Legal Document View

Unlock Advanced Research with PRISMAI

- Know your Kanoon - Doc Gen Hub - Counter Argument - Case Predict AI - Talk with IK Doc - ...
Upgrade to Premium
[Cites 0, Cited by 0] [Entire Act]

State of Rajasthan - Section

Section 28 in Rajasthan Factories Rules, 1951

28. How to introduce steam for humidification.

— In any room in which steam pipes are used for the introduction of steam for the purpose of artificial humidification of the air the following provisions shall apply:—
(a)The diameter of such pipes shall not exceed [50 mms.] [Substituted by No. 1. dated 24.3.1979.] and in the case of pipes installed after 1st day of January, 1950 the diameter shall not exceed [25 mms.] [Substituted by No. 1. dated 24.3.1979.]:
(b)Such pipes shall be as short as is reasonably practicable:
(c)All hangers supporting such pipes shall be separated from the bare pipes by an efficient insulator not less than [13 ms.] [Substituted by No. 1. dated 24.3.1979.] in thickness:
(d)No uncovered jet from such pipe shall project more than [110 mms.] [Substituted by No.1, dated 24.3.1979.] beyond the outer surface of any cover;
(e)The steam pressure shall be as low as practicable and shall not exceed [5kg/square cm] [Substituted by No. 1. dated 24.3.1979.]
(f)The pipe employed for the introduction of steam into the air in a department shall be effectively covered with such non- conducting material as may be approved by the Inspector in order to minimise the amount of heat radiated by them into the department.
Rules 29 to 33 prescribed under sub-section (4) of section 17