NCT Delhi - Act
The BSES Rajdhani/Yamuna Power Limited Complaint Handling Procedures Relating To Distribution And Retail Supply
DELHI
India
India
The BSES Rajdhani/Yamuna Power Limited Complaint Handling Procedures Relating To Distribution And Retail Supply
Rule THE-BSES-RAJDHANI-YAMUNA-POWER-LIMITED-COMPLAINT-HANDLING-PROCEDURES-RELATING-TO-DISTRIBUTION-AND-RETAIL-SUPPLY of 2003
- Published on 3 June 2003
- Commenced on 3 June 2003
- [This is the version of this document from 3 June 2003.]
- [Note: The original publication document is not available and this content could not be verified.]
1. Introduction.
- This "Complaint Handling Procedure relating to Distribution and Retail Supply" as approved by the Delhi Electricity Regulatory Commission is hereby adopted by the licensee.2. Nature of complaints:
3. Where to lodge Complaints.
- The contact telephone number(s) where consumers can lodge their complaints as also the name and contact telephone number of the Asst. Engineer concerned, who can be approached in case of delay in the redressal of complaint would be notified as under :4. No Current/failure of power supply.
- Power supply in premises could fail due to one of the following reasons, which could be attributed to Distribution Companies (DISCOM):| Nature of cause of power supply failure | Maximum Time Limit for restoration. |
| Fuse blown out or MCB tripped | Within 3 hours |
| Suburban – 8 hours | |
| Service line broken | Within 6 hours |
| Service line snapped from the pole | Suburban – 12 hours |
| Fault in distribution mains | Temporary Supply to be restored within 4 hours from alternatesource, wherever feasible. |
| Rectification of fault and thereafter Restoration of powersupply within 12 hours | |
| Distribution transformer failed/burnt | Temporary Restoration of supply through mobile transformer oranother backup source within 8 hours, wherever feasible |
| Replacement of failed transformer within 48 hours | |
| HT mains failed | Temporary restoration of power supply within 4 hours,wherever feasible. |
| Rectification of fault within 12 hours | |
| Problem in grid (33 kV or 66 kV) substation | Restoration of supply from alternate source, whereverfeasible within 6 hours |
| Roster load shedding may be carried out to avoid overloadingof alternate source. | |
| Repair and restoration of supply within 48 hours | |
| Failure of Power Transformer | Restoration of supply from alternate source, whereverfeasible within 6 hours |
| Roster load shedding may be carried out to avoid overloadingof alternate source. | |
| Replacement action to be intimated to DERC within 72 hours | |
| Burnt meter | Restoration of supply by bypassing the burnt meter within 6hours |
| Replacement of burnt meter within 3 days |
5. Voltage Complaints.
- In the case of Low / High voltage, the complaint should be lodged at the Centralised Call Centre giving name, address of the complainant along with brief nature of the problem faced. The operator on duty shall register the complaint and intimate the complaint number in every case.The Centralized Call Centre shall communicate the complaint to the mobile service groups at the concerned Service Centres. The mobile service group would then proceed to the address provided by the complainant, investigate the cause of complaint and resolve the problem.In case problem is local e.g. due to loose connection of service line, the mobile group shall rectify the fault themselves. In case the voltage problem is due to some other reason(s), such as, deficiency in the system, the mobile group shall bring this to the notice of the Area Assistant Engineer.The Area Assistant Engineer shall ascertain if the problem can be rectified by changing the Tap position of the transformer, and if possible, he shall do so after getting the approval from the Executive Engineer. However, in case the Assistant Engineer find that problem is due to deficiency in the distribution system requiring up-gradation of distribution lines, transformers, capacitors etc., he shall inform the Executive Engineer for taking further necessary action.The voltage problem shall be resolved with the time limits specified in Table given below:| S.No. | Cause of Problem related to voltage variation | Time limit for the rendering service | Authorised Person | Next higher level for complaint |
| 1. | Local problem | Within 4 hours | Assistant Engineer | Executive Engineer |
| 2. | Tap of transformer | Within 3 days | Assistant Engineer | Executive Engineer |
| 3. | Repair of distribution line / transformer / capacitor | Within 60 days | Assistant Engineer | Executive Engineer |
| 4. | Installation & Up-gradation of HT / LT System | Within 180 days | Assistant Engineer | Executive Engineer |