State of Jharkhand - Act
Jharkhand Building Byelaws 2016
JHARKHAND
India
India
Jharkhand Building Byelaws 2016
Rule JHARKHAND-BUILDING-BYELAWS-2016 of 2016
- Published on 14 September 2006
- Commenced on 14 September 2006
- [This is the version of this document from 14 September 2006.]
- [Note: The original publication document is not available and this content could not be verified.]
1. Short title, Extent and commencement.
- 1.1 These byelaws shall be called the Jharkhand Building Byelaws 2016.2. Definitions.
- 2.1 In these bye laws, unless the context otherwise requires:| Criteria | High Risk | Medium Risk | Low Risk |
| Hazardous Building | Storing explosives and inflammable | Not so | Not so |
| Fly Zone | Above 30 meters in any place and within funnelzone of Airport. | Less than 30 meters and within funnel zone ofAirport | Outside funnel zone of Airport |
| Fire | Ground Coverage of more than 500 sqm. on anyfloor of building and more than 15 meters height | Ground coverage of more than 300 sqm. on anyfloor of building or more and 11 meters height | None |
| Building Stability (Concrete Building) | More than 60 year of age of building | 50-70 years | Less than 50 years |
| Type of usage | close assembly building | Open assembly building | Non assembly building |
| Name of Inspection | Risk Category of Building | ||
| Low | Medium | High | |
| Inspection | Mandatory | Mandatory | Mandatory |
| Third Party inspection cum certification | Optional | Mandate | Mandatory |
| Joint Inspection | Optional | Mandate | Mandatory |
| Surprise Inspection | Optional | Optional |
3. Applicability.
- Subject to the provisions of the Jharkhand Regional Development Authority Act/MADA Act/Jharkhand Municipal Act-2011 and Jharkhand Area Development Authority Act 2001 these bye laws shall apply:4. Deemed Permission.
- 4.1 The construction of any building in respect of which permission has been issued before coming into force of these bye laws, shall, so far as it is not inconsistent with the provisions of the old bye laws, continue to be validly made and the said permission shall be deemed to have been issued under the corresponding provisions of these bye laws.5. Application.
- 5.1 Any person who intends to develop land, erect, re-erect or make additions or alterations in any building, demolish any building or subdivide a plot for development shall apply to the Competent Authority. The Competent Authority may prescribe separate formats for different categories of buildings and group housing and land development.| Sl. | Item | Site Plan | Building Plan | ||||
| Computer Print/White Print | Blue Print | Ammonia Print | Computer Print/White Print | Blue Print | Ammonia Print | ||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| 1 | Plot Line | Thick Black | Thick Black | Thick Black | Thick Black | Thick Black | Thick Black |
| 2 | Existing Street | Green | Green | Green | - | - | - |
| 3 | Future Street | Green dotted | Green dotted | Green dotted | Green dotted | - | - |
| 4 | Permissible Building | Thick dotted black | Thick dotted black | Thick dotted black | Thick | Thick | Thick |
| 5 | Open Spaces | No Colour | No Colour | No Colour | No Colour | No Colour | No Colour |
| 6 | Existing outline | Black | White | Blue | Black | White | Black |
| 7 | Work Proposed to be demolished | Yellow hatched | Yellow hatched | Yellow hatched | Yellow hatched | Yellow hatched | Yellow hatched |
| 8 | Proposed work- | ||||||
| (a) Additions and alterations | Red tilled | Red | Red | Red | Red | Red | |
| (b) Entirely new work | Not to be coloured | Not to be coloured | Not to he coloured | Not to be coloured | Not to be coloured | Not to be coloured | |
| 9 | Drainage and sewerage work | Red dotted | Red dotted | Red dotted | Red dotted | Red dotted | Red dotted |
| 10 | Water Supply work | Black dotted thin | Black dotted thin | Black dotted thin | Black dotted thin | Black dotted thin | Black dotted thin |
6. Application for building permit.
- Application shall be made to the Competent Authority in Form-II. The following shall accompany the application for building permit in the case of permission for erection, re-erection of making material alternation of Post-Facto approval of the existing building. The documents shall be submitted in 4 copies along with a soft copy in PDF and CAD format.7. Certificates/Clearances.
- 7.1 Self Attested copy of original sale/lease deed, attested copy of the revenue receipt/Municipal Holding Tax receipt/holding number and mutation records.8. Signing the Plans.
- 8.1 All the plans shall be prepared and duly signed by a registered/empanelled technical person as specified in Annexure-I (viz. Architect, Engineer, Structural Engineer, Town Planner, Supervisor, Draftsman) and Builder who shall indicate their names, addresses, and registration numbers on the body of the plan and in all other relevant documents. The concerned owner of the land shall also sign the plans.2. Wherever required under these bye-laws, the registered Structural Engineer, who has prepared the structural design, shall put his seal, and address on all the documents signed by him and shall also furnish a certificate to the effect that he shall supervise the structural part of the construction and shall be responsible for any structural failure except caused by unprecedented natural calamities in Form-W and except if the owner intimates that his services have been terminated.
3. All aspects related to structural design, building surface, plumbing, electrical installation, sanitary arrangements, fire protection shall adhere to the specification, standards and code of practice recommended in the National Building Code of India, 2005 and any breach' thereof shall be deemed to be a breach of the requirements tinder these Bye laws.
9. Fees.
- 9.1 The Authority shall levy the following fees:9.1.1Every application for permission for building operation or development shall be accompanied by a building fee as specified in these bye laws.9.1.2Fees for retention of structures for temporary period shall he as decided by the Authority from time to time.9.1.3Fees for change of occupancy as decided by the Authority from time to time.9.1.4Fees for change of land use as decided by the Authority with permission to State Government from time to time.9.1.5Any other fee decided by the authority with the approval of the Urban Development and Housing Department or concern Department.9.1.6The concern department may change the fees prescribed in these bye laws through a notification from time to time.| Sl. | Area of Plot | Nagar Panchayat (Rs) | Municipal Council (Rs) | Municipal Corporation/RRDAMADA/IADA |
| (i) | (ii) | (iii) | (iv) | (v) |
| 1 | upto 1.0 hectare | 6000 | 8000 | 10000 |
| 2 | above 1.0 hectare & up to 2.5 hectare | 12000 | 15000 | 20000 |
| 3 | above 2.5 hectare & up to 5.0 hectare | 16000 | 20000 | 30000 |
| Sl. | Height of Building | Nagar Panchayat | Municipal Council | Municipal Corporation/DevelopmentAuthorities/IADA |
| (i) | (ii) | (iii) | (iv) | (v) |
| 1 | upto 10.0 m | 10.0 | 15.0 | 20.0 |
| 2 | more than 10 up to 16.4m | 20.0 | 25.0 | 40.0 |
| 3 | More than 16.4 m | 30.0 | 35.0 | 50.0 |
| Sl. | Height of Building | Nagar Panchayat | Municipal Council | Municipal Corporation/DevelopmentAuthorities/IADA |
| (i) | (ii) | (iii) | (iv) | (v) |
| 1 | upto 10.0 m | 15.0 | 20.0 | 30.0 |
| 2 | more than 10 up to 16.4m | 25.0 | 35.0 | 50.0 |
| 3 | More than 16.4 m | 35.0 | 45.0 | 60.0 |
10. Permission.
- 10.1 No permission or notice shall be required for the works related to the following alterations and the like which do not otherwise violate any provisions regarding general building requirements, structural stability and fire and health safety requirements of the National Building Code-2005:10.1.1Opening and closing of a window or door or ventilator;10.1.2Providing intercommunicating doors;10.1.3Providing or removing partitions;10.1.4Providing false ceiling;10.1.5Gardening;10.1.6White washing;10.1.7Painting;10.1.8Re-tiling and reproofing;10.1.9Plastering and patch work;10.1.10Re-flooring; and10.1.11Construction of sunshades on one's own land.11. Duration of Permission.
- 1 1.1 Every permission granted under these bye laws shall remain valid up to three years from the date such permission is granted for buildings more than 10,000 sqm. built up area the validity duration will be of 5 years. The completion certificate shall have to be submitted within this period. However, in case of failure to submit the completion certificate within the prescribed period, the permission shall have to be revalidated before the expiry of the above period on payment of such fee as may be prescribed by the authority and such revalidation shall be valid for another two years.12. Information at the site of construction.
- 12.1 Whereas tests of any material are made to ensure conformity of the requirements of these bye laws, records of the tests data shall be kept available for inspection during the construction of building and for such period thereafter as required by the Authority.13. Periodic report of Construction.
- 13.1 In case of high rise buildings the builder/owner/applicant shall submit a periodic progress report after plinth level, each roof slab casting in Form-XI to the authority. The process of submission of such reports shall be made easy through an online process. The authority has to make site inspection within 15 days from the date of application and if the construction is found as per bye laws the authority will issue a go ahead certificate to the applicant within 10 days of inspection.14. Inspection procedure. - 14.1 As a matter of course all construction or work for which a permit is required shall be subject to inspection by the Authority at all reasonable hours with prior intimation.
15. Third Party certification.
- 15.1 Accredited architects/engineers may be authorized to do inspection as third party inspection of any building under construction or completed, by the head of the authority.16. Accreditation and gradation of Architects/Engineers.
- 16.1 The accreditation of architects/engineers shall be done by the authority on the basis of their professional experience. The person concerned should have minimum experience of 5 years as registered architect/engineers/technical person in any ULBs/Authorities.| Grade | Minimum Experience | Work Assigned |
| A | 10 Yrs and above | Any work |
| B | More than 8 Yrs | Up to 16.4 meter height |
| C | Minimum 3Yrs | Up to 10 meter height |
| Grade | Minimum Experience | Work Assigned |
| A | 10 Yrs with PG and above | Any work |
| B | More than 8 Yrs | Up to 16.4 meter height |
| C | Minimum 3Yrs | Up to 10 meter height |
17. Cancellation.
- 17.1 If any time after permission to proceed with any building or development work has been given, the Authority is satisfied that such permission was granted in consequence of any material misrepresentation or fraudulent statement contained in the application given or information furnished, the. Authority may cancel such permission and any work done thereafter shall be deemed to have been done without permission.18. Completion of Construction.
- 18.1 The applicant/builder/owner/registered architect/registered engineer shall certify the completion of all building designed by Architect/Engineer. The responsibility of compliance with respect to provisions of these Bye-laws shall rest entirely on applicant/builder/owner19. Certificate for occupancy.
- 19.1 The Authority shall issue a certificate for occupancy for all category of buildings, or for part of a building during its construction, or whole of the building after construction in Performa as Annexed as Annexure VII or refuse occupancy, as the case may be, within 30 days from the date of application.20. Construction not according to plan.
- 20.1 If the Authority finds at any stage that the construction is not being carried out according to the sanctioned plan or is in violation of any of the provisions of these bye laws, it shall notify the owner giving details of deviation and no further construction shall be allowed until necessary corrections in the plan are made and the corrected plan is approved. In case the deviation is within condonable limits, the construction shall not be stopped.21. Single Window Clearance.
- 21.1 The Planning Authority/Authority shall set up a Single Window Clearance system to process all the NOCs and grant permissions. There shall be a Website through which all the applications/documents/forms shall be filed online. The stages of approval/refusal shall also be communicated through the website.22. Construction near important buildings.
- 22.1 The Authority shall take rational view in sanctioning plan near important building like Governor's House. High Court. Heritage building etc.23. Construction near river front.
- 23.1 No construction or re-construction of any building, within a river boundary, or such other higher distance as may be prescribed from time to time by the State Government, from the outer boundary of the river of Ganges (as prescribed by the Irrigation Department), shall be permitted except for repair and renovation work of heritage buildings.24. Unsafe building.
- 24.1 All unsafe buildings shall be considered to constitute danger to public safety and shall be restored by repairs or demolished or dealt with otherwise as directed by the Authority.25. Demolition of building.
- 25.1 Before a building is demolished & the owner shall notify all utilities having service connections within the building, such as water, electricity, gas, sewer and other connections. A permit to demolish a building shall not be issued until a release is obtained from the utilities departments stating that their respective service connections and appurtenant equipment, such as meters and regulators have been removed or sealed and plugged in a safe manner.26. Responsibility and Duty of the Applicant/Builder/Owner.
- 26.1 Neither granting of the permit nor the approval of the drawing and specifications, nor inspections made by the Authority during erection of the, building shall in any way relieve the owner of such building from full responsibility for carrying out the work in accordance with the requirements of these bye laws.27. Responsibility of Authority.
- 27.1 Approval of plans and acceptance of any statement or document pertaining to such plan shall not exempt the owner or person or persons under whose supervision the building is constructed from the responsibilities imposed under these bye laws, or under any other law for the time being in force.28. Zoning.
- 28.1 In the Planning area or areas where various use zones, residential, commercial, industrial, administrative, institutional, open space uses, transport & communication, green belt, natural drainage channel and water bodies having their zonal boundaries have been indicated, they shall be regulated as per the Table 4. Except as otherwise provided no structure or land hereinafter shall be used and no structure shall be erected, re-erected or altered unless its use is in conformity with these bye laws.29. Different use of land.
- 29.1 Permission for different uses shall be accorded outright for principal use earmarked in the different zones described in column (2) of table No 4.| Sl. | Land Uses | Use Zones in which permitted | |||||||||
| R | C | I | P | T | G | E | CUI | CUII | A | ||
| 1. | Airport, Helipad, Flying Club | • | • | ||||||||
| 2. | Art gallery, museum, exhibition centre | • | • | • | • | • | |||||
| 3. | Auto Supply store and show room for motorvehicle and machinery | • | • | • | • | ||||||
| 4. | Automobile service and repairing station | • | • | ||||||||
| 5. | Bank and Safe deposit vault | • | • | • | • | • | • | • | |||
| 6. | Bird Sanctuary | • | • | ||||||||
| 7. | Boarding or lodging house | • | • | • | • | • | |||||
| 8. | Botanical garden | • | |||||||||
| 9. | Bus Depot | • | • | • | • | ||||||
| 10. | Bus Terminal | • | • | ||||||||
| 11. | Canteen and eating house serving the industries | • | • | ||||||||
| 12. | Cemetery, crematorium, burial ground, electriccrematorium | • | • | ||||||||
| 13. | Children Traffic Park | • | • | ||||||||
| 14. | Cinema | • | • | • | • | • | |||||
| 15. | Clinic for pets | • | • | • | • | • | • | ||||
| 16. | Clinical Laboratory | • | • | • | • | • | |||||
| 17. | Club house not conducted primarily as business | • | • | • | • | • | • | ||||
| 18. | Club house or other recreational activesconducted as business | • | • | • | |||||||
| 19. | Cold storage and ice factory | • | • | ||||||||
| 20. | College | • | • | • | |||||||
| 21. | Commercial/business Offices | • | • | • | • | ||||||
| 22. | Commercial hall & welfare center, | • | • | • | • | • | • | ||||
| 23. | Contractor plant and storage for buildingmaterial | • | • | ||||||||
| 24. | Convenience Shopping Center | • | • | • | • | • | • | • | |||
| 25. | Convention Center | • | • | • | • | ||||||
| 26. | Cottage, Handloom and Household Industries | • | • | • | • | • | |||||
| 27. | Court | • | • | • | |||||||
| 28. | Creche and Day Care Center | • | • | • | • | • | • | ||||
| 29. | Cultural and information Center | • | • | • | • | ||||||
| 30. | Customary home occupation | • | • | • | • | ||||||
| 31. | Defence | • | • | • | • | • | • | • | |||
| 32. | Dairy and poultry industry | • | • | ||||||||
| 33. | Dispensary | • | • | • | • | • | • | ||||
| 34. | Dry Cleaners-cleaning and dyeing | • | • | • | • | ||||||
| 35. | Educational and research Institution | • | • | • | • | • | • | ||||
| 36. | Electric Sub-station | • | • | • | • | • | • | • | • | • | |
| 37. | Existing Village | • | • | • | • | • | • | • | • | • | • |
| 38. | Fair Ground | • | • | • | |||||||
| 39. | Film studio | • | |||||||||
| 40. | Fish curing | • | • | • | |||||||
| 41. | Flatted Group Industry | • | • | • | • | ||||||
| 42. | Flood control work | • | • | • | • | • | • | • | • | • | • |
| 43. | Forensic Science Laboratory | • | • | • | • | ||||||
| 44. | Forest | • | • | • | |||||||
| 45. | Gas Godown | • | • | • | • | • | |||||
| 46. | General Industries | • | • | ||||||||
| 47. | Golf course | • | |||||||||
| 48. | Green house | • | • | • | • | • | • | ||||
| 49. | Gymnasium | • | • | • | • | • | • | ||||
| 50. | Health Centre | • | • | • | • | • | • | ||||
| 51. | Hospital | • | • | • | • | • | • | ||||
| 52. | Hostels for educational institution | • | • | • | • | • | |||||
| 53. | Hotel | • | • | • | • | ||||||
| 54. | Indoor Games Hall | • | • | • | • | • | • | • | |||
| 55. | Jail | • | |||||||||
| 56. | Junk yard | • | |||||||||
| 57. | Local, Municipal, State or Central Governmentoffice | • | • | • | • | • | • | • | |||
| 58. | Mechanical workshop with lathes, drills,grinders, spot welding set | • | • | ||||||||
| 59. | Medical, eye and dental practitioners' clinic | • | • | • | • | • | • | ||||
| 60. | Monument | • | • | • | • | • | • | • | • | • | • |
| 61. | Motor Driving Training Center | • | • | • | • | • | |||||
| 62. | Municipal facility (as listed inedia Annex VII) | • | • | • | • | • | • | • | |||
| 63. | Music, dance, drama training centre | • | • | • | • | • | |||||
| 64. | Neighbourhood Shopping Centre-convenience andlocal shopping with vegetables, fruits, flowers, fish and meat. | • | • | • | • | ||||||
| 65. | Night Shelter | • | • | • | • | • | • | • | |||
| 66. | Nursery, Horticulture and Orchards | • | • | • | • | • | • | • | • | • | |
| 67. | Nursing Home | • | • | • | • | • | • | ||||
| 68. | Oil Depot | • | • | • | |||||||
| 69. | Open Air Theatre | • | • | • | • | • | • | • | |||
| 70. | Orphanage | • | • | • | • | • | |||||
| 71. | Park, play ground, playfield and recreationalarea | • | • | • | • | • | • | • | |||
| 72. | Personal Service Shop | • | • | • | • | • | • | • | |||
| 73. | Petrol filling station | • | • | • | • | • | • | • | |||
| 74. | Photograph studio and laboratory | • | • | • | • | • | • | ||||
| 75. | Piggery | • | • | ||||||||
| 76. | Planetarium | • | • | • | • | • | |||||
| 77. | Police Headquarter and Police Lines | • | |||||||||
| 78. | Police Station, Out Post and Fire Station | • | • | • | • | • | • | • | |||
| 79. | Post office, Telephone Exchange, TelegraphOffices | • | • | • | • | • | • | • | |||
| 80. | Professional office of a resident of the premise | • | • | • | • | ||||||
| 81. | Public library | • | • | • | • | • | • | ||||
| 82. | Radio broadcasting studio | • | • | • | |||||||
| 83. | Railway Station | • | • | • | |||||||
| 84. | Reformatory(Juvenile Home) | • | • | • | |||||||
| 85. | Refinery | • | |||||||||
| 86. | Religious Place like temple, Namghar, SameSathal, mosque, church etc | • | • | • | • | • | • | ||||
| 87. | Research and Development Centre | • | • | • | |||||||
| 88. | Residence cum Work Plot | • | • | • | • | ||||||
| 89. | Residential Dwelling | • | • | • | • | • | |||||
| 90. | Residential Plot- Plotted Housing | • | • | • | • | ||||||
| 91. | Restaurant, cafeteria, milk bar | • | • | • | • | • | • | • | • | ||
| 92. | Retail Shop | • | • | • | • | • | • | • | |||
| 93. | Satellite and Telecommunication Center | • | • | • | |||||||
| 94. | Schools | • | • | • | • | • | |||||
| 95. | Service Centre | • | • | • | • | • | • | ||||
| 96. | Sewerage treatment plant | • | • | • | |||||||
| 97. | Social, cultural and religious institution | • | • | • | • | • | |||||
| 98. | Specialised Park/Ground | • | • | • | • | • | |||||
| 99. | Sports Training Center | • | • | • | • | ||||||
| 100. | Stadium | • | |||||||||
| 101. | Storage of petroleum and other inflammablematerials | • | • | ||||||||
| 102. | Storage, Warehouses and Godown | • | • | • | • | ||||||
| 103. | Swimming Pool | • | • | • | • | • | • | ||||
| 104. | Taxi stand and bus stand, cycle and rickshawstand | • | • | • | • | • | • | • | • | ||
| 105. | Theatre, assembly or concert hall, dance andmusic hall and such other place of entertainment; | • | • | • | • | • | |||||
| 106. | Truck terminal | • | • | ||||||||
| 107. | Vending Booth | • | • | • | • | • | • | • | • | ||
| 108. | Vocational Training/Technical Training Institute | • | • | • | • | • | • | ||||
| 109. | Watchmen or caretaker's lodges | • | • | • | • | • | • | • | • | ||
| 110. | Water Treatment Plant | • | • | • | • | • | • | • | • | ||
| 111. | Weekly Market/informal Sector Unit | • | • | • | • | • | • | ||||
| 112. | Wholesale Trade | • | |||||||||
| 113. | Wireless transmitting and weather station,Transmission Tower | • | • | • | |||||||
| 114. | Zoological park | • |
| 1 | All Existing nonnuisance, non-polluting uses to continue in the following usezones:- Residential- Commercial- Industrial- Public/Semi-public- Transportation andCommunication- Composite Use I- Composite Use IIAll existing nonnuisance, non-polluting uses may be allowed to continue/discontinue after an application for special permission to theAuthority in the following use zones:- Recreational- Eco-sensitive-Agricultural |
| 2 | To be permitted in commercial areas to beindicated in Industrial Use Zones in Local Area Plans/LayoutPlans |
| 3 | In Residential use zone, existing uses tocontinue and new ones to come on special permission from theauthority. Refer Annexure - 13.1 |
| 4 | In the New Development proposed RecreationalArea |
| 5 | Only Existing uses to continue |
| 6 | Only those industries as listed in Annexure -13.1 |
| 7 | Permitted only in Heavy Industrial Zone |
| 8 | Existing locations to continue |
| 9 | Permitted only in Heavy Industrial Zone |
| 10 | Permitted only in Heavy Industrial Zone |
| 11 | In commercial centers |
| 12 | In industrial areas |
| 13 | The provision of table 4 shall also beapplicable for village settlement as defined in Master Plan. |
30. Restriction on permission.
- Without prejudice to any other stipulation in these bye laws, no permission to construct a building on a site shall be granted:31. Requirement of Site.
- 31.1 No building shall be constructed on any site on any part of which there is deposited refuse, excreta or other offensive matter objectionable to the Authority. Until such refuse has been removed there from and the site has been prepared or left in a manner suitable for building purposes to the satisfaction of the Authority;32. Distance from Electric lines.
- No verandah, balcony or the like shall be allowed to be erected or re-erected or any additions or alterations made to a building, within the distances 'quoted below between the building and any overhead electric supply line. The minimum distance from the electric line shall be as per Table 5.Table - 5: Minimum distance from electric line| Vertical distance in meters | Horizontal distance in meters | |
| Low and medium voltage lines and service lines | 2.5 | 2.5 |
| High voltage lines up to and including 11.000Volt | Not Permitted | 3.7 |
| High voltage lines above 11.000 volt and up toand including 33,000 Volt | Not Permitted | 3.7 |
| Extra high voltage line beyond 33.000 Volt | Not Permitted | 3.7 (Plus 0.3 meters for every additional 33,000volts or part thereof) |
33. Plantation.
- 33.1 In every building area, at least 5% of the land shall be covered by plantation (tree cover), but in case of multi-storied buildings/Group Housing/Apartment building/Industrial/Assembly/Educational/Institutional buildings, it is desirable that at least 10% of the land shall be covered by plantation (tree cover). Internal gardens within the building shall be encouraged.34. Means of Access.
- 34.1 Every plot shall abut on a public/private means of access like streets/roads of duly formed of width as specified in these byelaws or specified in the Master Plan/Development/Zonal Plan/Scheme.The minimum width of the road/street required for access to a new building in an existing colony not developed by any authorized agency such as Regional Development Authority. Municipality, Housing Board, Co-operative societies, Government and Semi government organization shall be as per Table 6.Table 6; Length of road limitation| Old Area | ||
| SI. No. | Maximum Length of the road in Meter | Minimum width of road of street in Meter |
| (i) | (ii) | (iii) |
| 1 | Upto 50 meter | 3.6 meter |
| 2 | Exceeding 50 meter and upto 100 meter | 5.1 meter |
| 3 | Exceeding 100 up to 300 meter | 6.6 meter |
| 4 | Exceeding 300 meter | 7.5 meter |
| Note-On lessthan 6.1 m. wide roads the encroachment from both sides will beremoved by measuring 3.05 m. from the centre line of the width ofroads declared by or belonging to Road Construction DepartmentJharkhand. Municipal Authorities, Housing Board, CooperativeSocieties, Government and Semi-Government Organizations In othercases maximum 3.05 m. land from such revenue plot on either sidewill be taken into account to make it 6.1 m. wide road and theconstruction falling in between the said width of road will beremoved as an encroachment.Similarly 1.80 m. and 2.55 m. land from eachRevenue plot on either side will be taken into account to make it3.1 m. and 5.1 m. wide road correspondingly | ||
| New Area (Residential) | ||
| SI. No. | Maximum Length of the road in Meter | Minimum width of road of street in Meter |
| 1 | Up to 100 | 6.10 |
| 2 | More than 100 to 250 | 7.5 |
| 3 | More than 250 to 500 | 9.10 |
| 4 | Murc than 500 tv 1000 | 12.20 |
| 5 | More than 1000 | 15.30 |
| Note- If the developments only on oneside of the means of access, the prescribed widths maybe reducedby 1.0 meter each case. In no case, development on plots shall bepermitted unless it is accessible by a public street of width notless than 6 m. | ||
| New Area (Non residential) | ||
| Sl. No. | Maximum Length of the road in Meter | Minimum width of road of street in Meter |
| 1 | 200 | 7.5 |
| 2 | 400 | 9.1 |
| 3 | 600 | 12.2 |
| 4 | above 600 | 15.30 |
35. Minimum size of plots and road width.
- 35.1 The minimum size of plots and road width for different categories of building is given in Table 7.Table - 7: Category wise size of plots| Category | Min. road width (m) | Min. size of plot in Sqm. |
| Marriage Halls | 12.20 | 1000 |
| Cinema, Multiplex, Shopping Malls, Conventioncenters, Game centers. | 18.30 | 2000 |
| Social clubs and amenities | 12.20 | 1000 |
| Multi storey car parking | 12.20 | 1000 |
| Office buildings | 12.20 | 300 |
| Primary/Upper Primary school | 09.00 | 2000 |
| I figh School, Residential School | 12.20 | 6000 |
| +2 College/Junior College | 12.20 | 4000 |
| Degree College | 12.20 | 6000 |
| Technical educational institution | 12.20 | 10000 |
| Petrol Pumps/Fill ing stations | 12.20 | 500 |
| Restaurant | 12.20 | 500 |
| LPG storages | 12.20 | 500 |
| Places of congregation | 12.20 | 500 |
| Public libraries | 12.20 | 300 |
| Conference hall | 12.20 | 1000 |
| Community hall | 12.20 | 500 |
| Nursing homes/polyclinics/Hospital | 12.20 | 300 |
| Hotel (below three star) | 12.20 | 1000 |
| Hotel (three star and above) | 18.30 | 2000 |
| R&D Lab | 18.30 | 1500 |
| Group Housing | 6.10 | 3000 |
36. Minimum setbacks & Height for non-high rise buildings.
| Sl. | Average Depth of plot (In meters) | Building Height Upto G+2 Maximum-10m | Building Height Upto G+3 Maximum-13.3m | Building Height Upto G+4 Maximum-16.4m | |||
| Minimum Front set back (m) | Minimum Rear set back (m) | Minimum Front set back (m) | Minimum Rear set back (m) | Minimum Front set back (m) | Minimum Rear set back (m) | ||
| (i) | (ii) | (iii) | (iv) | (v) | (vi) | (vii) | (viii) |
| 1 | Upto 10m | 1.5 | 0.90 | No construction shall be permitted | No construction shall be permitted | ||
| 2 | Exceeding 10m & upto 15m | 2.0 | 1.5 | 3.0 | 1.5 | No construction shall be permitted | |
| 3 | Exceeding 15m & upto 21m | 2.5 | 1.5 | 3.0 | 1.8 | 3.0 | 3.0 |
| 4 | Exceeding 21m & upto 27m | 3.0 | 1.8 | 3.0 | 2.0 | 3.5 | 3.0 |
| 5 | Exceeding 27m & upto 33m | 4.0 | 2.5 | 4.0 | 3.0 | 4.0 | 3.5 |
| 6 | Exceeding 33m & upto 39m | 4.0 | 3.0 | 4.5 | 4.0 | 4.5 | 4.0 |
| 7 | Exceeding 39m & upto 45m | 4.0 | 4.0 | 4.5 | 4.0 | 5.0 | 4.5 |
| 8 | More the 45m | 4.0 | 4.0 | 5.0 | 5.0 | 6.0 | 5.0 |
| Sl. | Average Width of plot (in meters) | Building Height Upto G+2 Maxmimum-10m | Building Height G+3 Upto Maxmimum-13.3m | Building Height Upto G+4 Maximum-16.4m | |||
| (i) | (ii) | (iii) | (iv) | (v) | (vi) | (vii) | (viii) |
| 1 | Upto 10m | At least one side from 0.90 m. | No construction shall be permitted | No construction shall be permitted | |||
| 2 | Exceeding 10m & upto 15m | 0.90 | 0.90 | 0.90 | 0.90 | No construction shall be permitted | |
| 3 | Exceeding 15m & upto 21m | 1.0 | 1.0 | 1.5 | 1.5 | 2.0 | 2.0 |
| 4 | Exceeding 21 m & upto 27m | 1.5 | 1.5 | 2.0 | 2.0 | 2.5 | 2.5 |
| 5 | Exceeding 27m & upto 33m | 1.5 | 1.5 | 2.5 | 2.5 | 3.0 | 3.0 |
| 6 | Exceeding 33m & upto 39m | 2.0 | 2.0 | 3.0 | 3.0 | 3.66 | 3.66 |
| 7 | Exceeding 39m & upto 45m | 3.0 | 3.0 | 3.66 | 3.66 | 4.50 | 4.50 |
| 8 | More the 45m | 3.66 | 3.66 | 4.00 | 4.00 | 5.00 | 5.00 |
| Sl. | Average Depth of plot (In meters) | Building Height up to 16.4 m | |
| Minimum Front set back (m) | Minimum Rear set back (m) | ||
| (i) | (ii) | (iii) | (iv) |
| 1 | Upto 10m | No construction is allowed | |
| 2 | Exceeding 10m & upto 15m | 4.5 | 3.0 |
| 3 | Exceeding 15m & upto 21m | 5.5 | 4.0 |
| 4 | Exceeding 2Im & upto 27m | 6.0 | 4.0 |
| 5 | Exceeding 27m & upto 33m | 6.5 | 4.0 |
| 6 | Exceeding 33m & upto 39m | 7.0 | 4.5 |
| 7 | Exceeding 39m & upto 45m | 7.5 | 4.5 |
| 8 | More than 45m | 8.0 | 5.0 |
| Sl. | Average width of plot (In meters) | Building Hei ht up to16.4m | |
| Minimum Left set back (m) | Minimum Right set back (m) | ||
| (i) | (ii) | (iii) | (iv) |
| 1 | Upto 10m | At least one side 1.5 m. | |
| 2 | Exceeding 10m & upto 15m | 2.0 | 2.0 |
| 3 | Exceeding 15m & upto 2Im | 2.5 | 2.5 |
| 4 | Exceeding 21m & upto 27m | 3.0 | 3.0 |
| 5 | Exceeding 27m & upto 33m | 4.0 | 4.0 |
| 6 | Exceeding 33m & upto 39m | 4.0 | 4.0 |
| 7 | Exceeding 39m & upto 45m | 5.0 | 5.0 |
| 8 | More than 45m | 5.5 | 5.5 |
| Sl. | Plot Size | Minimum Front set back (m) | Minimum Rear set back (m) | Minimum Sides set back (m) |
| (i) | (ii) | (iii) | (iv) | (v) |
| 1 | 550 sqm to 1000 sqm | 9.0 | 4.5 | 4.5 |
| 2 | 1000 sqm to 5000 sqm | 10.0 | 6.0 | 6.0 |
| 3 | 5000 sqm to 30000 sqm | 12.0 | 9.0 | 9.0 |
| 4 | Above 30000 sqm | 15.0 | 12.0 | 10.0 |
| Sl. | Width of Plot | Minimum Front set back (m) | Minimum Rear set back (m) | Minimum Sides set back (m) |
| (i) | (ii) | (iii) | (iv) | (v) |
| 1 | Upto 10 mtrs. | 3.0 | 3.0 | 1.5 |
| 2 | Exceeding 10m & upto 12m | 4.0 | 3.0 | 2.0 |
| 3 | Exceeding 12m & upto 15m | 5.0 | 3.0 | 3.0 |
| 4 | Exceeding 15m & upto 18m | 6.0 | 4.0 | 4.0 |
| 5 | Exceeding 18m | 6.0 | 4.5 | 4.5 |
37. Minimum setbacks for high rise buildings.
| Sl. | Height of the Building Upto (m) | Exterior open spaces to be left out on allsides in m. | |
| Front setback | Side and Rear setback | ||
| 1 | More than 16.4 and upto 19.25m | 6.5 | 4.5 |
| 2 | More than 19.25m and upto 23.10m | 7.5 | 4.5 |
| 3 | More than 23.10m and upto 30m | 8.0 | 5.0 |
| 4 | In case of buildings of more than 30m height, forevery increase in height of 3.35m. or fraction thereof oraddition of one floor, 1m. in the front set back and 0.75 m. inthe sides and rear setbacks shall be added. |
| Coverage of Building | Maximum ground coverage |
| 1. Up to 235 sqm. of plot and building ht. notexceeding 10m. | -70% |
| 2. Up to 1000 sqm. of plot and building ht. upto 16.4m. | -60% |
| 3. Above 1000 sqm. of plot area or building ht.of more than 16.4m. | -50% |
| 4. For commercial uses ground coverage is 50% ofthe plot area. |
38. General Conditions for Setback.
- 38.1 In case of more than one block of buildings are constructed on the same the plot, the minimum distance between the two blocks shall be 6in. (Six meter) or 1.5 times side setback required for the taller block whichever is higher. Basement can be constructed in this open area in between the buildings, top of which may be used as passage and garden and if used for vehicular passage the roof slab should have sufficient strength for the fire of engine 45 tones.39. Floor Area Ratio.
- 39.1 The Floor Area Ratio (F.A.R) for buildings shall be decided on the basis of the road width on which the plot/site abuts as per Table 15 and 16 and with upper limit for various ULBs as indicated in Annexure-III.Table 15: Road width and FAR table for (Old Area)| Category | Road Width (in meter) | FAR | Floor | Maximum Height (in meter) | Conditions | |
| Residential | Non residential | |||||
| 0-I | 3.60(12 ft.)to less than 4.80m | 1.5 | Nil | C+2 | 10.0 | |
| 0-II | 4.80 (16 ft.)to less than6.10m | 1.8 | Nil | G+2 | 10.0 | |
| 0-III | 6.10 (20 11.) to less than 7.5m | 2.0 | 2.0 | G+4, S+4 | 16.4 | Parking shall beallowed on any floor. Under no circumstances the parking floorsorprovision for parking shall be used for anyother purposes. Mezaninine floors or any floor partition shall becomputed under FAR and counted as a floor. |
| 0-IV | 7.5 (25 ft.)to less than 9.10m | 2.5 | 2.5 | G+5 S+5 | 19.25 | |
| 0-V | 9.10 (30 ft.)to less than 12.20m | 2.5 | 2.5 | G+6 S+6 | 23.10 | |
| 0-VI | 12.20 (40 ft.)to less than 18.30m | 2.5 | 2.5 | Maximum Height 30 meter | ||
| 0-VII | 18.30 (60 II) and above | 2.5 | 3.00 | No restriction on height and number of floorshowever it may be regulated by the master plan/developmentplan/zonal plan. |
| Category | Road Width (in meter) | FAR | Floor | Maximum Height (in meter) | Conditions | |
| Residential | Non residential | |||||
| N-I | 6.10 (20 ft.) to less than 7.5m | 2.0 | 2.0 | G+4 S+4 | 16.4 | Parking shall be allowed on any floor. Under nocircumstances the parking floors or provision for parking shallbe used for any other purposes. Mezzanine floors or any floorpartition shall be computed under FAR and counted as a floor. |
| N-II | 7.5 (25 ft.)to less than 9.10m | 2.5 | 2.5 | G+4 S+4 | 19.25 | |
| N-III | 9.10 (30 ft.)to less than 12.20m | 2.5 | 2.5 | S+5 | 23.10 | |
| N-IV | 12.20 (40 ft.)to less than 18.30m | 2.5 | 2.5 | Maximum Height 30 meter | ||
| N-V | 18.30 (60 ft) to less than 24.40m | 2.5 | 3.0 | Height restriction as per rule-39 and 40.1.1 | ||
| N-VI | 24.40 (80 ft.) and above | 3.0 | 3.0 |
40. Height of a building.
- 40.1 The height of the building shall be governed by the limitations of Floor Area Ratio, open space (setbacks), and the width of the street facing the plot described as detailed below:40.1.1The maximum height of a building shall in no case exceed (1.5 times the width of the road on which the plot abuts) + Road widening + the front setback.40.1.2If a building abuts on two or more streets of different widths, the building shall be deemed to face upon the street that has the greater width and the height of the building shall be regulated by the width of that street.| Distance from nearest runway end (In metres) | Maximum Permissible height above the elevation ofthe nearest runway end |
| Up to 360 | 0 |
| 631 to 510 | 6 |
| 511 to 660 | 9 |
| 661 to 810 | 12 |
| 811 to 960 | 15 |
| 961 to 1110 | 18 |
| 1111 to 1260 | 21 |
| 1261 to 1410 | 24 |
| 1411 to 1560 | 27 |
| More than 1560 | 30 |
| Distance of the Inner Boundary of theTransitional Area (Outer Boundary of the Air Port) [Metres] | Maximum Permissible height above the elevation ofthe airport reference point [metres] |
| Up to 21 | 0 |
| 22 to 42 | 3 |
| 43 to 63 | 6 |
| 64 to 84 | 9 |
| 85 to 105 | 12 |
| 106 to 126 | 15 |
| 127 to 147 | 18 |
| 148 to 168 | 21 |
| 169 to 189 | 24 |
| 190 to 210 | 27 |
| More than 210 M | 30 |
41. Off Street Parking Space.
- 41.1 In all buildings including Apartment buildings/Group Housing, Hotels, Restaurants and Lodges, business buildings, commercial buildings, Institutional buildings like hospitals, Educational buildings like schools and colleges, multi-storied buildings/complexes etc. and all other non-residential activities provision shall be made for parking spaces as per the require vents mentioned in table 19.Table 19: Parking space for different category of occupancies| Sl. | Occupancy Type | One Car Parking For Every or Fraction Thereof:(The Minimum Size of a Car Parking Stall Shall be 2.40mx 4.80m.,and Minimum Stall Length of 5.40m. For Parallel Parking, With aMinimum Driveway Width of 4.25 M.) | |||
| Population up to 50,000 | Population up to 1,50,000 | Population up to 10,00,000 | Population 10,00,000 and above | ||
| 1 | Residential a)Multi-Familyb) Lodging establishment, tourist homes andhotels with lodging accommodation | 1 apartment8 guest rooms | 1 apartment6 guest rooms | 1 apartment4 guest rooms | I apartment of builtarea up to 140 sq. m. and 0.5 apartment of built area above 140sq.m3 guest rooms |
| 2 | Educational ( see Note 1) | 150 sq.m of area of the administrative officearea and public service area | 100 sq.m of area of the administrative officearea and public service area | 70 sq.m of area of the administrative officearea and public service area | 50 sq.m of area of the administrative officearea and public service area |
| 3 | institutional (Medical) | 10 bed (Private) 15 beds (Public) | 7 bed (Private) 12 beds (Public | 5 bed (Private) 10 beds (Public | 2 bed (Private) 5 beds (Public |
| 4 | Buildings for PublicGatheringa) Assembly halls, Cinema theatres and Auditoriab) Restaurants(Including Restaurants in Lodging establishment, tourist homesand hotels with lodging accommodation)c) Stadiad) exhibition centres | 25 seats20 seats200 seats | 15 seats20seats100 seats | 10 seats10seats40 seats | 10 seats10seats20 seats |
| 5 | Commercial a)Business offices and firms for private businessb) Public orsemi-public officesc) Mercantile (see note 3) | 200 sq.m. of built uparea excluding parking and services areas300 sq.m. of built uparea excluding parking and services areas200 sq.m. of built up area excluding parking andservices areas | 150 sq.m. of built uparea excluding parking and services areas200 sq.m. of built uparea excluding parking and services areas100 sq.m. of built up area excluding parking andservices areas | 100 sq.m. of built uparea excluding parking and services areas100 sq.m. of built uparea excluding parking and services areas100 sq.m. of built up area excluding parking andservices areas | 75 sq.m. of built uparea excluding parking and services areas75 sq.m. of built uparea excluding parking and services areas75 sq.m of built up area excluding parking andservices areas |
| d) Industriale) Storage | 400 sq.m.600 sq.m. | 300 sq.m.500 sq.m. | 200 sq.m.400 sq.m. | 100 sq.m.250 sq.m. |
2. For other institutions, transport, communication center and occupancy types not mentioned above, parking requirements shall be decided by the authority.
3. For shops on plots up to 50 sq.m. parking space need not be insisted upon.
4. For all apartment/multi dwelling of residential buildings:
5. All non-residential buildings should provide one third area, out of the total car parking area, for parking of two wheelers. These two wheeler parking should have a minimum size of 1 m x 2 m. excluding the driveway. The minimum width of the drive way meant exclusively for 2 wheelers should be 3m.
6. In addition to the parking spaces provided for building of mercantile (commercial) Industrial and storage type, one space of 3.50X7.50 meters for loading and unloading activities, for each 2000 sqm. of total area (as per FAR calculation) or fraction thereof shall be provided
42. Requirement of Parts of Building.
- The various parts of the buildings shall have the following minimum specifications.43. Exit Requirements.
- 43.1 GeneralEvery building meant for human occupancy shall be provided with exits sufficient to permit safe escape of occupants, in case of fire or other emergency.43.1.1In every building exit shall comply with the minimum requirement of exit.43.1.2All exits shall be free from obstructions.43.1.3No building shall be altered so as to reduce the number, width of protection of exits to less than that required.43.1.4Exits shall be clearly visible and the routes to reach the exits shall be clearly marked and signposted to guide the population of floor concerned.43.1.5Adequate and reliable illumination shall be provided for exits.43.1.6Firefighting equipment shall be suitably located and clearly marked.43.1.7Alarm devices shall be installed to ensure prompt evacuation of the population concerned.43.1.8All exits shall provide continuous means of egress to the exterior of building or to an exterior open space leading to street.43.1.9Exits shall be so arranged that they may be reached without passing through another occupied unit.| Sl. | Type of Occupancy | Number of occupants per unit exit | |
| Stair Case | Door | ||
| (1) | (2) | (3) | (4) |
| 1 | Residential | 25 | 75 |
| 2 | Educational | 25 | 75 |
| 3 | Institutional | 25 | 75 |
| 4 | Assembly | 60 | 90 |
| 5 | Business | 50 | 75 |
| 6 | Mercantile | 50 | 75 |
| 7 | Industrial | 50 | 75 |
| 8 | Storage | 50 | 75 |
| 9 | Hazardous | 25 | 10 |
44. Interior open space.
- 44.1 At least one side of all the rooms intended for human habitation, if such room does not abut on the front or the rear or the side setbacks, shall abut on an interior open space whose minimum dimension shall be 3 meters X 3 meters in cases of buildings up to a height of 12meters. In cases where the height of the building is more than 12meters, the width of the interior open space shall be increased at the rate of one meter for every additional 3 (three) meters height. This provision shall be applicable to all categories of buildings, like residential, group housing, commercial. institutional, administrative. assembly etc.45. Height exemption of a building.
- Any exemption to height shall not be taken in account in case of AAI approval. The following appurtenant structures shall not be included in the height of the building.46. Exemption in Open space.
- 46.1 Every open space provided either in the interior or exterior in respect of any building shall be kept free from any erection thereon and shall be open to the sky and no cornice, roof, or weather shade of more than 0.75 m. in width shall overhang or project over such open space.47. Mezzanine.
- 47.1 Mezzanine floor may be permitted above any floor in all types of buildings up to an extent of one-third of the actual covered area of that floor. All Mezzanine floors shall be counted toward FAR calculation.The mezzanine floor shall have a minimum clear height of 2.10 m The minimum size of the mezzanine floor, if it is to be used as a living room, shall not be less than 9.5 Sq meter. The aggregate area of such mezzanine floor in a building shall in no case exceed one- third the plinth area of the building.48. Basement/Cellar.
- 48.1 Basements/cellars shall not be permitted in low lying area and without adequate drainage facilities to ensure drainage from the basement. Basement shall not be allowed in flood prone areas.49. Provision of Lift.
- 49.1 For Residential49.1.1For no. of flats more than 8 and up to 18, one lift of the capacity of 6 passengers will be mandatory for G+4 and above.49.1.2For every 16 flats and part thereof one lift of the capacity of 6 passengers shall be provided for residential buildings up to G+4 or of the height of 12 meters and above.49.1.3However in case, where part thereof is less than 50%, then the requirement can be met by increasing the passenger capacity of lift.49.1.4If the number of flats in a multi-storied residential building is more than 12, the provision of lift will be compulsory for G+3, even if the height of the building is less than 12meters. The capacity and no. of lifts shall be as mentioned above.49.1.5Provision of lift should be made for residential buildings of more than G+3 storied or buildings having the height of 12 meters , whichever is lower49.1.6Provision of one stretcher lift every building more than 6 storey height49.1.7Every lift should have Provision of automatic rescue device, door sensor and automatic fire proof door.2. All sizes of lift (i.e. car inside, lift well, entrance, headroom etc.) shall be as per the requirements of N.B.C. or as per manufacturers specifications.
3. All lifts shall be inspected at least once a year by the agency designated by the Authority. The Authority can also outsource the inspection of lifts.
4. The area of lift well at one floor only (not the sum of total area of lift well at every floor) shall be counted for F.A.R calculation.
50. Barrier free access for the differently abled person.
- 50.1 Barrier free environment is one, which enables people with disabilities to move about safely and freely and to use all facilities within the built environment. The goal of barrier free design .is to provide an environment that supports the independent functioning of individuals so that they can get into and participate in all activities without assistance.51. Rainwater harvesting system.
- 51.1 Provision of rainwater harvesting shall be mandatory for 300 sqm. and above size of plots-The dimension of recharging pits/trenches shall be at least 6 cubic meters for every 100 Sqm. of roof area. Percolation Pits shall be filled with small pebbles or brick jali or river sand and covered with perforated concrete slabs. Apart from this, the following requirements are optional and may be provided depending on site conditions.52. Signs and outdoor display structures.
- 52.1 Signs and outdoor display structures shall be governed by the relevant provisions of the area where no specific guideline for the above structures is framed; the Authority shall prescribe the guidelines with approval of Government.53. Lightening Protection.
- 53.1 To arrest Lightening, provision of lightening conductor is mandatory in the all types of buildings as per NBC-2005 norms.54. Penal Action against Builders/Technical Personnel.
- 54.1 Not withstanding anything contained in these regulations, the Authority reserves the right to debar/black list the builder/technical person who have deviated from the professional conduct or has made any fraudulent statement or has misrepresented/suppressed any material facts in his application/plan or is involved in construction of the building deviating from the approved plan/norms of these bye laws.55. Builder to register an association.
- 55.1 The builder shall cause to register an Association of apartment owners as required under The Jharkhand Apartment Ownership Act, 2006 before occupancy certificate for minimum of 50% or more of the floor area is given.56. Reference to the standards.
- The following standards shall be referred while preparing the design of the building:57. Life Safety.
- The building design shall comply to the provisions of life safety as mentioned in National Building Code 2005 (Group-I Part-TV Fire and Life Safety-4) or wherever applicable and the applicant shall reflect compliance of these provisions in completion certificate.Chapter - V Additional Requirements for Saftey and Services58. For construction of Multi-storied building.
- 58.1 Construction of multi- storied building shall not be permitted villages/wards/municipalities/planning areas specified by the State Government. The Authority may include or exclude any other areas for prohibition of multi storied building from time to time.| Sl. | Height of Building | Area (sqm.) | Min. Width (in meter) |
| 1 | Upto 12.00 meter | 1.2 | 0.9 |
| 2 | Upto 16.00 meter | 2.8 | 1.2 |
| 3 | Upto 22.00 meter | 4.0 | 1.5 |
| 4 | Upto 28.00 meter | 5.4 | 1.8 |
| 5 | Upto 34.00 meter | 8.0 | 2.4 |
| 6 | Above 34.00 meter | 9.0 | 3.0 |
59. Maintenance.
- 59.1 In case of buildings with a height of 15.0 meters and above or ground coverage more than 500 sqm., the main entrance to the premises shall not be less than 5 (five) meters in width in order to allow easy access to fire engine. The gate shall fold back against the compound wall of the premises, thus leaving the exterior access way, within the plot, free for the movement of fire service vehicles. If archway is provided over the main entrances, the height of the archway shall not be less than 5 (five) meters.60. Structural Safety Design, Standards and other Services requirements.
- 60.1 All buildings shall comply with the standards as mentioned below:Structural Design: The structural design of foundation, elements of masonry, timber, plain concrete, reinforced concrete, prestressed concrete and structural steel shall be carried out in accordance with Part-6 of Group-2 structural design and related aspects, section-I loads, forces and effects] section-2 soils and foundations, section-3 Timber and bamboo, 3A timber, 3B bamboo, section-4 masonry, section-5 concrete, 5A plain and reinforced concrete, 5B pre stressed concrete and section-6 steel, section-7 prefabrication, systems building and mixed/composite construction, 7A prefabricated concrete, 7B systems building and mixed/composite construction of National Building Code of India, 2005 taking into consideration all relevant Indian Standards prescribed by Bureau of Indian Standards including the Indian Standard as given below for structural safety. In case of High Rise Buildings a Certificate of Under Taking for Hazard Safety Requirement shall be submitted in Form-XIV.1. IS: 456:2000 "Code of Practice for Plain and Reinforced Concrete
2. IS: 800-1984 "Code of Practice for General construction in Steel
3. IS: 801-1975 "Code of Practice for Use of Cold Formal Light Gauge Steel Structural Members in General Building Construction
4. IS 875 (Part 2): 1987 Design loads (other than earthquake) for buildings and structures Part 2 Imposed Loads
5. IS 875 (Part 3): 1987 Design loads (other than earthquake) for buildings and structures Part 3 Wind Loads
6. IS 875 (Part 4): 1987 Design loads (other than earthquake) for buildings and structures Part 4 Snow Loads
7. IS 875 (Part 5): 1987 Design loads (other than earthquake) for buildings and structures Part 5 special loads and load combination
8. IS: 883:1966 "Code of Practice for Design of Structural Timber in Building
9. IS: 1904:1987 "Code of Practice for Structural safety or Buildings: Foundation"
10. IS 1905:1987 "Code of Practice for Structural Safety of Buildings: Masonry Wall
11. IS 2911 (Part I): Section 1: 1979 "Code of Practice for Design and Construction of Pile Foundation Section 1
12. IS: 1893-2002 "Criteria for Earthquake Resistant Design of Structures (Fifth Revision)"
13. Is: 13920-1993 "Ductile Detailing of Reinforced concrete Structures subjected to Seismic Forces - Code of Practice"
14. IS:4326-1993 "Earthquake Resistant Design and Construction of Buildings- Code of Practice (Second Revision)"
15. IS: 13828-1993 "Improving Earthquake Resistance of Low Strength Masonry Buildings - Guidelines"
16. IS:13827-1993 "Improving Earthquake Resistance of Earthen Buildings - Guidelines",
17. IS: 13935-1993 "Repair and Seismic Strengthening of Buildings - Guidelines"
61. Housing Schemes.
-| 61.1 | Minimum Size of the Plot | - | 3000 sqm. |
| 61.2 | Maximum Ground Coverage | - | 35% |
| 61.3 | Maximum F.A.R | - | 3.0 |
| 61.4 | Height Limitation |
| Area | Rate for sqm. |
| Ranchi Regional Development Authortity/RanchiMunicipal Corporation/Dhanbad Municipal Corporation | Rs. 13,000.00 |
| Other Municipal Corporations | Rs. 11,000.00 |
| Mango Notified Area Committee Jamshedpur,Jugsalai Municipality | Rs. 13 000.00 |
| Other Municipalities, Nagar Panchayats and otherRural Local Bodies falling in Regional Development Authority Area(Except RRDA)/UDA area/Master Plan areas | Rs. 8,000.00 |
62. Semi-detached and row housing.
- 62.1 Owners of adjacent similar dimension plot abutting a road may be permitted to construct row or semi-detached buildings.63. Shop-cum-residence.
- 63.1 Where plots are in a row for shop-cum-residential purpose the Authority may allow construction of shop-cum-residential building without any side set backs up to a depth of 10 meters from the front exterior wall. Provided that no part of the building up to said depth is used for residential purpose on the ground floor. No building exceeding 12 meters in height shall be allowed to be constructed as a shop-cum-residential plot, unless so permitted under the zonal Development Plan, provided that the shop-cum-residence shall have 2/3rd of the total floor area used for shops. The FAR and other parameters shall conform to that specified for commercial buildings.64. Cinema, Multiplex and Theatre building.
- 64.1 The relevant provisions of the Jharkhand Cinemas (Regulation) Act, 1954 or any other relevant act shall apply for planning, designing and construction of Cinema and Theatre buildings.65. Liquefied Petroleum Gas.
- 65.1 Vacant space shall be maintained at all times, with the following distances for storage shed used for the storage of liquefied petroleum gas cylinders between any building, public space, public road or any adjoining property which may be built upon and the said storage shed. The minimum clear distance shall be as per Table 21.Table - 21: Minimum distances required for storage shed of liquefied petroleum gas cylinders| Quantity of Compressed Gas in Cylinders (Kg.) | Minimum Clear Distance to be Kept (meters) |
| 0-100 | 1 |
| 101-1000 | 3 |
| 1001-4000 | 5 |
| 4001-8000 | 7 |
| 8001-12000 | 9 |
| 12001-30,000 | 12 |
| Over 30,000 | 15 |
66. Petrol Pump.
- 66.1 Minimum distance from the road intersections shall be:A. For minor roads having less than 30 in. width - 50 m.B. For major roads having width 30 m. or more -100 m.| 66.6.1 | Ground coverage | - | 20% |
| 66.6.2 | FAR | - | 1.0 |
| 66.6.3 | Max Height | - | 7m |
| 66.6.4 | Canopy equivalent to permissible ground coveragewithin setback line, | ||
| 66.6.5 | Front set back - minimum 9 m |
67. Farm House.
- 67.1 For construction of Farm House Building in Agriculture and Forest use Zone| A | Maximum permissible ground coverage for alltypes of activity | 10 % |
| B | Maximum permissible FAR | 0.20 |
| C | Residential accommodation of watch andward/maintenance staff | 40 sqm. |
| D | Maximum height | 7m. |
| E | Setbacks | Front/side abutting road 15.0 m. and all othersides 9.0 |
68. Application.
- 68.1 Applications for subdivision of land for utilizing selling, leasing out or otherwise disposing it off shall be made to the Authority in Form-1.69. Use in relation to Development Plans.
- 69.1 Subdivision of land shall normally be permitted for the purpose for which the concerned land is earmarked in the development plan. Such subdivision may be for residential, commercial industrial, institutional or combination of one or more of this purpose or such other purpose as may be considered conforming to the provisions in the development plan: provided that in every subdivision plan spaces for roads, community facilities and public utilities as specified in this part or such other facilities as the Authority may determine shall be incorporated.70. Size of the plot and road width.
- 70.1 Minimum Road Widths for Subdivision in Residential Area: No subdivided plot will be less than 50 sqm. However the Authority reserves the right to relax in special cases such as EWS housing. The size of the plot shall be according to the relevant sub-division of plot size in the zones as per Table-23.Table-23: Minimum road widths for sub division in residential area| Sl. | Length of road in (m) | Min. width of road** (m) |
| 1 | Up to 250 | 9.0 |
| 2 | Above 250 up 500 | 12.0 |
| 3 | Above 500 to 1000 | 15.0 |
| Class of Road | Width (m) | Maximum length permissible (m) |
| 1 | 12 | 200 |
| 2 | 18 | 600 |
| 3 | 24 | Above 600 |
71. Area for development.
- 71.1 Apart from the provision for amenities and open spaces, the area for residential development shall be up to maximum of 50% of the total land area.72. Park and Open Spaces.
- 72.1 Parks and open spaces shall not be less than 10% of the total land area. This shall be relinquished to the Authority and if required, the Authority may handover area over for maintenance to the residents welfare association or owner or developer. If the site is not utilized for which it is leased out within a prescribed period, it will be resumed back to the Authority.73. Community facilities.
- 73.1 Community facilities shall be provided minimum 10% of the plot area.74. Exemptions.
- 74.1 In case of developable area for residential development is less than 50% by providing for Master Plan roads or any other road or due to statutory reasons, prescribed by the Authority in a layout, the applicant may be exempted from complying with civic amenities reservation.75. Submission of layout plan.
- 75.1 The layout plan may be submitted for approval to Authority by the signature of the members of the concerned Society in lieu of Secretary/president of the society. Even a single member of the Society may apply with his signature, if he is authorized by all the members of the society for doing the same.76. Incentive for solar heating & lighting and waste water recycling.
- Duly admissible incentive for installing Solar Heating, Lighting and Waste Water Recycling may be given by the Authority after assessing the installation.Chapter IX
Compounding, Penalties and Compliance
77. Restriction on Compounding.
- 77.1 Any deviation pertaining to unauthorized development shall not be compounded;7.1.1Where construction has been undertaken on Government land or land belonging to local body or land not owned by the person undertaking such development;77.1.2Where development has been undertaken un-authorized within the prohibited limits of any ancient or archaeological monuments.77.1.3Where such developments interfere with the natural drainage of the locality;77.1.4Where development has been undertaken un-authorized over the area earmarked/approved for parking; and,77.1.5Where road or drain whether public or private, whether constructed or natural, has been encroached.77.1.6Where number of floors has been increased from permissible limit/sanctioned map.78. Compounding Rate.
- 78.1 Compounding Rates for various categories shall be as per Table- 25;Table 25: Compounding rates| Sl. | Situations | Compounding fees (in Rs.) per sqm. for theviolated area | |
| Residential/Institutional | Others | ||
| 1 | Where development has been undertaken withoutpermission, but within the framework of use restrictions and theprovisions of the Bye laws applicable to concerned plot | 10000 | 15000 |
| 2 | Constructions beyond permission but within thelimit of 10% as mentioned as in section-77.3.3 in bye-laws of thegross areas on all floor thus in violation beyond the permittedsetback line or beyond the permissible limit of FAR | 15000 | 25000 |
79. Compounding amount.
- 79.1 At least 50% of the compounding amount shall be utilized for development of public utility services and protection of heritage sites and structures.80. System for monitoring.
- 80.1 A system for monitoring shall be put in place by all authorities to ensure that the Bye laws are followed and prompt action shall be taken in case of violation of these bye laws.81. Telecom Tower Permission.
- 81.1 Telecom Tower Permission with appropriate fees, should be obtained from the authority before erection on prescribed forms with certificate for structural safety from the competent Engineer. An application form for the erection of telecom/phone tower for obtaining N.O.0 from Authority on form Annexure-IV. Fee shall be as per Jharkhand Communication Tower and Related Structure Policy, 2015. NOC shall be issued within maximum 60 days from date of application if relevant papers in order. Certificate of permission/NOC and related indemnity bond format shall be as per above mention policy, subject to approval from Airport Authority as and where required.Chapter - X E-Governance and Service Delivery82. E-Governance.
- 82.1 The State Government shall set up an integrated E-Governance system to be used by all the authorities. All the applications and the associated documents to be submitted to the various authorities under these byelaws shall be submitted through the E-Governance system.83. "Affordable Housing Project".
- shall mean housing projects where 35% of the houses are constructed for EWS/LIG category.| Length of road limitation | ||
| Sl. | Maximum Length of the road in Meter | Minimum width of road of street in Meter(Inclusive of passive Development) |
| (i) | (ii) | (iii) |
| 1 | Upto 100 m | 3.6 meter 5.1 |
| 2 | Exceeding 100 meter and upto 300 meter | 4.5 meter 6.6 |
| 3 | Exceeding 300 | 6.6 meter 7.5 |
| Sl. | Average Depth of plot (In meters) | Building height Upto G+2 Maximum-10m | Building Height Upto G+3 Maximum-12m | Building Height Upto G+4 Maximum-15m | |||
| Minimum Front set back (m) | Minimum Rear set back (m) | Minimum Front set back (m) | Minimum Rear set back(m) | Minimum Front Rear set back(m) | Minimum set back (m) | ||
| (i) | (ii) | (iii) | (iv) | (v) | (vi) | (vii) | (viii) |
| 1 | Exceeding 15m & upto 33m | 3.0 | 1.8 | 3.0 | 2.0 | 3.0 | 2.0 |
| 2 | Exceeding 33m & upto 45 m | 4.0 | 3.0 | 4.5 | 3.0 | 4.5 | 3.5 |
| 3 | More the 45m | 4.0 | 3.0 | 4.0 | 4.0 | 5.0 | 5.0 |
| Sl. | Average Width of plot (In meters) | Building Height Upto G+2 Maximum-10m | Building Height Upto G+3 Maximum-12m | Building Height Upto G4-4 Maximum-15 m | |||
| (i) | (ii) | (iii) | (iv) | (v) | (vi) | (vii) | (viii) |
| 3 | Exceeding 15m & upto 27m | 1.5 | 1.5 | 1.5 | 1.5 | 2.0 | 2.0 |
| 5 | Exceeding 27m & upto 39m | 2.0 | 2.0 | 2.5 | 2.5 | 3.0 | 3.0 |
| 7 | Exceeding 39m & upto 45m | 3.0 | 3.0 | 3.60 | 3.60 | 4.50 | 4.50 |
| 8 | More the 45m | 3.60 | 3.60 | 4.00 | 4.00 | 5.00 | 5.00 |
| Sl. | Height of the Building Upto (m) | Exterior open spaces to be left out on allsides in m. | |
| (front setback) | Side and back | ||
| 1 | More than 15 and upto 18 | 6.5 | 4.5 |
| 2 | More than 18 and upto 21 | 7.0 | 4.5 |
| 3 | More than 21 | 7.5 | 4.5 |
| EWS | LIG | ||
| Flooring and Skirting (100mm-ht) | Living Room Dining Room Kitchen Bed RoomVerandah Balcony Passages Lobby | Ceramic Tiles (300mm x 300mm) | Ceramic Tiles (300mm x 300mm) |
| Flooring | Toilet | Anti Skid Ceramic Tiles(300mm x300mm) | Anti Skid Ceramic Tiles (300mm x300mm) |
| Wall Tiles/Dado | Kitchen 600mm height on platform | Ceramic wall tiles (300mm x 200mm) | Ceramic wall tiles (300mm x 200mm) |
| Toilet 2000mm height | Ceramic wall tiles (300mm x 200mm) | Ceramic wall tiles (300mm x 200mm) | |
| Staircase | Floor and skirting(100mm) | Kota/marble/concrete paver/mosaic tiles | Kota/arble/concrete paver/mosaic tiles |
| Parking floor | Paver Tiles | Paver Tiles | |
| Wall work | External (200mm thick) | Red Bricks/Conc. Hollow Blocks/Flyash Bricks | Red Bricks/Conc. Hollow Blocks/Flyash Bricks |
| Internal (150/100mm thick) | Conc. Hollow Blocks | Conc. Hollow Blocks | |
| External Plaster | 20mm thick cement Plaster in 1:4 with properwaterproofing | 20mm thick cement Plaster in 1:4 with properwaterproofing | |
| Internal Plaster | 12/15 mm thick cement Plaster in 1:6 | 12/15 mm thick cement Plaster in 1:6 | |
| Kitchen Platform | Width approx 525mm | Kota Stone with Stainless Steel sink | Polished Granite Stone with Stainless Steel sink |
| Windows | 2 track Aluminium Anodised with 4mm thick glass | 3 track Aluminium Anodised with 2 track -4mmthick glass and and I track stainless steel mosquito mesh) | |
| Doors | External-30mm thick Internal-25mm thick | Wooden Commercial Flush Doors | Wooden Commercial Flush Doors |
| Sanitary ware | White Vitrified/porcelain | White Vitrified/porcelain | |
| CP Fittings | As per ISI Mark | As per ISI Mark | |
| Plumbing | PVC/uPVC/cPVC Pipes | PVC/uPVC/cPVC Pipes | |
| External Paint | Cement Based Paint | Cement Based Paint | |
| Internal Paint | Oil bound distemper over a coat of Plaster ofParis | Oil bound distemper over a coat of Plaster ofParis | |
| Electrical | Electrical work with copper wires in concealedPVC conduits, Provision shall be made for sufficient lighting andpower points. Required switches and sockets, telephone and TVpoints. Each bedroom shall have min 3 Nos-5 Amp points and 1No-15 Amp point, MCB as required | Electrical work with copper wires in concealedPVC conduits, Provision shall be made for sufficient lighting andpower points. Required switches and sockets, telephone and TVpoints. Each bedroom shall have min 3 Nos-5 Amp points and 1 No-15 Amp point, MCB as required | |
| Hardware Fittings | Aluminium fittings including Aldrop, tower bolt,handles as per ISI fittings | Aluminium fittings including Aldrop, tower bolt,handles as per ISI fittings | |
| Water Supply | Deep Bore wells/Shallow wells/Municipal supplylines through Overhead tanks | Deep Bore wells/Shallow wells/Municipal supplylines through Over head tanks |
| Sl No. | Component of Building | Requirements | |
| 3.1 | Habimhle Room(i) In case of oneroomed house including space for cooking(ii) Two roomed house(iii) Height in case of sloping roofs | AreaWidthHeightAreaWidthHeightAvg. heightMtn. height at eaves) | 2.5 sq.mt2.4 mt.2.6 mt.6.5 sq.mt2.1 tnt.2..6 mt.2.6 mt2.0 nu. |
| 3.2 | Kitchen(i) Cook mg alcovesewing as cooking space(ii) Two room-d house | AreaWidthHeightAreaWidthHeight | 2.4 sq.mt1.2 mt.2.4 mt.3.3 sq.mt1.5 mt.2.4 mt. |
| 3.3 | Bathroom | AreaWidthHeight | 1.2 sq.mt1.0 mt.11 mt. |
| 3.4 | W.O. | AreaWidthHeight | 0.9 sq.mt0.9 mt.2.2 mt. |
| 3.5 | Combined bath and W.O | AreaWidthHeight | 1.2 sq_mt1.0 mt.2.2 mt. |
| 3.6 | Balcony | Min. width | 0.9 m |
| 3.7 | Staircase(1) 2 storeyed -Straight Flight Winding(ii) 3 storeyed or more Strait Flight Winding | WidthWidthMin. treadMax riserWidthWidthMin. TreadMax riser | 0.60 mt. (min)0.75 mt. (min)22.5 cm.20.0 cm.0.75 mt.. (min)0.90 int_ (min)25.0 cm.20 0 cm. |
| Notes :-i) die minimum clear head room:bail be 2.1 rat. | |||
| 3.8 | Plinth | Min. height 30 cm from the surrounding groundlevel | |
| 3.9 | Lighting and Ventilation | (a) one - tenth ofthe room floor area for dry hot climate(b) one sixth of the room floor area for wet-hotclimate |
84. Repeal and Savings.
- 84.1 The Jharkhand Planning Standards and Building Bye Laws 2002 with all its amendments, any other building byelaws framed under Mineral Area Development Authority Act Industrial Area Development Authority Act and associated executive orders are hereby repealed.85. Interim Development Plan.
- 85.1 The Authority may prepare Interim Development Plans (IDP) for newly included development areas including rayati land within a reasonable time frame so that development may not be held up in the name of pendency of Interim Development Plan. Where such IDP has not been prepared, the general provisions of these bye laws shall apply without any zonal restrictions.86. Applicability of National Building Code.
- 86.1 Where no express provision has been made in respect of any matter connected with planning and building standards by the Act, the Rules, the Development Plan, the Town Planning Schemes, or these Bye laws or by any resolution of the Authority, the provisions of the National Building Code of India shall be mutatis mutandis.87. Prior Commitments.
- If any Department of Government/Statutory Authority has given any commitment for a project under PPP with the prior approval of Government, but the building plan of such project has not yet been approved by the Authority as on date of enforcement of these Bye laws, such commitment shall be treated to be made under these Bye laws.88. Decision of the Government to be final.
- In case of any dispute in interpretation of these bye laws, the decision of the State Government shall be final.89. Relaxation and modification by the Government.
- The Authority may recommend to the Government for relaxation/modification of any of the clauses of these Bye laws in the general interest of the public pertaining to projects/schemes developed by the Government agencies and the decision of the Government in this regard shall be final.A Building Bye Laws Review Committee shall be constituted by the Urban Development and Housing Department for periodic review and reconsideration and necessary modification of these Bye Laws.Annexure-IQulification, Experience & Competence of Technical Person and Builder1.
) Architect. - A) Qualification & Experience:-The minimum qualification for an Architect shall be bachelor Degree in Architecture or equivalent, and registered with the Council of Architecture and not in arrears of subscription.B) Competence:- The Architect shall be competent to carry out the work related to the building permit as given below and shall be entitled to submit:i) All plans and information connected with the building permit subject to section-16.3.1ii) Certificate of supervision and completion of all buildings,iii) Preparation of sub-division/layout plans and related information connected with development permit of area upto 4 hectare.iv) Certificate of supervision for development of land area up to 4 hectare.C) Duties & Responsibilities:- i) He/She shall be responsible for making adequate arrangements to ensure not only that the work is executed as per the approval plans but also in conformity with the stipulations of the National Code, 2005 and the BIS standards for safe and sound construction non-hazardous, functioning of the services incorporated in the building and for making adequate provision for services and equipment for protection from the fire hazards as per the stipulations of the National Building Code, 2005 in the buildings.D) Registration Fee:- Architects registered under the Council of Architecture Act 1972 shall be entitled for a registration as a licensed technical personnel of Authority without paying any licensing annual fees for the same. This shall not be binding on registration of an Architect engaged for any specific purpose. However if they desire to be enrolled as lifetime licensee of the Authority , a lump sum payment of Rs. 1000/-(One Thousand) shall have to be made to the Authority as a fee for such enrollment, so that Authority may be able to intimate them by post from time to time about the provisions of planning standards and building byelaws and other relevant information with amendments (if any ) in rules and byelaws of the Authority. But In case an architect enrolled as Authority licensee, violates any of the rules, regulations, byelaws and/or planning standards of Authority, for the time being in force , his enrolment in authority shall be cancelled and the enrollment fee of Rs. 1000/- charged initially from him shall be forfeited2.
) Engineer. - (A) Qualification and Experience:-The minimum qualification for an Engineer shall be Degree in Civil Engineering or equivalent. The qualification for licensing of Engineer will be corporate membership (Civil) of the Institution of Engineers or such Degree or Diploma in Civil or Municipal or Structural Engineering which make him eligible for such membership. of which is recognized by Union Public Service Commission for the post of an assistant Engineer.3.
) Structural Engineer. - A) Qualification & Experience:-The minimum qualifications for a structural engineer shall be degree in Civil Engineering/fellow of the Intuition of Engineers (India) or equivalent degree in Civil Engineer from recognized foreign institution, with 5 year experience in structural engineering practice.Note - 5 years experience shall be relaxed to 2 year in the case of Post Graduate degree in Structural Engineering/higher qualification.B) Competence:- The licensed structural Engineers shall be competent to prepare the structural details and calculations for all buildings and undertake supervision. In case of buildings having special structural features, as decided by the Authority, which are within the horizontal areas and vertical limits specified in Annex A of Part-11, A-2.2.1(b) and A-2.4.1(a) of NBC 2005 they shall be designed only by structural engineers.C) Duties and Responsibilities:- i) To prepare a report of the structural design.ii) To prepare detailed structural design, drawings and specifications and to prescribe the method and technique of its execution strictly on the basis of the National Building Code or relevant BIS specifications.iii) To supply copies of structural drawings to the site supervisor.iv) To inspect the works at all important stages and certify that the work being executed is up to the satisfaction of the Architect.v) To certify the structural safety and overall structural soundness of the building to the Architect.vi) To advise the Owner/Architect/Engineer for arranging for tests and their reports for soil, building material etc. for his evaluation and design consideration.vii) To prepare the revised calculations & drawings in case of any revision with reference to the earlier submission of drawing and design in a particular case.viii) To submit the certificate of structural safety and over all structural soundness of building to Authority.xi) In case of multistoried buildings and buildings of a special nature as identified by the Authority from time to time, the structural Calculations/Drawings shall be got vetted by Indian Institute of Technology/National Institute of Technology or any organization empanelled by the State Disaster Management Authority or the Building Construction Department.D) Registration Fee :- The fees for this purpose shall be Rs. 5000/- for one calendar year and it may be renewed in next calendar years by paying Rs. 1000/- to the Authority. But In case an structural engineers enrolled as Authority licensee, violates any of the rules, regulations, byelaws and/or planning standards of Authority, for the time being in force, his enrolment in authority shall be cancelled and the enrollment fee of Rs. 1000/- charged initially from him shall be forfeited.4.
) Town Planner. - Qualification & Experience:-The minimum qualification for a town planner shall be recognized Post Graduate Degree/Diploma in Town Planning and registered membership of ITPI and not be in arrears of subscription.B) Competence:- The licensed town planner shall be entitled to submit:i) All plans and related information connected with development of land of all areas including integrated township.ii) Certificate of supervision for development of land of all areas.C) Duties and Responsibilities:- He/she shall be responsible for making adequate arrangements to ensure not only that the work is executed as per the approved plans but also is conformity with the stipulations of the National Building Code, 2005 and the BIS standards for safe and sound construction non-hazardous, functioning of the services incorporated in the building and for making adequate provisions for services and equipment for protection from the fire hazards as per the stipulations of the National Building Code of India 2005.D) Registration Fee :- The fees for this purpose shall be Rs. 5000/- for one calendar year and it may be renewed in next calendar years by paying Rs. 1000/- to the Authority. But In case an Town Planner enrolled as Authority licensee, violates any of the rules, regulations. byelaws and/or planning standards of Authority, for the time being in force, his enrolment in authority shall be cancelled and the enrollment fee of Rs. 1000/- charged initially from him shall be forfeited.5.
) Supervisor/draftsman. - A) Qualification and Experience:-The minimum qualifications for a supervisor shall be recognized Diploma in Civil or Architecture, or Draftsmanship in Civil or Architectural Assistant ship plus 2 years experience in building design, construction and supervision.B) Competence:- The licensed supervisor/Draftsman shall be entitled to submit:i) All plans and related information connected with building permit for residential buildings on plot up to 100 sq. m. and up to two storeys,ii) Certificate of supervision for buildings as per (i).C) Duties and Responsibilities of Supervisor:- i) To adhere strictly to the architectural and structural drawings/specifications and written instructions of the structural Engineer and Architect/Engineer.ii) To follow the provisions of NBC, 2005 or BIS specifications as regards materials, components, quality control and the process of construction.iii) To bring to the notice of the structural Engineer and Architect/Engineer/any situation or circumstances which in his opinion are liable to endanger the safety of structure.iv) He shall be in charge of site and responsible for supervision of the work.v) He shall ensure that all the works under his charge are carried out in conformity with the approved drawings and as per the details and specifications supplied by the Architect/Engineer.vi) He shall take adequate measures to ensure that no damage is caused to the work under construction and the adjoining properties.vii) He shall also ensure that no undue inconvenience is caused in the course of his work in the people in neighborhood.D) Registration Fee - The fees for this purpose shall be Rs. 2000/- for one calendar year and it may be renewed in next calendar years by paying Rs. 500/- to the Authority. But In case an Supervisor/Draftsman enrolled as Authority licensee, violates any of the rules, regulations, byelaws and/or planning standards of Authority, for the time being in force, his enrolment in authority shall be cancelled and the enrollment fee of Rs. 1000/- charged initially from him shall be forfeited.6.
) Group Agency - i) When any Group or Agency comprising of qualified Architect/Engineer/Town Planner is practicing, then the qualifications and experience, competence, duties and responsibilities and registration will be the combination of individual qualification and experience, competence, duties & responsibilities and registration as provided in Schedule lto5.ii) The Authority may also empanel public undertaking/agencies engaged in development work for quick execution of Government/Private projects within its jurisdiction.Registration Fee. - The fees for this purpose shall be Rs. 10000/- for one calendar year and it may be renewed in next calendar years by paying Rs. 2000/- to the Authority. But In case an Group Agency enrolled as Authority licensee, violates any of the rules, regulations, byelaws and/or planning standards of Authority, for the time being in force, his enrolment in authority shall be cancelled and the enrollment fee of Rs. 1000/- charged initially from him shall be forfeited.7.
) Builder. - A) Qualification:-i) A person/firm engaged in construction activities/building activities in an urban area.ii) A person or group of persons having qualification of Civil Engineering, Architecture and Town Planning.iii) The Authority may classify the builders into different categories considering their experience, expertise and annual turnover.B) Registration/Renewal:- i) Registration of builders shall be done by the Authority. The registration shall be done in the prescribed form. The registration shall be valid for one calendar year and shall be renewable annually. The fee for initial registration of a builder shall be Rs. 75000/- and the renewal fee shall be Rs. 15000/- An application form for the registration of builders will be as follows:-Form of Application For Registration of Builder| Paste passportsizecolour photoof applicant |
| 1 | Name of the applicant (Builder/Firm/Developer) | :- | |
| 2 | Address of Applicant, issued by the officer, not below therank of Civil SDO/SDM | :- | |
| (a) Local Address | :- | ||
| (b) Permanent Address | :- | ||
| 3 | Academic/Technical Qualifications | :- | |
| (a) Builder/Developer | :- | ||
| (b) Name, Address and Technical Qualification of EngineerAssociated with the builder/developer(Engineer should haverecognized Degree/Diploma and 3 years minimum experience in civilbuilding construction work). | :- | ||
| (c) Name, Address of Architect and Technical qualification(Architect associated with builder/developer should have Degreefrom recognized institution with 3 years minimum experience incivil building Planning work) | :- | ||
| 4 | Service Tax Registration Number and Latest return of serviceTax In case of new builder/developer, Service Tax registrationmust be submitted by him within 3 months from the date of makinginvestment in construction of Building/Apartment etc. | :- | |
| 5 | Current year Income tax return (Certified copy to be attached) | :- | |
| 6 | Affidavit to be submitted at the time of registration by theBuilder/Developer that he would submit Labour License either inhis own name or in the name of Labour Supplier employed by theBuilder for construction of that specific project within 3 monthsfrom the date of start of construction of the project | :- | |
| 7 | Work Experience in Civil Construction work (if any) | :- | |
| 8 | (a) If Building Construction has been done by the applicant,mention the B.C. No. and Passing Authority with details. | :- | |
| (b) Year of Building Construction | :- | ||
| (c) Name of Land Owner/Building Owner if the Land/Builder isnot belonging to Builder/Developer by self and certified copy ofMutual contract/agreement to be attached for construction of theBuilding/Apartment over that land | :- | ||
| 9 | Character Certificate issued by the DeputyCommissioner/District Magistrate of period not earlier than 6months | :- | |
| 10 | Is any unauthorized construction case pending after theconstruction of the sanctioned building plan (If yes, mention itsfull details, Name of the Authority/Court, case no. and presentstatus of case) Information to be submitted by affidavit. | :- | |
| 11 | Annual Turn Over of not below 50 lacs rupees duly Audited byChartered Accountant for the last three years. (Certified copy tobe attached) | :- | |
| 12 | Details of the Movable and Immovable Property to be supportedby affidavit containing that the concerned Developer/Builder ishaving property of value not below than 50 lacs rupees. | :- | |
| 13 | Is applicant registered for work in any department? (If yes,mention full details with Registration No.) | :- | |
| 14 | Details of Registration fee by way of DD payable in favour theAuthority. For Rs. 50,000/-in case of new registrationRs. 10,000/- in case of renewal. | :- | |
| Cost of Application Form 1250.00 Only (Non-Refundable) | Full signature of applicant with Date |
8.
) Contractor. - A) Qualification:-i) A person/firm engaged in construction activities/building activities in the State of Jharkhand/India.ii) Availability ()f-a) Ownership/proof of hire/lease.b) Equipment/key technical personnelc) Credit facility/liquid assets.d) Bidding capacity of project.ii) Any other relevant criteria required as per Standard Bidding Document (SBD) of the project.iii) Registration with the BCD of Government of Jharkhand or C.P.W.D. or public sector undertakings.Annexure-IIGuidelines for installation of solar water heating system - 1. Installation of Solar Assisted Water Heating System in Buildings: to ensure the implementation of the guidelines issued by ministry of non-conventional energy sources on accelerated development and deployment of solar water heating systems in domestic, industrial and commercial sectors. No new building in the following categories in which there is a system of installation for supplying hot water shall be built unless the system of the installation is also having an auxiliary solar assisted water heating system:-i) Hospitals and Nursing Homeii) Hotels, Lodges, and Guest Houses, Group Housing with the plot area of 4000 sq m.iii) Hostels of Schools, Colleges and Training Centres with more than 100 Students.iv) Barracks of armed forces, paramilitary forces and policev) Individual residential buildings having more than 150 sq m. plinth areavi) Functional Buildings of Railway Stations and Air Ports like waiting rooms, retiring rooms, rest rooms, inspection bungalows and catering unitsvii) Community Centres, Banquet Halls, Barat Ghars, Kalayana Mandaps and buildings for similar use.A. Definitions| (i) | "Solar Assisted Water Heating System | A device to heat water using solar energy asheat source. |
| (ii) | "Auxiliary back up" | Electricity operated or fuel fired boilers/systems to heat water coming out 'from solar water heating systemto meet continuous requirement of hot water. |
| (iii) | "New Building" | Such buildings of above said categories forwhich construction plans have been submitted to the Authority forclearance. |
| (iv) | "Existing building" | Such buildings, which are licensed to performtheir respective business. |
2. A separate guide lines shall be issued for installation of solar plant. solar power backup and metering system by the Urban Development and Housing Department.
Annexure-IIIMaximum Permissible FAR for Different ULBs| Sl. | Name of ULB | Maximum Permissible FAR | |
| Residential | Commercial | ||
| 1 | Ranchi Municipal Corporation | As per Master Plan | |
| 2 | Dhanbad Municipal Corporation & MADA Area | 2.5 | 2.5 |
| 3 | Chirkunda Nagar Panchayat | 2.0 | 2.0 |
| 4 | Giridih Nagar Parishad | 2.5 | 2.5 |
| 5 | Hazaribagh Nagar Parishad | 2.5 | 2.5 |
| 6 | Jhumritilya Nagar Parishad | 2.0 | 2.0 |
| 7 | Koderma Nagar Panchayat | 2.0 | 2.0 |
| 8 | Chas Municipal Corporation | 2.5 | 2.5 |
| 9 | Phusaro Nagar Parishad | 2.0 | 2.0 |
| 10 | Chatra Nagar Parishad | 2.0 | 2.0 |
| 11 | Bundu Nagar Panchayat | 2.0 | 2.0 |
| 12 | Gumla Nahgar Panchayat | 2.0 | 2.0 |
| 13 | Lohardaga Nagar Parishad | 2.0 | 2.0 |
| 14 | Simdega Nagar Parishad | 2.0 | 2.0 |
| 15 | Khunti Nagar Panchayat | 2.0 | 2.0 |
| 16 | Ramgarh Nagar Parishad | 2.0 | . 2.5 |
| 17 | Dumka Nagar Parishad | 2.5 | 2.5 |
| 18 | Basukinath Nagar Panchayat | 2.0 | 2.0 |
| 19 | Deoghar Municipal Corporation | 2.5 | 2.5 |
| 20 | Madhupur Nagar Parishad | 2.0 | 2.0 |
| 21 | Godda Nagar Panchayat | 2.0 | 2.0 |
| 22 | Pakur Nagar Panchayat | 2.0 | 2.0 |
| 23 | Sahebganj Nagar Parishad | 2.0 | 2.0 |
| 24 | Rajmahal Nagar Panchayat | 2.0 | 2.0 |
| 25 | Mihijham Nagar Parishad | 2.0 | 2.0 |
| 26 | Jamtara Nagar Panchayat | 2.0 | 2.0 |
| 27 | Chaibasa Nagar Parishad | 2.0 | 2.0 |
| 28 | Chakaradharpur Nagar Parishad | 2.0 | 2.0 |
| 29 | Jamshedpur NAC | 2.5 | 3.0 |
| 30 | Mango NAC | 2.5 | 3.0 |
| 31 | Jugsalai Municipality | 2.5 | 3.0 |
| 32 | Chakuliya Nagar Panchayat | 2.0 | 2.0 |
| 33 | Saraikela Nagar Panchayat | 2.0 | 2.0 |
| 34 | Adityapur Nagar Parishad | 2.5 | 3.0 |
| 35 | Medininagar Nagar Parishad | 2.5 | 2.5 |
| 36 | Hussianabad Nagar Panchayat | 2.0 | 2.0 |
| 37 | Vishrampur Nagar Panchayat | 2.0 | 2.0 |
| 38 | Garhwa Nagar Panchayat | 2.0 | 2.0 |
| 39 | Nagar Untari Nagar Panchayat | 1.5 | 1.5 |
| 40 | Manjhiaon Nagar Panchayat | 1.5 | 1.5 |
| 41 | Latehar Nagar Panchayat | 1.5 | 2.0 |
| 42 | Ranchi Regional Development Authority. Ranchi | As per Master Plan |
| 1 | Name of the Firm | - | Photo | |
| 2 | Registration of the Firm | - | ||
| 3 | Details of land onwhich tower is to be installed (land related paper):(a) Photocopy of saledeed/lease(b) Photocopy ofKhatiyan(c) Photocopy ofMutation(d) Photocopy of Rent receipt | - | ||
| 4 | Land/Building Owner of Consent Paper/Agreement | - | ||||
| 5 | Certificate satisfy that proposed tower shallbe able to carry wind pressure. | - | {| | |||
| 10 | (a) If height is less than 40m. and outside 7km.than whether online application has been made or not. A oath withdetailing out that in case of any objection/rejection correctionmeasures shall be taken out by TSPs/IPs. OR | - | {| | |
| 11 | Acknowledgement receipt has been enclosed ornot by TSPs/lPs in context of self certificate produced beforeTERM CELL of DOT with regard to EMR. OR | - | {| | |
| 12 | Fee as per Jharkhand Communication Tower andRelated Structures Policy, 2015 for 8m. height/more than 8m.height (Non refundable). | - | Bank Draft No................................................... Name ofBank .................................................... Date...................................................... |
| Construction Stage | Element | As Per Building Plan | Remark | |
| Yes | No | |||
| Plan check | All, specially structural calculation, firesafety, area of glazing | |||
| Commencement | Assessment of existing lintels, foundations,beams | |||
| Trial Hole | ||||
| Check for encroaching trees, made up of ground,etc | ||||
| Access for tire service | ||||
| Foundation & Excavations | Excavations (Depth/width, distance to tree &drain) | |||
| Movement of Joints, anti-heave protection,clearance to drain | ||||
| Piling | ||||
| Steel Enforcement | ||||
| Ground Preparation for raft | ||||
| Basement/tanking | Tanking for below ground walls & floor | |||
| Retaining wall | ||||
| Over site | Ground Floor preparation (hardcore etc.) | |||
| Suspended timber ground floor preparation | ||||
| Pre cast concrete beams/floor (ventilation &DPC ) | ||||
| DPC | ||||
| DBM | ||||
| Gas Protection - landfill, radon etc | ||||
| Floor insulation | ||||
| Site level for disabled access | ||||
| Drainage (before back fill) | Sewer branches to the site | |||
| Drainage laid prior to coverage | ||||
| Ground percolation's tests ( septic tanks and/orsoak-aways ) | ||||
| Excavated Soak-away pits | ||||
| Exposure of main sewer | ||||
| Rerouting of main sewer/relocation of mainsewer | ||||
| Super Structure | Frame-concrete reinforcement or steel or timber | |||
| Floor joists and beams and connections | ||||
| Construction at first floor level. cg block workand wall ties | ||||
| Construction at 2"d and subsequent floorlevels | ||||
| Dormer framework prior to boarding over | ||||
| Roof timbers, restrains straps, bracing | ||||
| Roof breather membrane | ||||
| Staircase installed | ||||
| Vehicle Barriers/bay | ||||
| Super Structure | Fire protection applied to structural members | |||
| Cavity barriers/fire stopping | ||||
| Fire dampers and fire collars | ||||
| Means of escape | ||||
| Space separation & compartmentation | ||||
| Glazing | ||||
| Opening to conservatories etc | ||||
| Area of Glazing | ||||
| Thermal elements (cavity walls etc) | ||||
| Access | ||||
| Pre Plaster | Sound insulation in walls, floors and stairs | |||
| Insulation in walls and roof | ||||
| Bare walls, beams. lintels | ||||
| Fire door | ||||
| First fix electrical (dwellings only) | ||||
| Ventilation system | ||||
| Hygiene (sanitary convenience & washingfacilities - pipes etc ) | ||||
| Completion | Drainage water tightness test | |||
| Internal lighting, appliance (CO2 emission rate(DER/BER) | ||||
| Heating system, incl thermostatic control | ||||
| Sound insulation test | ||||
| Gas tightness test to flues | ||||
| Electrical installations (dwellings only) | ||||
| Combustion appliance & fuel system storage | ||||
| Air leakage test | ||||
| Hygiene (sanitary conveniences & washingfacilities) | ||||
| Test of emergency lighting and fire alarms |
1. Signature of Licensed ..............................................................................................
Architect/Engineer/TownPlanner/Draftsman/Group ..............................................................................................Name of Licensed Architect/Licensed Town/Planner/Draftsman/Group ............................................................................................................................................................................................ (in block letters)Address of licensed Architect/Engineer/TownPlanner/Draftsman/Group ................................................................................................................................................ Dated .............................................................................2. Signature of the Builder/Owner/Applicant:
Name:Address:Date:Registration no.Note - In case the building has been constructed with deviation a statement of such deviation together with line drawings indicating the extent of deviation shall be submitted along with the completion certificate, duly signed by the technical personnel and the builder/owner/applicant.Annexure VIIForm For Occupancy CertificateI hereby certify that the erection, re-erection or alteration of building on ........................................................................................................................................................ or the ...................................................................................................................................... on in Plot on ................................................................................................................ in and sanctioned vide Plan case No. ............................................................................................................. Dated ............................................................................................... Colony .......................................................................................... Street ..............................................................................................................Mohalla/Bazar/Road ................................................................................................. City ........................................................... completed under the supervision of ......................................................................................................... Licensed Architect/Engineer/Draftsman/Group. License No. .................................................................................................................. has been inspected by me and I declare that building conforms in all respect to the requirements of the Bye-laws. It is certified that the building is fit for occupation.Signature of Authority ...............................................................................................................Office Stamp .................................................................................................................Office (Communication) No ........................................................................................................................... Name, Designation and address of Authority ........................................................................................ Date .........................................................................Annexure-VIIIInformation for Intimation of Completion of Work up to Plinth LevelTo,The .................................................................................................................................................................... Authority,Sir,The construction up to plinth/column up to plinth level has been completed in Building .................................................................................................... on/in Plot No .............................................................................................. Road/Street ........................................................................................................ Ward ............................................................................................ in accordance with your permission No. ........................................................................dated ................................................................................ and is in accordance with the sanctioned plan.Yours faithfully,Signature of Licensed Architect/Engineer/SupervisorName .............................................................(in Block letters)Address .................................................................................................................................................Registration No .....................................................Date .............................................................Signature of Builder/Owner/ApplicantName .............................................................(In Block letters)Address .............................................................Registration No .....................................................Date .............................................................Annexure-IXChecklist for Structural Safety| Item | As Per Buildin Plan | Remark by authorized representative | |||
| Yes | No | Non applicable | Applicable | ||
| 1) Structural Safety | |||||
| 1. Provide Design Basis Report as per thedocument | |||||
| 2. Provide description of Sub-structure andSuper structure as per the format given in the Ref(5&6)enclosed. | |||||
| 3. Provide brief Description of StructuralSystem with sketches, images of drawing. etc. with specific focuson Lateral load resisting system'. | |||||
| 4. Provide brief note on modeling, software usedetc. Clear mention whether infill/partition wall is idealizedas part of lateral load system? | |||||
| 5. Provide the height of building in meters. | |||||
| 6. Provide plan dimensions of the building (mt xmt) | |||||
| EQ Loading Details | |||||
| 7. Provide following EQ loading details. | |||||
| a) Zone Factor | |||||
| b) Importance factor | |||||
| c) Response Reduction factor | |||||
| d) Soil Type | |||||
| e) % LL considered in seismic | |||||
| f) Time Period in the horizontal X- direction(sec) | |||||
| g) Time Period in the horizontal Z-direction(sec) | |||||
| h) Total Seismic weight (Sw) of building (kN) | |||||
| i) Static Base-shear in X-direction (as % of Sw) | |||||
| j) Static Base-shear in Z-direction (as % of Sw) | |||||
| k) Table of distribution for static base shear | |||||
| l) Max. deflection at roof level. (mm) | |||||
| m) Max. inter storey drift./Height | |||||
| Vertical Elements Details | |||||
| 8. Provide following data regarding VerticalElements. | |||||
| a) Size of maximum loaded column | |||||
| b) Gravity load on max. loaded column | |||||
| c) Axial stress in max. loaded column (Gravityloads) | |||||
| d) Grade of max. loaded column | |||||
| e) Axial settlement in max. loaded column | |||||
| f) Axial settlement in min. loaded column | |||||
| g) % Base-shear resisted by all columns along X(static) | |||||
| h) % Base-shear resisted by all columns along Z(static) | |||||
| Dynamic Analysis | |||||
| 9. Provide following data from Dynamic Analysis | |||||
| a) Total gravity load on floating column(provide table if there are multiple floating columns) | |||||
| b) Size and span of girders supporting floatingcolumns | |||||
| c) Number of floors supported by floatingcolumns | |||||
| d) Deflection of girder under column (frommodel) | |||||
| e) Deflection of girder under column (from s/saction) | |||||
| f) Specific details about floating columns oncantilevergirders (Refer Table below) | |||||
| 10. Provide, if applicable, following data foreachcantilever. | |||||
| a) Cantilever span | |||||
| b) Structural system | |||||
| c) Nature of usage | |||||
| d) Maximum elastic deflection under gravityloads | |||||
| 11. Provide stability calculations for upliftand overturning(model extract in case of model) | |||||
| 12. Typical design calculations for footings | |||||
| 13. Typical design calculations for RCC columnsComposite Columns | |||||
| 14. Typical design calculations for RCC walls | |||||
| 15. Typical design calculations for RC beams (OrSteel Beams) | |||||
| 16. Typical design calculations for RCC Girders(Or Steel Girders/Truss) | |||||
| 17. Typical design calculations for SteelBracings | |||||
| 18. Provide a note on special provisionssuggested for the building (like dampers etc.) | |||||
| 19. Soft copy of model including input andoutput. |
| Provide following data from Dynamic Analysis | ||||
| Modes | Frequency | Time Period in Sec | X-Participation | Z-Participation |
| Mode 1 | ||||
| Mode 2 | ||||
| Mode 3 | ||||
| Mode 4 | ||||
| Mode 5 | ||||
| Mode 6 | ||||
| Mode 7 | ||||
| Mode 8 | ||||
| Mode 9 | ||||
| Mode 10 | ||||
| Mode 11 | ||||
| Mode 12 | ||||
| Mode 13 | ||||
| Mode 14 | ||||
| Mode 15 | ||||
| Summation |
| Provide Table for lateral deflections (mm) atTerrace Level in the following format. | ||||||
| Load Case | Dxmax | H/Dx | Drift-x | Dzmax | H/Dz | Drift-z |
| Provide Corner displacements (mm) forTorsional Irregularity(along x-direction) in the followingformat. | ||||||
| Load Case | Corner- I | Corner- 2 | Corner-2 | Corner-4 | Avg - x | %Max./Avg, |
| Eq-x | ||||||
| WI-x | ||||||
| Provide Corner displacements (mm) forTorsional Irregularity(along z-direction) in the followingformat. | ||||||
| Load Case | Corner- 1 | Corner-2 | Corner- 2 | Corner- 4 | Avg - x | %Max./Avg. |
| Eq-z | ||||||
| WI-z |
| Provide acceleration (mg) values in thefollowing format. | |||
| Eq-x | Eq-z | WL-x | WL-z |
| Ref 5 | |
| Description of Sub-Structure | |
| No. of basement | |
| Minimum clearance between outermost basementretaining wall and compound wall | |
| Has a Shoring system been installed ? Submitsectional detail of the shoring system | |
| Give details of methodology used to resistuplift pressure due to ground water for tower portion as well asthe portion outside the tower. | |
| Description of the foundation for the towerblock | |
| Nature of Foundation | |
| SBC assumed T/sq.mt. | |
| Sub-grade Elastic Modulus | |
| Intended Use of basements | |
| If rock anchors are used, arc they grouted afterinstallation and stressing? | |
| Is structural steel used in the construction ofthe sub-structure? | |
| If yes, what are the measures taken for its lireproofing and corrosion resistance? | |
| Whether Expansion/ | |
| Separation joints provided? | |
| Whether expansion joint/separation jointcontinues through basement? | |
| If yes, detail at Basement level & retainingwall junction | |
| Ref 6 | |
| Description of Super Structure | |
| No. of Floors & height of building in m | |
| Shape of Building, Plan, Elevation, WhetherSymmetric in Elevation | |
| Maximum plan dimension in either direction.in m. | |
| Ratio of plan dimension | |
| Typical Floor to floor height in in Maximumfloor to floor height in entire height of building in m. | |
| Aspect ratio ( Height of Building till Terrace/Minimum Dimension of Building) | |
| Type of floor slab | |
| Average thickness of floor slab in mm | |
| Whether column are RCC, Composite or Instructural steel |
| The materials to be tested on site includecement, water, aggregates for concrete, bricks and stones, soilfor embankments, and aggregates for construction works. The listof materials to be tested on site is given in the Table 1 below. | |
| Table 1 List of Materials Tested on Site | |
| Material | |
| Sl.No. | |
| 1 | Cement |
| 2 | Sand/Fine Aggregates. |
| 3 | Water for Construction Works (can be tested inapproved lab) |
| 4 | Bricks |
| 5 | Size Stone |
| 6 | Coarse Aggregate for Concrete Work |
| 7 | Soil/Earth/Sub-grade Material |
| 8 | Granular Sub-base (GSB) Material |
| 9 | Material for WBM/WMM |
| 10 | Metal for BM/DBM/BC/Surface Dressing/MSS/PremixCarpet |
| 11 | Binder for WBM |
| 12 | Fine Aggregate for DBM/BC |
| 13 | Lime |
| 14 | Borrow Material |
| 15 | Steel (to be procured directly form manufacturealong with test certificate |
| Item | As Per Building Plan | Remark by authorized representative | |||
| Yes | No | Non applicable | Applicable | ||
| 1. Number of floors | |||||
| Building height | |||||
| 2.External Setbacks | |||||
| 3. Building Line, if any | |||||
| 4.Parking space provision | |||||
| 5. Abutting road width | |||||
| 6. FAR | |||||
| 7. Coverage percentage | |||||
| 8. Tree Cover | |||||
| 9. Water harvesting structures | |||||
| 10. Land if required to be surrendered | |||||
| 11. Lift/s, water pumps and storage tanks | |||||
| 12. Internal roads/paving | |||||
| 13. Parking areas and external lighting | |||||
| 14. Lightening arrestors | |||||
| 15. Fire Fighting installations | |||||
| 16. Lifts | |||||
| 17. Water pump | |||||
| 18. Drainage and arrangement for waste water andsewage disposal | |||||
| 19. Copy of agreement with the apartment Owners'Association/Society | |||||
| 20. Implementation of Life Safety provisions asmentioned in National Building Code 2005(Group-I Part-W Fire andLife Safety-4) | |||||
| 21.NOC from Fire Service Department | |||||
| Quality Checklists for Building Works | |||||
| Item | As Per Building Plan | Remark by authorized representative | |||
| Yes | No | Non applicable | Applicable | ||
| 1) Excavation & PCC | |||||
| A. Pre Excavation | |||||
| 1. Construction Drawings | |||||
| indicating levels available at Site | |||||
| 2. Proper safety precautions taken | |||||
| for site and public | |||||
| 3. Precautions taken for dewatering | |||||
| and protecting site from flooding | |||||
| 4. Dumping ground established | |||||
| Setting out and levels as per | |||||
| drawings | |||||
| 5. Intermediate levels checked | |||||
| B. Post Excavation | |||||
| 1. Characteristics of excavated strata | |||||
| noted and deviations informed | |||||
| 2. Appropriate shoring and | |||||
| shuttering done | |||||
| 3. Final excavation levels, surface | |||||
| inspected and approved | |||||
| 4. Anti-Termite Treatment has been done postexcavation | |||||
| 2) Plain Cement Concrete Works | |||||
| A . Pre-concreting | |||||
| 1. All levels and dimensions checked forcorrectness | |||||
| 2. Shuttering is as per plan and has no gaps inbetween | |||||
| 3. All materials are of specified brand andgrade | |||||
| B. During Concreting | |||||
| 1. Mixing of concrete has been done as specified | |||||
| 2. Slump and other tests carried out asspecified | |||||
| 3. Slump and other tests carried out asspecified | |||||
| 4. Required number of Samples have been takenfor carrying out slump tests, cube tests etc | |||||
| C. Post Concreting | |||||
| 1 Concreting has been done as per specified lineand level | |||||
| 2 Curing has been done as specified | |||||
| 3 Compaction has been done Properly | |||||
| 4 Remedial measures taken for removal of defects | |||||
| 3) Anti Termite Treatment (ATT) | |||||
| 1 Chemicals for ATT are as per Specifications | |||||
| 2 Chemicals in use are within the expiry date. | |||||
| 3 Sufficient quantities of chemicals areavailable at site for ATT. | |||||
| 4 Safety precautions have been taken forcarrying out ATT and storage of Chemicals | |||||
| 5 Record of consumption maintained at site | |||||
| 4) Backfilling | |||||
| 1. Filling material/earth is as perspecification | |||||
| 2 Anti-termite treatment has been carried nutbefore commencement of back filling | |||||
| 3 Filling has been done in layers of 300 mm.watered and compacted as per specifications | |||||
| 4 Proper compaction method has been adopted | |||||
| 5 Filling has been done to the required levels | |||||
| 5) Reinforced Cement Concrete Works | |||||
| A. Pre-concreting | |||||
| 1. All specified materials available at site | |||||
| 2 Cement is of the required grade and not morethan three months old. | |||||
| 3 Shuttering checked for Staging & Propping.line & level, dimensions cleaning etc and its qualityapproved | |||||
| 4 Application of oil & grease carried out | |||||
| 5 Mixer/Vibrator as specified available at sitewith adequate means to run them during concreting | |||||
| 6 Cut-out & Sleeves/Inserted | |||||
| 7 Surface of reinforcement is clean and freefrom rust | |||||
| 8 Bars have been provided as per structuraldrawings | |||||
| 9 Lap length & dowels provided as per codalprovisions | |||||
| 10 Pin bars & chairs/cover blocks providedas per requirements | |||||
| 11 Tying of bars has been done Correctly | |||||
| 12 Service lines(Electrical. Plumbing, Others)if any. provided before commencement of concrete | |||||
| B. General Arrangement | |||||
| 1. Availability/Arrangement of pumps etc.proper access & walkway checked | |||||
| 2 Adequacy of vibrators/needle including dieselvibrator | |||||
| 3 Slump cone & test cubes made | |||||
| 4 Safety and health measures taken beforecommencement | |||||
| C. During Concreting | |||||
| 1 All necessary precautions taken beforecommencement of concreting | |||||
| 2 Samples of taken for slump, cube tests etc foreach batch | |||||
| 3 Proper Compaction done and checks on Staging &Scaffolding carried out | |||||
| 4 Covering of green concrete carried out | |||||
| 5 Surface finish checked | |||||
| 6 Construction joints provided | |||||
| D. Post Concreting | |||||
| 1 De-shuttering started on Vertical faces/Otherfaces carried out as per codal provisions | |||||
| 2 Proper curing of concrete carried Out | |||||
| 3 Line& Level of surface checked forcorrectness | |||||
| 4 Defects, notified and removed | |||||
| 5 Cube and other test results will be intimatedto the engineer in charge for further action | |||||
| 6) Masonry, Mortar and Plaster | |||||
| A. Pre-Masonry Work | |||||
| 1 Availability of material as per dailyrequirement checked | |||||
| 2 Quality check for bricks/blocks/sand/cementcarried out | |||||
| 3 Provisions kept for electrical and otherservices | |||||
| B. During masonry work | |||||
| 1 Checking for line/level/right angle carriedout | |||||
| 2 Mortar checked for mix proportion | |||||
| 3 Proper raking of joints | |||||
| 4 Seismic bands provided as per zonalrequirements | |||||
| C. Post masonry | |||||
| Check cleaning of dead mortar and broken bricks/blocks etc. | |||||
| 2 Curing carried out as per requirements | |||||
| D. Plastering/Pointing | |||||
| 1 Mortar for plastering as specified for eachside of wall | |||||
| 2 Quality of cement and sand checked | |||||
| 3 Curing work done as per requirement | |||||
| 4 Preparation of surface | |||||
| E. During Plastering | |||||
| 1 Mortar mixing in tray | |||||
| 2 Addition of water proofing compound | |||||
| 3 Proper roughing of first coat | |||||
| 4 Check for collection of mortar Spills | |||||
| 5 Cleaning of dead mortar | |||||
| 6 Check of waviness | |||||
| 7 Check for grooves/drip moulds | |||||
| 8 Application of cement slurry on concretesurface | |||||
| F. After Plastering | |||||
| 1 Curing | |||||
| 2 Check for hollowness | |||||
| 3 Check for cracks | |||||
| 4 Check for diagonal | |||||
| 5 Lime wash aller 3 days (within 5 days in caseof neeru application) | |||||
| 6 Safety and health measures | |||||
| 7) Water Proofing | |||||
| 1 Surface for waterproofing has been preparedand cleaned | |||||
| 2 Safety measures/precautions taken beforecommencement of works | |||||
| 3 Specified type of water proofing Used | |||||
| 4 Specified material used for waterproofing | |||||
| 5 The material used was as per specification | |||||
| 6 Work has been carried out as perspecifications by the department/specialized agency | |||||
| 8) IPS/Till Flooring and Dado | |||||
| 1 Layout of floor checked and proper slopes fordraining water are maintained specially in bath room and toilet. | |||||
| 2 Thickness bases at Gl. checked of differentfloor | |||||
| 3 Check fOr proper back filling under floor done | |||||
| 4 Metal/glass strips laid properly in IPSflooring | |||||
| 5 Curing of IPS Flooring done as perrequirements | |||||
| 6 Dado provided as per required height | |||||
| 7 Cleaning and finishing done | |||||
| 9) Plumbing & Water Supply | |||||
| 1 GI/Cl/HDPE pipes etc. confirms to relevant IScodes | |||||
| 2 Pipes of required diameter and their fittingsused | |||||
| 3 Plumbing and Water Supply work carried outthrough a licensed plumber | |||||
| 4 Works done as per specification | |||||
| 5 Plumbing and Water Supply I works tested oncompletion - | |||||
| 6 Defects rectified | |||||
| 10) InternalElectrical WorksA .General | |||||
| 1 Layout plans: showing the position of L.TPanels/distribution board, lighting fixtures, lightingdistribution, scheme, receptacles, etc available beforecommencement of work | |||||
| 2 All the following items are as perspecification and of approved makes | |||||
| L T Panels/Distribution BoardsLighting FixturesConduits, including accessoriesReceptaclesJunction BoxesCables/WiresAny other item | |||||
| B. Surface Conduit Wiring/Concealed ConduitWiring | |||||
| 1 Conduit and accessories are of specified make,gauge and diameter | |||||
| 2 Proper installation of all conduit wiring andconcealed wiring. | |||||
| C. Check List For Earthing | |||||
| 1 Earth electrode provided as specified. | |||||
| B. Surface Conduit Wiring/concealed ConduitWiring | |||||
| 1 Conduit and accessories are of specified make,gauge and diameter | |||||
| 2 Proper installation of all conduit wiring andconcealed wiring. | |||||
| C. Check List For Earthing | |||||
| 1 Earth electrode provided as specified | |||||
| B. Surface Conduit Wiring/Concealed ConduitWiring | |||||
| 1 Conduit and accessories are of specified make,gauge and diameter | |||||
| 2 Proper installation of all conduit wiring andconcealed wiring. | |||||
| C. Check List For Earthing | |||||
| 1 Earth electrode provided as specified. | |||||
| Check List For External Electrical Works | |||||
| A. Check List For O.H. Lines | |||||
| 1 Poles used arc of approved make as specifiedand conform to relevant BIS codes | |||||
| 2 Test certificate as applicable. | |||||
| 3 Pole embedded below ground level as specified. | |||||
| 4 Metallic poles are adequately earthed withspecified size of earth conductor. | |||||
| 5 Strays struts, insulators, conductors usedconform to relevant BIS Code. | |||||
| 6 Earth wire conductor used as specified | |||||
| 7 Lightning arrestors used as specified | |||||
| B. Cable Laying | |||||
| 1 Trenches of specified dimensions excavated andprepared | |||||
| 2 Required quantity of sand cushioning provided;cable laid; another layer of sand and brick protective coveringprovided. Refilling done earth ramming and dressing done | |||||
| 3 Cables entry point in building or crossingroads path protected by providing Hume pipes or PVC Pipe | |||||
| 4 Cable tested before and after laying andbefore emerging | |||||
| C. Check List For Earthing | |||||
| 1 Earth electrode provided as specified | |||||
| 2 Types and size of main/sub main and circuitearthing conductors provided as specified. | |||||
| 11) Drainage Works | |||||
| 1 Excavation for drains carried out as per theapproved lay-out | |||||
| 2 Bed Concrete laid as per specifications withproper slopes and cuttings | |||||
| 3 All pipes procured and laid as per requirement | |||||
| 4 Jointing of pipesdone as per specifications5 Manholes provided as per design | |||||
| 6 Materials for construction of manhole asspecified | |||||
| 7 End of the pipes plugged | |||||
| 8 Drainage line tested before putting to use | |||||
| 13) Others | |||||
| 1 Whether the provision for adequate ventilationand natural lighting has been made as per National Building code? | |||||
| 2 Whether facility for storage in terms ofAlmirah/Shelves/Lofts/Platform has been made ? | |||||
| 3 Whether Sanitary fittings have been provided? |
| From | for office use only |
| Name and address(in Block letters) | Regd No. .............Date ..................... |
| ............................................... | |
| ............................................... | |
| ............................................... | Signature of Authorised Person |
| ............................................... | |
| Tel No/Mobile No............................................... | |
| Email id............................................... | |
| To | |
| ............................................... | |
| ............................................... | |
| ............................................... |
| 1. Four/Eight sets of the building plan: | Yes/No/Not applicable |
| 2. Ownership document: | Yes/No/Not applicable |
| 3. Supervision Certificate in form-V: | Yes/No/Not applicable |
| 4. Affidavit or peaceful possession of the land: | Yes/No/Not applicable |
| 5 Certificate for Structural stability in form-TV: | Yes/No/Not applicable |
| 6. NOC from lease case of lease hold: | Yes/No/Not applicable |
| 7. NOC from Fire Authority: | Yes/No/Not applicable |
| 8. NOC from Airport Authority: | Yes/No/Not applicable |
| 9. Environmental clearance: | Yes/No/Not applicable |
| 10. Details Fee : | Yes/No/Not applicable |
| 11 . Checklist: | Yes/No/Not applicable |
| 12. Any other certificate/NOC(please specify): | Yes/No/Not applicable |
| From | for office use only |
| Name and address(in Block letters) | Regd No. .............Date ..................... |
| ............................................... | |
| ............................................... | |
| ............................................... | Signature of Authorised Person |
| ............................................... | |
| Tel No/Mobile No............................................... | |
| Email id............................................... | |
| To | |
| ............................................... | |
| ............................................... | |
| ............................................... |
| 1. Four/Eight sets of the building plan: | Yes/No/Not applicable |
| 2. Ownership document: | Yes/No/Not applicable |
| 3. Supervision Certificate in form-V: | Yes/No/Not applicable |
| 4. Affidavit or peaceful possession of the land: | Yes/No/Not applicable |
| 5 Structural stability certificate: | Yes/No/Not applicable |
| 6. NOC from lease case of lease hold: | Yes/No/Not applicable |
| 7. NOC from Fire Authority: | Yes/No/Not applicable |
| 8. NOC from Airport Authority: | Yes/No/Not applicable |
| 9. Environmental clearance: | Yes/No/Not applicable |
| 10. Details Fee : | Yes/No/Not applicable |
| 11 . Checklist of the proposed building: | Yes/No/Not applicable |
| 12. Any other certificate/NOC(please specify): | Yes/No/Not applicable |
1. That the building has been constructed according to the structural design and specification prepared by me, which incorporates the provisions of structural safety norms as specified in part 6 (Structural Design) of the national building code of India, 2005 and other relevant codes and the design complies with the Earthquake safety requirement.
2. That the construction has been done under my supervision and guidance and adheres to the structural drawings and specifications prepared by me and records of supervision have been maintained.
Any subsequent changes or deviation from the structural drawings and specifications shall be the responsibility of the owner/builder.Name and signature of competentTechnical PersonRegistration no.Date:Address:Name and Signature of Owner/Builder/ApplicantRegistration no.Date:Address:Form-IVCertificate For Structural StabilityWith respect to the building work of erection, re-erection or for making alteration with respect of Plot No(CS) ............................................... Plot No.(MSP) ............................................................... khata No Holdings No ................................................................ Village/Mauza Ward No ...................................................... of Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act.I certify that the structural calculations, plans and details including the relevant specifications of the building prepared by me, satisfy the structural safety requirements for all situations including natural disasters like cyclone & earth quake etc: as applicable under the Byelaws and stipulated under Part-6 (Structural Design) of the National Building Code of India, 2005 and other relevant codes; and the information given the in is factually correct to the best of my knowledge.I undertake the responsibility with regard to supervision of the work at each and every stage of construction of the structure, regularly to the effect that the building is being constructed conforming to the structural plan prepared structural calculations, plans and details including the relevant specifications of the building prepared by me.I will be responsible and liable for action by ............................................................................ Authority/Government if the plan/design contain misrepresentation or fraudulent information and the construction is made in deviation from structural calculations, plans and details including the relevant specifications of the building prepared by me or if there is any structural failure due wrong/unsafe structural design/use of low quality material and/or poor workmanship endangering the safety of inmates or public and the the structural stability of the building.Name and signature of competentTechnical PersonRegistration no.Date:Address:Name and Signature of Owner/Builder/ApplicantRegistration no.Date:Address:Form-VForm For SupervisionI hereby certify that development erection/re-erection/demolition material alteration in/of the building in respect of Plot No(CS) ............................................................... Plot No(MSP) ............................................................... khata No ............................................................... Holding No ............................................................... Village/Mauza .............................................................../Ward No ............................................................... of ............................................................... Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act shall be carried out under my supervision and certify that all the materials (type and grade) and the workmanship of the work shall be generally in accordance with the general and detailed specifications submitted along with and that the work shall be carried out according to the sanctioned plans.Signature of Empanelled Technical PersonName of the Technical Person with Registration numberAddress ..............................................................................................................................Date .................................Form VICheck List1. Name of the Applicant:
2. Name of the Owner:
3. Name of the Builder/Developer and Name of the Project:
4. Ownership documents: Established/Non established
5. Land Area
| As per Document | As per Building Plan | As per Possession |
6. Tenancy:-Lease hold/Free hold.
If lease hold:7. Existing off site Physical Infrastructure:
8. Nature of Construction: New Construction/Reconstruction/Addition/Alteration
9. (i) Amount of fee deposited
10.
| Use applied | Prescribed Land use in the development plan(ifany) | Whether permissible/not permissible/specialconsideration |
11. (i) Whether first permission/Revised permission/Revalidation .......................................................
12. Contents of Buildings Plan:
13. Approach road:
| As per site/key plan | Site inspection report |
14. Whether the plot is affected by proposed road/proposed drain/proposed lake/any other public use ...........................................................
15. Whether the plot is within 100meter/100-300 meter of State/A.S.I. protected monuments.... Whether the plot is within 200 meter radius of important buildings (i.e. Governor House, High Court, State Secretariat, Legislative Assembly)
16. Building Parameters:
| Category | Requirement as per norm | Approved building plan | Proposal | Remarks |
| 1 | 2 | 3 | 4 | 5 |
| Basement/stilsqmt | ||||
| 1stfloor sqmt | ||||
| 2ndfloor sqmt | ||||
| 3rdfloor sqmt | ||||
| 4thfloor sqmt | ||||
| Other Floors | ||||
| Society room | ||||
| Front set back | ||||
| Rear set back | ||||
| Left/Right side set back | ||||
| FAR | ||||
| Parking | ||||
| Height | ||||
| No. of dwelling unit | ||||
| Population density | ||||
| No. of staircase | ||||
| No. of lift | ||||
| Recharging pit | ||||
| Fee deposited | ||||
| Any other item | ||||
| Exemptions(i) height(ii) setback(iii) FAR |
17. Whether falls in the Airport funnel zone .......................................
18. Provision of proposed on site physical infrastructure
19. Clearance/Certificate produced
20. Involvement of Technical Person & Builder:
| (i) Architect/Engineer:- | |
| Name:- | |
| CoA registration no.(for Architects) | |
| Empanelment no: | |
| Signature | |
| (ii) Engineer/Structural Engineer:- | |
| Name | |
| Empanelment No: | |
| Signature | |
| (iv) Builder/Owner/Applicant | |
| Name: | |
| Registration no. | |
| Signature |
| Self-Attestedpassport sizephoto of theapplication |
1. Name .....................................................................................
(In block letter)2. Father's/Husband's Name ...................................................................................
3. Date of Birth ..............................................................................
4. Nationality ...............................................................................
5. Educational Qualification .............................................................
6. Professional Experience ...................................................................
7. Registration No. With Council of Architecture, New Delhi ..................................
8. Registration with other relevant Institutions/ULBs .........................................
9. Details of other Academic & Professional Achievements .......................................
10. Details of Certificate relating to qualifications/testimonials, if any as per column 5 & 6 with self attested copies .........................................................
11. Details of Bank Draft/Postal Order (separately for empanelment Rs. 500/ ............................
12. Permanent Address - ..........................................................................
13. Address for Correspondence - ...................................................................
14. Tel. No./Mob. No - ..........................................................................
15. Email id - ..................................................................................
DeclarationI hereby solemnly affirm and declare that the information as furnished above are true and correct to the best of my knowledge and belief. I further undertake that if any information at any stage shall be found to be false, any my empanelment shall be liable to be cancelled without any prior notice in that regard and I shall not claim any compensation etc. for such a default on my part. In case of any discrepancies found later, I shall be liable for punishment under the relevant provision of law as also under Jharkhand Municipal Act-2011, Jharkhand Regional Development Authority Act-2002, Jharkhand Mineral Area Development Authority Act. Jharkhand Industrial Area Development Authority Act.Place ..................................................................Date ...................................................................Name and Signature of the ApplicantNote:- Self Attested copies of supporting documents shall be submitted along with the form.Form-VII (B)For Registration of Builder| To,The Authority…..............................….............................. | Self-Attestedpassport Sizephoto of theapplication |
1. Name of the Firm
2. Type of Firm-(Partnership/Company) (In block letters)
3. Name of Partner/Directors ....................................................
(In block letters)4. Father's/Husband's Name ...............................................................
5. Date of Birth ....................................................
6. Nationality .........................................................................
7. Registration No .............................................................
8. PAN/DIN .......................................................................
9. Sales Tax No ...............................................................
10. VAT No .....................................................................
11. Income Tax Statement of Last Three consecutive Financial Year ..........................................................................
12. Category applied for .......................................................
13. Details of fee ...........................................................
14. Permanent Address ..........................................................
15. Address for Correspondence - ................................................................................
16. Tel. No./Mob. No .............................................................................
17. Email id ................................................................
DeclarationI hereby solemnly affirm and declare that the information as furnished above are true and correct to the best of my knowledge and belief. I/we have not been barred for building construction activities by any competent authority and further undertake that if any information at any stage shall be found to be false, my registration shall be liable to be cancelled without any prior notice in that regard and I shall not claim any compensation etc. for such a default on my part. In case of any discrepancies found later, I shall be liable for punishment under the relevant provision of law as also under Jharkhand Municipal Act-2011, Jharkhand Regional Development Authority Act-2002, Jharkhand Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act.Place ............................................................Date ...............................................................Name and Signature of the ApplicantNote:- Self Attested copies of supporting documents shall be submitted along with the form.Form-VIII (A)For Approval of Building PermitWith respect to your Application No .................................... date .................................... permission is hereby granted in favour of, Smt/Shri .................................... fora) Construction of a .................................... buildingb) Reconstruction of .................................... buildingc) Alteration of .................................... buildingd) Alteration or additions in the existing buildinge) Institution of change of the use of building .................................... (Specify)In respect of Plot No (CS) .......................................... Plot No (MSP) .......................................... Khata No .......................................... Holding No. .......................................... Village/Mauza .......................................... of Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act to the following conditions/restrictions.a) The land/Building shall be used exclusively for .......................................... purpose and the uses shall not be changed to any other use without prior approval of this Authority.b) The development shall be undertaken strictly according to plans enclosed with necessary permission endorsement.c) Parking space measuring .......................................... sq. m. as shown in the approved plan shall be kept open and no part of it will be built upon.d) The land over which construction is proposed is accessible by an approved means of access of .......................................... m. width.e) The land in question must be in lawful ownership and peaceful possession of the applicant.f) The applicant shall free gift .......................................... m. wide strip of land of the road in the name of the authority for the purposes as mentioned in these Byelaws.g) The permission is valid for period of three years with effect from the date of issue.h) Permission accorded under the provision cannot be construed as evidence in respect of right title interest of the plot over which the plan is approved.i) Any dispute arising out of land record or in respect of right/title/interest after this approval the plan shall be treated automatically cancelled during the period of dispute.j) Any other conditions.By OrderAuthorised Officer..........................................Memo No .......................................... , Date ..........................................Copy along with .......................................... copies of the approved plans to Smt./Shri ..........................................Authority Officer/AuthorityMemo No .......................................... Date ..........................................Copy with a copy approved plan forwarded to the ...................................... Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayats for information.Authority Officer/Authority..............................Form-VIII (B)For Approval of Land Development PermitWith respect to your Application No .......................................... date .......................................... permission is hereby granted in favour of, Smt/Shri .......................................... fora) For layout plan of land developmentb) Institution of change of the use of land (Specify)In respect of Plot No (CS) .......................................... Plot No (MSP) Khata No .......................................... Holding No. .......................................... Village/Mauza .......................................... of Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act to the following conditions/restrictions.a) The land shall be used exclusively for .......................................... purpose and the uses shall not be changed to any other use without prior approval of this Authority.b) The development shall be undertaken strictly according to plans enclosed with necessary permission endorsement.c) Parking space measuring .......................................... sq. m. as shown in the approved plan shall be kept open and no part of it will be built upon.d) The land over which construction is proposed is accessible by an approved means of .......................................... access of m. width.e) The land in question must be in lawful ownership and peaceful possession of the applicant.f) The applicant shall free gift .......................................... m. wide ..........................................strip of land in the Municipal Corporations/Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act for the further widening of the road to the standard width.g) The permission is valid for period of three years with effect from the date of issue.h) Permission accorded under the provision cannot be construed as evidence in respect of right title interest of the plot over which the plan is approved.i) Any dispute arising out of land record or in respect of right/title/interest after this approval the plan shall be treated automatically cancelled during the period of dispute.j) Any other conditions.By OrderAuthorised OfficerMemo No .......................................... , Date ..........................................Copy along with .......................................... copies of the approved plans to Smt./Shri ..........................................Authorised Officer/AuthorityMemo No .......................................... , Date ..........................................Copy with a copy approved plan forwarded to the ........................................ Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayats for information.Authorised Officer/AuthorityForm-IXForm of Refusal of Building Permit/Development PermitFrom.............................................................................................................................To,Smt/Sri .........................................................With respect to the Application No .............................................. dated .............................................. , your reply to the objections made by this office vide its letter No .............................................. dated .............................................. has not been found satisfactory.Your application for permission to undertake building/land development on Plot No1. ............................................................................................
2. ............................................................................................
3. ............................................................................................
4. ............................................................................................
Two copies of the plans are retained in this office for record and reference and the rest are returned herewith.Authorised Officer/ Authority..............................................Memo No .............................................. , Date ..............................................Copy forwarded to the ..................................... Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayats for information.Authorised Officer/ Authority..........................Form-XForm of Notice For Commencement of Work(To Be Furnished by the Plot Owner(S) and the Builder/developer)From.........................................................................................................................................................................................................................................................(Name and address of the applicant in block letters)To.........................................................................................................................................................................................................................................................Sir,I/we hereby given of the erection of building in with respect of plot No (CS) ............................................. Plot No (MSP) ............................................. Khata No ............................................. Holding No. ............................................. Village/Mauza ............................................. Mohalla ................................................/Ward No ............................................. of ............................................. Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act within the development plan area of ............................................. to be commenced on ............................................. as per the permission given in your letter no ............................................. dated ............................................. Under the supervision of ............................................. Authority/empanelled Architect/Structural Engineer ............................................. Regd. No ............................................. in accordance with the approval plan.Yours faithfully,Name and Signature of Owner/Builder/Applicant Registration no.Phone/Mobile no.-Date:Address:Form-XIPeriodic Progress Report(To be submitted by the Empanelled Structure/Architect/Engineer)From.........................................................................................................................................................................................................................................................To,........................................................................................................................................................................................................................................................Ref .......................................... Authority approval letter No .......................................... Dated ..........................................Madam/Sir,I/we hereby certify that the construction of the building up to plinth level/ground floor roof slab level/first floor roof slab level/second floor roof slab level .......................................... of the building with respect of plot No (CS) .......................................... Plot No (MSP) .......................................... Khata No .......................................... Holding No .......................................... Village/Mauza ........................................../Ward No .......................................... of .......................................... Municipal Corporation/Municipal Council/Nagar Panchayat/Municipality/Notified Area Committee/Regional Development Authorities/Industrial Area Development Authorities/Mineral Area Development Authority, Gram Panchayat areas covered under Development Plan or Planning Scheme notified under Jharkhand Municipal Act 2011, Jharkhand Regional Development Authority Act 2002, Mineral Area Development Authority Act, Jharkhand Industrial Area Development Authority Act within the development plan area of .......................................... has been supervised by me/us and has been constructed strictly conforming to the sanctioned plan and structural design as per the provision of NBC,2005. The work has been done to my/our best satisfaction. All the materials used in construction of this building are strictly in accordance with BIS specifications and norms conforming to National building Code, 2005 covering all the safety factors including earthquake and cyclone. I/we will be responsible and liable for action by .......................................... Authority/Government if there is any structural failure and fire endangering the inmates and public.| (i) Architect/Engineer:- | |
| Name:- | |
| CoA registration no.(for Architects) | |
| Empanelment no: | |
| Signature | |
| (ii) Engineer/Structural Engineer:- | |
| Name | |
| Empanelment No: | |
| Signature | |
| (iv) Builder/Owner/Applicant | |
| Name: | |
| Registration no. | |
| Signature |
| Sl. | Name and address of the applicant | Date of receipt of application | Date of permission/refusal with letter No. | Date of Submission of commencement | Submission of notice of completion | Date of issue/refusal of occupancy permissionwith letter no. | Remarks | Signature of the Aurthorised Person |
| (i) | (ii) | (iii) | (iv) | (v) | (vi) | (viii) | (ix) | (x) |
1. That in consideration of the sanction of the plans by .................................................... Authority for construction of the basement the executant undertakes that he/she shall at all times keep .................................................... Authority free from any liability, loss or damages/flowing from any injury or damage caused to the adjoining built up properties or to any person as a consequence of the construction of at the time of digging of its foundations or during the course of its construction or at any time thereafter.
2. The owner agreed and undertakes that in the event of any claim being made by any person or persons against the concerned Authority either in respect of the sanction granted by the concerned Authority to the owner for the construction of basement or in respect of the construction or manner of construct ion of the basement .by the owner of the consequences flowing from the said sanction the executant shall be responsible and liable and not .................................................... Authority.
3. The executant agrees and undertake to indemnify the concerned Authority fully in respect of any amount which the concerned Authority may be required to pay to any person either by way of compensation or on any other account as a result of any claim or suit or any other proceedings concerning the sanctioning of the construction of the basement of the making there of and also in respect of the costs and expenses which the concerned Authority may incur on defending any action.
4. Without prejudice to the above undertaking the executant hereby binds itself to pay to .................................................... Authority to the full extent any amount which .................................................... Authority may be required to pay to any person in connection with relating to or concerning the sanctioning or the basement o the making thereof.
5. The owner agrees and undertakes that this bond shall remain in full force and effect till the executant faithfully observes/performs the undertaking here in before contained. In witness where of the executant above named has signed this bond on this .................................................... of .................................................... at .................................................... day
IndemnifierName and Signature of Owner/Builder/ApplicantRegistration no.Phone/Mobile no.-Date:Address:Witness:| 1. Name.............................................. |
| Full Address............................................ |
| Date.............................................. |
| (Signatures) |
| 2. Name.................................................. |
| Full Address.............................................. |
| Date.................................................. |
| (Signatures) |
1. That I am the Owner/Power of Attorney Holder of land having R.S./M.S. Plot No. ........................................................................... khata No. ........................................................................... Khewat No. ........................................................................... Thana No. ........................................................................... corresponding to holding No. ........................................................................... Ward No. ........................................................................... of name of the Authority ..........................................................................., measuring an area of ........................................................................... situated at Village/Mauza ........................................................................... P.S.Name of the Place ...........................................................................
2. That the land mentioned above is a freehold property and does not belong to Khas Mahal Estate of Government. It is not either Gair Mazarua Aam Khas, Kaisare Hind, District Board or Acquired Land.
3. That the land stated above is a tribal land/not a tribal land for tribal land; permission for transfer has been obtained vide Case No. Year from SAR/DC/Commissioner Court.
4. That I have applied a building Plan vide B.C. Case No.................................
5. That further declare that in future, if it will be found that property mentioned above are Gair Mazarua Aam Khas, Kaisare Hind, District Board or Acquired Land property of Government the sanctioned map will be deemed to be cancelled due to misrepresentation and suppression of facts.
Sworn & Signed this Affidavit on this the ........................................................................... day of 200 ........................................................................... at Name of the place ...........................................................................DeponentIdentified by :(Advocate, Name of the place ........................................)Form-XIVCertificate of Undertaking for Hazard Safety RequirementTo,REF:- Proposed work of ............................................................ (Title of project) C.S.No./R.S.No in ward No. ............................................................ at village/Mauza ............................................................ Scheme No ............................................................ of ............................................................ village/Town/City ............................................................1. Certified that the building plans submitted for approval will satisfy the safety requirements as stipulated under Building Bye-laws 59 and the information given there in is factually correct to the best of our knowledge and understanding .
2. It also certified that the structural design including safety from hazards based on soil conditions shall be duly incorporated in the design of the building and these provisions shall be adhered to during the construction as per Annexure-IX & X.
| (ii) Engineer/Structural Engineer:- | |
| NameEmpanelment No:Signature with date | |
| (iii) Builder/Owner/Applicant | |
| Name:Registration no.Signature with date | |