Section 20 in Rajasthan Electricity Regulatory Commission (Metering) Regulations 2007
20. Review of regulations.
| S.No. | Particulars | Interface Meters | Energy ACcounting and Audit Meters above 33KV |
| 1 | 2 | 3 | 4 |
| 1 | Meter Type (Number phases and wries) | AC Static HT TVM 3 Phase-4 Wire type ABTcompliant | AC Static HT TVM 3 Phase-4Wire TOD type |
| 2 | Measurand(s) | Wh (Imp/Exp), V Arh at 103% voltage and 97%voltage & Vah during Wh (Imp/Exp), V Arh (Lag/lead) &PF(lag/lead), W, VA, phase voltage, Line current, frequency,instantaneous load in W, Anomaly Data, Power On hours andmeasurement in four quadrants. | kWh (Imp/Exp), kV Arh at 103% voltage and 97%voltage & kVArh (lag/lead) & kVAh during KWh (Imp/Exp),PF (lag/lead), kW, kVA, Phase Voltage, Line current, frequency,instantaneous load in kW, Anomaly Data, Power on hours, andmeasurement in four quadrants |
| 3 | Indian Standard or IEC to which confirming | IS 14697, IEC 62052—11 IEC 62053—22&, CBIP Report No. 88 | |
| 4 | Rated Current. | 3x-/1 Amp or 3x-/5 Amp (Ib) | |
| 5 | Reference frequency, Hz & variation | 50 Hz, (+/-)5% | |
| 6 | (a) Accuracy class of meter.(b) Classificationangle for Var meters | 0.2SFour quadrants | |
| 7 | Maximum demand recording period (for MDI only) | 15 Min. | |
| 8 | Display of measurands | Wh (Imp/Exp), Varh (lag/lead) & Vah duringWh (Imp/Exp) Cumulative reactive energy at 103% voltage and 97%voltage PF (leg/lead), W, VA, Phase Voltage, Line current,frequency instantaneous load In W, Anomaly Data, BP Wh (I/E), BPPF (I/E) Power On hours. Measurement in four quadrants | KWh (Imp/Exp), KV Arh (lag/lead) & KVAhduring KWh (Imp/Exp), Cumulative reactive energy at 103% voltageand 97% voltage, PF (lag/lead), W, KVA, Phase voltage, Linecurrent frequency , instantaneous load in KW, KVR, KVAR, AnomalyData, BP KWh (I/E), BP PF (I/E) Power On hours. Measurement infour quadrants. |
| 9 | Storage of measurands | Load Survey for 75 days with integration periodof 15 min. for W (Imp/Exp) VA (Imp/Exp), coded frequency wise Wh(Imp/Exp), Vah (Imp/Exp), Billing parameters for last 3 monthsincluding Power On hours and anomaly information meter readingcount, MD reset count. | Load Survey for 75 days with integration periodof 15 min. for KW (Imp/Exp), KVA (Imp/Exp), KWh (Imp/Exp), KVAh(Imp/Exp), Billing parameters for last three (3) months includingPower On Hours and anomaly information, meter reading count, MDreset count. |
| 10 | Any other displays | Total energy i.e. Fundamental energy plusHarmonic energy, self-diagnostic features. | |
| 11 | a) Output device (forreadings)(b) Whether remote reading feasible. | For calibrationYes | |
| 12 | Immunity to externalfactors(a) Heat & Fire(b) Shock &vibration(c) Dust & Water(d) Electro magneticfields(e) Radiointerference(f) Electro static fields | As per IS: 11000As per IS: 9000IP: 51As per IS: 61 0000As per IS: 6842As per IS: 61000-4-2 | |
| 13 | Any other feature/requirement. | (a) 2 ports suitablefor local & remote communication.(b) Draw out type modular metering units withfacility of automatic CT shorting. Meter mounting shall be eitherof projection type or rack type as per space and siterequirement. | |
| 14 | Common Meter Reading Instrument, (CMRI) | CBIP report No. 111, IP67, IEC 529, IS 12063,CISPA R22, IEC 61000-4 |
| S.No. | Particulars | Specification of Meters | |||
| Meter Type 'A' | Meter Type 'B' | Meter Type C | |||
| Single Phase | Poly Phase | LT Tri-vector | HT Tri-vector | ||
| 1 | 2 | 3 | 4 | 5 | 6 |
| 1 | Meter Type | Electro-static | Electro-static | Electro-static | Electro-static |
| 2 | Applicable | Upto 5.0 Kw connected load of LT supply. | Normally upto 18.65 kW connected load of LTsupply. | Normally above 18.65 KW connected load and upto50 kVA contact demand | HT/EHV Supply |
| 3 | Number of phases and wires | Single Phase 2 Wire | Three Phase 4 Wire | Three Phase 4 Wire | Three Phase 4 Wire except traction supply. |
| 4 | Measurand[s] | KWH | KWH | KWH, KVAH, KVA, PF | kWH (Imp/Exp), kVAh, kVARh |
| 5 | Indian standard or IEC to which confirming | IS 13779-1999 | IS 13779-1999 | IS 14697, IS 13779 | IS 14697, IS 13779 |
| 6 | Reference frequency, HZ and variation | 50 HZ + 5% | 50 HZ + 5% | 50 HZ + 5% | 50 HZ + 5% |
| 7 | Accuracy Class of meter | 1.0 or better | 1.0 or better | 0.5S or better | up to 33 kV supply 0.2s above 33kV supply |
| 8 | Meter operation or CT/PT | Whole Current | Whole Current | CT Operated | CT-PT Operated |
| 9 | Demand period | - | - | 30 Min | 30 Min |
| 10 | Minimum Starting current as % of base | 0.2 | 0.2 | 0.1 | 0.1 |
| 11 | Import-export feature | Forward Import | Forward Import | Import and Export | Import and Export |
| 12 | Load Anti-creeping device | Not more than one Pulse | Not more than one Pulse | Not more than one Pulse | Not more than one Pulse |
| 13 | a. Out-put device [for readings] b. Whetherremote reading feasible | VisualNot Required | VisualNot Required | Visual as well asthrough MRINot Required | Visual as well asthrough MRIRequired |
| 14 | Immunity to Externalfactors:a. Heat and fireb. Shock andvibrationc. Dust and Water [IPclass]d. Electro MagneticFieldse. Radio Interferencef. Electro Static Fields | As per IS 11000As per IS 9000As per IS 12063As per IEC 61000As per IS 6842As per IEC 61000-4-2 | As per IS 11000As per IS 9000As per IS 12063As per IEC 61000As per IS 6842As per IEC 61000-4-2 | As per IS 11000As per IS 9000As per IS 12063As per IEC 801-3As per IS 6842As per IEC 61000-4-2 | As per IS 11000As per IS 9000As per IS 12063As per IEC 801-3As per IS 6842As per IEC 61000-4-2 |
| 15 | Any Other feature/ requirement | i. Communicationcapabilityii. Up gradation capability (preferred) | i. Communicationcapabilityii. Up gradation capability (preferred) | i. Communicationcapabilityii. Up gradation capability (preferred) | i. Communicationcapabilityii. Up gradation capability (preferred) |
| 16 | LED indication | i. Visual signal toindicate the operation of the meterii. Line loadreversal indicationiii. Earth loading indication | i. Visual signal toindicate the operation of the meterii. Line loadreversal indication | i. Visual signal toindicate the operation of the meterii. Line load reversal indication | i. Visual signal toindicate the operation of the meterii. Line load reversal indication |
| Particulars | Year | |
| A. | Meter instruments | |
| (1) Consumer Meters: | ||
| (i) Extra High Voltage consumers. | 1 | |
| (ii) High Voltage consumers | ||
| (a) Above 500 KVA contract demand | 1 | |
| (b) Up to 500 KVA contract demand | 1 | |
| (iii) Industrial Low Tension consumers | 1 | |
| (iv) Low Tension consumers other than domestic services | 2 | |
| (v) Domestic service consumers | 5 | |
| (2). Interface meters | 1 | |
| (1) Energy accounting and audit meters (including Stationauxiliary metering) | 5 | |
| B. | Instrument Transformers for: | |
| (1) Consumer meter | ||
| (i) Extra High Voltage consumers | 2 | |
| (ii) High Voltage consumers | ||
| (a) Above 500 KVA contract demand | 2 | |
| (b) Up to 500 KVA contract demand | 2 | |
| (iii) Industrial Low Tension consumers | 2 | |
| (iv) Low Tension consumers other than domestic services | 2 | |
| (v) Domestic Service consumer | 5 | |
| (2) Interface meters | 2 | |
| (3) Energy accounting and audit meters (including Stationauxiliary metering) | 5 |