Union of India - Act
Central Electricity Authority (Installation and Operation of Meters) Regulations, 2006
UNION OF INDIA
India
India
Central Electricity Authority (Installation and Operation of Meters) Regulations, 2006
Rule CENTRAL-ELECTRICITY-AUTHORITY-INSTALLATION-AND-OPERATION-OF-METERS-REGULATIONS-2006 of 2006
- Published on 22 March 2006
- Commenced on 22 March 2006
- [This is the version of this document from 22 March 2006.]
- [Note: The original publication document is not available and this content could not be verified.]
1683.
Not. No. 502/70/CEA/DP&D, dated 17.3.2006.- In exercise of the powers conferred by sub-section (1) of section 55 and clause (e) of section 73 read with sub-section (2) of section 177 of Electricity Act, 2003, the Central Electricity Authority hereby makes the following regulations for regulating the installation and operation of meters, namely :-1. Short title and commencement.-
2. Definitions.-
3. Applicability of regulations.-
4. Type of meters.-
5. Standards.-
All interface meters, consumer meters and energy accounting and audit meters shall -6. Ownership of meters.-
7. Locations of meters.-
| Sl. No. | Stages | Main meter | Check meter | Stand by meter |
| A. | Generating Station | On all outgoing feeders. | On all outgoing feeders. | (i) High Voltage (HV) side of Generator Transformers(ii) High Voltage(HV) side of all Station Auxiliary Transformers |
| Sl.No. | Stages | Main Meter | Check Meter | Stand by Meter |
| B. | Transmission and Distribution System | At one end of the line between the sub-stations of the same licensee, and at both ends of the line between sub-stations of two different licensees. Meters at both ends shall be considered as main meters for respective licensees | - | There shall be no separate standby meter. Meter installed at other end of the line in case of two different licensees shall work as standby meter. |
| C. | Inter-Connecting Transformer (ICT) | High Voltage (HV) side of ICT. | - | Low Voltage (LV) side of ICT. |
| D. | Consumer directly connected to the Inter-State Transmission System or Intra-State Transmission System who have to be covered under ABT and have been permitted open access by the Appropriate Commission or Any other system not covered above | As decided by the Appropriate Commission. |