of the Licensing authority _______________________________This license is liable to be canceled if the licensed vehicle is not found conforming to the requirements of chapters II and IV of the Static and Mobile Pressure Vessels (Unfired) Rules 2016, or for the contravention of any of the said rules and conditions under which this license is granted and the holder of this license is also punishable under the ActConditions1. The license or its authenticated copy shall at all times be kept in the licensed vehicle and produced on demand by an officer specified in Rule 70.
2. Only responsible persons who are conversant with the conditions of this license shall be employed for driving the licensed vehicle or attending to it.
3. The licensed vehicle shall be constantly attended to by a responsible person and by at least two persons while it is transporting compressed gas:
Provided that the licensed vehicle may, if empty, be kept unattended in a place approved for the purpose, in writing, by the Chief Controller or Controller.4. The licensed vehicle shall at all times carry -
(a)at least two portable fire extinguishers of capacity not less than 9 litres and suitable for extinguishing chemical fires;(b)a strong flexible cable for electrical bonding in case of vehicle used for transportation of flammable compressed gas; the cable shall be at least 5 metres long and shall have at each end a suitable clamp or clip.5. The licensed vehicle shall not be loaded or unloaded except in a place which is approved within the premises licensed for the purpose under the rules by the Chief Controller or Controller or when the fitments including vessel becomes leaky, defective or otherwise insecure.
Provided that the licensed vehicle may be unloaded at any other place with all the precautions and under adequate supervision if such unloading is necessitated by an accident or break down.6. No vehicle shall discharge any compressed gas directly, into any process vessel in operation.
7. The licensed vehicle shall not be loaded if any of the fitments including vessel becomes leaky, defective or otherwise insecure.
8. Before compressed gas is loaded into or unloaded from the licensed vehicle-
(a)its engine shall be stopped and the battery shall be isolated by a proper switch or otherwise;(b)its wheels shall be secured by brakes or by scotching;(c)its chassis shall be electrically bonded by a cable with the pipe into or from which it is to be loaded or unloaded, in case of vehicle used for transportation of flammable compressed gas;(d)the correct filling or discharge pipe connections are made at both ends;(e)a responsible person shall be in attendance and remain so until loading or unloading is over and the vehicle has been sealed.9. Except when called upon by traffic signals or required by the licensing authority or any other officer entrusted with the job of enforcing the rules, the licensed vehicle shall not stop on any road, congested area or a place which is not a place situated within the premises licensed under the rules for the loading and unloading of vehicle.
10. No smoking and no fire or artificial light or any article capable of igniting flammable vapour shall be allowed on the licensed vehicle used for the transportation of any flammable gas.
11. The licensed vehicle shall not be used for carrying passengers.
12. No alteration in the licensed vehicle or its safety fittings shall be carried out without previous sanction in writing of the licensing authority. Such alteration so sanctioned shall be endorsed on the license by an amendment.
13. Free access to the licensed premises shall be given at all reasonable times to any of the officers specified in Rule 70 and every facility shall be afforded to such officer for ascertaining that the rules and the conditions of this license are duly observed.
14. If the licensing authority calls upon the holder of a license by a notice in writing to execute any repairs in the licensed premises which are, in the opinion of such authority, necessary for the safety of the premises, the holder of the license shall execute the repairs within such period as may be specified in the notice.
15. Any accident, fire ,explosion or untoward incident occurred within the licensed premises shall be immediately reported to the Chief Controller, Controller, nearest police station and District Magistrate by quickest mode of communication.