[Cites 0, Cited by 0]
[Entire Act]
State of Jammu-Kashmir - Section
Section 11 in Jammu and Kashmir State Electricity Regulatory Commission (Terms and Conditions for Determination of Multi Year Generation Tariff) Regulations, 2016
11. Thermal Power Generating Stations
- Components of tariff :| Pressure Rating (Kg/cm2) | 150 | 170 | 170 | 247 | 247 |
| SHT/RHT (0C) | 535/535 | 537/537 | 537/565 | 537/565 | 565/593 |
| Type of BFP | Electrical | Turbine | Turbine | Turbine | Turbine |
| Driven | Driven | Driven | Driven | Driven | |
| Max. Turbine CycleHeatrate (KCal/kWh) | 1955 | 1950 | 1935 | 1900 | 1850 |
| Min. Boiler Efficiency | |||||
| Sub-Bituminous Indian Coal | 0.85 | 0.85 | 0.85 | 0.85 | 0.85 |
| Bituminous Imported Coal | 0.89 | 0.89 | 0.89 | 0.89 | 0.89 |
| Max. Design Unit Heat rate (KCal/kWh) | |||||
| Sub-Bituminous Indian Coal | 2300 | 2294 | 2276 | 2235 | 2176 |
| Bituminous Imported Coal | 2197 | 2191 | 2174 | 2135 | 2079 |
| (i) Coal-based generating stations | ||
| 200 MW series | With Natural Draft cooling Toweror without cooling towers | 8.5% |
| 300/330/350/500 MW and above series-Steam Driven Boiler Feed Pumps | With Natural Draft cooling Toweror without cooling towers | 5.25% |
| 300/330/350/500 MW series-Electrically Driven Boiler Feed Pumps : | With Natural Draft cooling Toweror without cooling towers | 7.75% |
| Provided further that for thermal generating stations withinduced draft cooling towers, the norms shall be furtherincreased by 0.5%. | ||
| (ii) Gas-based and Naphtha-based generatingstations : | ||
| Combined cycle | 2.5% | |
| Open cycle | 1.0% |
| A=| 10(100-ACn)| *SFCn* (Pom- Pos) |
| B=| 10(100-ACn)| *[SFCn* {(Pcm/Kcm) - (Pcs/Kcs)}- |
| FPA| 10* SHRn* (Pm/Km)-(Ps/Ks)| |