Section 15(3) in The Static and Mobile Pressure Vessels (Unfired) Rules, 2016

(3)Cryogenic pressure vessels,-
(i)design service temperature of the cryogenic pressure vessels shall not be higher than the normal boiling point of the cryogenic liquid;
(ii)material of construction of the inner vessel, its piping and fittings shall be suitable for the service temperature and shall be compatible for the specific cryogenic liquid;
(iii)outer vessel shall be made of steel not less than 3mm nominal thickness or of aluminium not less than 4mm nominal thickness and shall have required structural strength and capable for supporting the inner vessel together with cryogenic liquid, insulation and other fittings. The outer vessel of vacuum insulated cryogenic tanks shall be designed for a minimum collapsible pressure of one atmosphere (gauge). The suitable protecting coating shall be provided on the outer vessel to avoid corrosion. The outer vessel shall also be provided with suitable lifting arrangement and supports for installation and mounting;
(iv)inner supports between the inner vessel and the outer vessel shall be of non-inflammable materials and capable of supporting the inner vessel together with the maximum allowable cryogenic liquid. The supports shall be able to withstand expansion or contraction within the operating temperature range. Cryogenic pressure vessels meant for transport purpose, shall be able to withstand maximum static loading of all the following individually -
(a)Vertical downward of two (2);
(b)Vertical upward of one and half (1 ½);
(c)Longitudinal of one and half (1 ½); and
(d)Lateral of one and half (1 ½)
times the weight of liquid container. The factor of safety of the supports shall be as per the design code;
(v)air in the annular space between the inner and outer vessel shall be evacuated and the space shall be filled with suitable insulating material compatible with the particular cryogenic liquid.