State of Bihar - Subsection

Section 62(7) in Bihar Factories Rules, 1950

(7)Storage of flammable liquids. - (a) The quantity of flammable liquids in any work room shall be the minimum required for the process or processes carried on in such room. Flammable liquids shall be stored in suitable containers with close fitting covers:Provided that not more than 20 litres of flammable liquids having a flash point of 21°C or less shall be kept or stored in any work room.
(b)Flammable liquids shall be stored in closed containers and in limited quantities in well ventilated of fire resistant construction which are isolated from the remainder or the building by fire walls and self closing arc doors.
(c)Large quantities of such liquids shall be stored in isolated adequately ventilated building or fire resisting construction or in storage tanks, preferably under-ground and at a distance from any building as required in the petroleum Rules, 1976.
(d)Effective steps shall be taken to prevent leakage of such liquids into basements, sumps or drains and to confine any escaping liquids within safe limits.