| Various Other Standards |
| Sl. |
Parameter |
Reference |
Requirements |
| 1. |
Overall conditions of service |
State Distribution/Supply Code |
State Distribution/Supply Code |
| 2. |
Overall Grid Standards |
Central Electricity Authority (Grid Standard)Regulations 2010
|
Central Electricity Authority (Grid Standard)Regulations 2010
|
| 3. |
Equipment |
BIS / IEC / IEEE |
BIS / IEC / IEEE |
| 4. |
Meters |
Central Electricity Authority (Installation &operation of meters) Regulation 2006 as amended time to time
|
Central Electricity Authority (Installation &operation of meters) Regulation 2006 as amended time to time
|
| 5. |
Safety and supply |
Central Electricity Authority (Measures relatingto Safety and Electricity Supply) Regulations, 2010
|
Central Electricity Authority (Measures relatingto Safety and Electricity Supply) Regulations, 2010
|
| 6. |
Harmonic Requirements Harmonic Current |
IEEE 519CEA (TechnicalStandards for Connectivity of the DistributedGeneration Resources) Regulations 2013.
|
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013.
|
| 7. |
Synchronization |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
Solar Plant must be equipped with a gridfrequency synchronization device. Every time the generatingstation is synchronized to the electricity system. It shall notcause voltage fluctuation greater than +/- 5% at the point ofconnection.
|
| 8. |
Voltage |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
The voltage-operating window should minimizenuisance tripping and should be under operating range of 80% to110% of the nominal connected voltage. Beyond a clearing time of2 second, the Solar Plant must isolate itself from the grid.
|
| 9. |
Flicker |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
Operation of Solar Plant should not causevoltage flicker in excess of the limits stated in IEC 61000standards or other equivalent Indian standards, if any.
|
| 10. |
Frequency |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
When the Distribution system frequency deviatesoutside the specified conditions (50.5 Hz on upper side and 47.5Hz on lower side), There should be over and under frequency tripfunctions with a clearing time of 0.2 seconds.
|
| 11. |
DC injection |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
Should not inject DCpower more than 0.5% of full rated output at the interconnectionpoint or1% of rated inverter output current intodistribution system under any operating condition.
|
| 12. |
Power Factor |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
While the output of the inverter is greater than50%, a lagging power factor of greater than 0.9 should operate.
|
| 13. |
Islanding and Disconnection |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
The Solar Project in the event of fault, voltageor frequency variations must island/disconnect itself within IECstandard on stipulated period.
|
| 14. |
Overload and Overheat |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
The inverter should have the facility toautomatically switch off in case of overload or overheating andshould restart when normal conditions are restored.
|
| 15. |
Paralleling Device |
IEEE 519CEA (Technical Standards for Connectivity of theDistributed Generation Resources) Regulations 2013
|
Paralleling device of Solar System shall becapable of withstanding 220% of the normal voltage at theinterconnection point.
|
| 16. |
Note:The standards/specifications shall be subject toamendments/revisions from time to time by the DistributionLicensee and the State Agency on respective websites.
|